View larger
EMG 17-REL/KSR-W230/21-21-LCAU 2941468 PHOENIX CONTACT Relay Module
EMG 17-REL/KSR-W230/21-21-LCAU
2941468
PHOENIX CONTACT
1 Pcs.
Automation > Switching relay
Industrial Relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
EMG 17-REL/KSR-W230/21-21-LCAU 2941468 PHOENIX CONTACT Relay Module provides complete interface isolation and signal amplification between sensitive electronic controllers and heavy-duty industrial switching elements.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Type of electric connection (EF003961): Screw connection
- Complete with socket (EF003359): Yes
- With detachable clamps (EF003340): No
- With LED indication (EF005950): Yes
- Rated control supply voltage AC 50 Hz (EF003978): 184 V
- Rated control supply voltage AC 60 Hz (EF003979): 184 V
- Voltage type for actuating (EF008242): AC
- Drive, polarization (EF003355): Polarized
- Drive, switching attitude (EF003356): Mono stable
- Number of contacts as normally closed contact (EF008255): 0
- Number of contacts as normally open contact (EF008256): 0
- Number of contacts as change-over contact (EF008257): 2
- Type of switch contact (EF003358): Single contact
- With forced-guided contacts (EF003357): No
- Material of contact surface (EF004020): Gold
- Nominal current (EF000001): 0.004 A
More info
▲Key Commercial Data
| Orderkey | 2941468 |
|---|---|
| Packing unit | 10 pc |
| Catalog page | Page 135 (IF-2011) |
| GTIN | 4017918080464 |
| Weight per Piece (excluding packing) | 56.370 g |
| Custom tariff number | 85364190 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -20 °C ... 40 °C |
|---|---|
| Ambient temperature (storage/transport) | -20 °C ... 70 °C |
Coil side
| Nominal input voltage UN | 230 V AC |
|---|---|
| Input voltage range in reference to UN | 0.85 ... 1.1 |
| Mains frequency | 50/60 Hz |
| Typical input current at UN | 4 mA |
| Typical response time | 7 ms |
| 3 ms ... 12 ms | |
| Typical release time | 3 ms |
| Typical release time range | 2 ms ... 9 ms |
| Operating voltage display | Glow lamp |
| Power dissipation for nominal condition | 0.92 W |
Contact side
| Contact type | Single contact, 2-PDT |
|---|---|
| Type of switch contact | Single contact |
| Contact material | AgNi, hard gold-plated |
| Maximum switching voltage | 30 V AC |
| 36 V DC | |
| Maximum inrush current | 0.2 A |
| Limiting continuous current | 50 mA |
| Interrupting rating (ohmic load) max. | 1.2 W (at 24 V DC) |
Contact side (with destroyed gold layer)
| Note | the following values are applicable if a gold layer is destroyed |
|---|---|
| Maximum switching voltage | 250 V AC/DC |
| Limiting continuous current | 5 A |
| Maximum inrush current | 6 A |
| Interrupting rating (ohmic load) max. | 120 W (at 24 V DC) |
| 95 W (at 48 V DC) | |
| 60 W (at 60 V DC) | |
| 40 W (at 110 V DC) | |
| 55 W (at 220 V DC) | |
| 1250 VA (for 250 V AC) |
General
| Note | Only available as AC voltage version. |
|---|---|
| Test voltage relay winding/relay contact | 4 kV AC (50 Hz, 1 min.) |
| Test voltage relay contact/relay contact | 1 kV AC (50 Hz, 1 min.) |
| Operating mode | 100% operating factor |
| Mechanical service life | approx. 5x 107cycles |
| Mounting position | any |
| Assembly instructions | In rows with zero spacing |
| Net weight (SAP) | 56.37 g |
Connection data input side
| Connection name | Coil side |
|---|---|
| Connection method | Screw connection |
| Stripping length | 8 mm |
| Screw thread | M3 |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 12 |
Connection data output side
| Connection name | Contact side |
|---|---|
| Connection method | Screw connection |
| Stripping length | 8 mm |
| Screw thread | M3 |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 12 |
Standards and Regulations
| Connection in acc. with standard | CUL |
|---|---|
| Designation | Air clearances and creepage distances between the power circuits |
| Standards/regulations | EN 50178 |
| Rated insulation voltage | 260 V AC |
| Rated surge voltage | 2.3 kV |
| Insulation | Basic insulation |
| Safe isolation, reinforced insulation, and 6 kV between input circuit and output contact current paths | |
| Degree of pollution | 2 |
| Overvoltage category | II |
| Designation | Air clearances and creepage distances between input and contact circuit (or output contact current path) |
| Standards/regulations | EN 50178 |
| Rated insulation voltage | 260 V AC |
| Rated surge voltage | 6 kV |
| Insulation | Safe isolation, reinforced insulation |
| Degree of pollution | 2 |
| Overvoltage category | III |
| Designation | Standards/regulations |
| Standards/regulations | EN 61810-1 |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |