View larger
PLC-2RPT-24DC/1 2901639 PHOENIX CONTACT Relay Module
PLC-2RPT-24DC/1
2901639
PHOENIX CONTACT
10 Pcs.
Automation > Switching relay
Industrial Relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact Relay Module designated as PLC-2RPT-24DC/1 provides modular signal conditioning and galvanic isolation within automated industrial architectures. Industrial control systems rely on such interface modules to protect sensitive controllers from voltage spikes and to adapt varying signal levels between field sensors and processing units. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product type: Relay Module
- Product family: PLC-INTERFACE
- Application: two integrated relays
- Operating mode: 100% operating factor
- Mechanical service life: 2x 10 7 cycles
- Data management status Date of last data management: 16.09.2024
- Article revision: 08
- Overvoltage category: III
- Pollution degree: 2
- Maximum power dissipation for nominal condition: 0.17 W
- Test voltage (Winding/contact): 3 kV AC (50 Hz, 1 min., winding/contact)
- Test voltage (Contact/contact): 3 kV AC (50 Hz, 1 min., contact/contact)
- Rated surge voltage: 4 kV
- Coil side Nominal input voltage U N: 24 V DC
- Input voltage range: 18 V DC ... 33.6 V DC (20 °C)
- Drive and function: monostable
More info
▲| Product type | Relay Module |
| Product family | PLC-INTERFACE |
| Application | two integrated relays |
| Operating mode | 100% operating factor |
| Mechanical service life | 2x 107cycles |
| Data management status | |
| Date of last data management | 16.09.2024 |
| Article revision | 08 |
| Insulation characteristics: Air clearances and creepage distances between the power circuits | |
| Insulation | Basic insulation |
| Overvoltage category | III |
| Pollution degree | 2 |
| Maximum power dissipation for nominal condition | 0.17 W |
| Test voltage (Winding/contact) | 3 kV AC (50 Hz, 1 min., winding/contact) |
| Test voltage (Contact/contact) | 3 kV AC (50 Hz, 1 min., contact/contact) |
| Air clearances and creepage distances between the power circuits | |
| Rated insulation voltage | 250 V AC |
| Rated surge voltage | 4 kV |
| Coil side | |
| Nominal input voltage UN | 24 V DC |
| Input voltage range | 18 V DC ... 33.6 V DC (20 °C) |
| Drive and function | monostable |
| Drive (polarity) | polarized |
| Typical input current at UN | 7 mA |
| Typical response time | 4 ms |
| Typical release time | 6 ms |
| Protective circuit | Reverse polarity protection; Polarity protection diode |
| Surge protection; Freewheeling diode | |
| Operating voltage display | Yellow LED |
| Switching | |
| Contact switching type | 2 N/O contacts |
| Type of switch contact | Single contact |
| Note regarding the switch contact | two integrated relays |
| Contact material | AgNi |
| Maximum switching voltage | 250 V AC |
| 30 V DC | |
| Minimum switching voltage | 24 V AC/DC |
| Limiting continuous current | 3.5 A |
| Maximum inrush current | 5 A |
| Min. switching current | 5 mA |
| Interrupting rating (ohmic load) max. | 84 W (at 24 V DC) |
| 24 W (at 48 V DC) | |
| 24 W (at 60 V DC) | |
| 31 W (at 110 V DC) | |
| 46 W (at 220 V DC) | |
| 875 VA (for 250 V AC) | |
| Connection method | Push-in connection |
| Stripping length | 10 mm |
| Conductor cross section rigid | 0.14 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
| 0.2 mm² ... 2.5 mm² (Single ferrule) | |
| 2x 0.5 mm² ... 1 mm² (TWIN ferrule) | |
| Conductor cross section AWG | 26 ... 14 |
| Width | 6.2 mm |
| Height | 80 mm |
| Depth | 94 mm |
| Color | gray (RAL 7042) |
| Flammability rating according to UL 94 | V0 (Housing) |
| Ambient conditions | |
| Degree of protection (Relay base) | IP20 (Relay base) |
| Ambient temperature (operation) | -20 °C ... 60 °C |
| Ambient temperature (storage/transport) | -20 °C ... 60 °C |
| CE | |
| Certificate | CE-compliant |
| Corrosive gas test | |
| Identification | ISA-S71.04. G3 Harsh Group |
| EN 60068-2-60 | |
| Electromagnetic compatibility | Conformance with EMC directive |
| Low Voltage Directive | Conformance with Low Voltage Directive |
| Air clearances and creepage distances between the power circuits | |
| Standards/regulations | IEC 60664 |
| EN 50178 | |
| Mounting type | DIN rail mounting |
| Assembly note | in rows with zero spacing |
| Mounting position | any |