Safety relay with forced conduction contacts according to DIN EN 61810-3, contact switching type 2 switches. The requirements for type A according to DIN EN 61810-3 are met if the connection is made as 1 normally open contact/1 normally closed contact. Safety relay with force-guided contacts in accordance with DIN EN 61810-3, contact switching type: 2 changeover contacts. The requirements for type A in accordance with DIN EN 61810-3 are satisfied if the circuit is designed as 1 N/O contact / 1 N/C contact.

Automation > Switching relay
Industrial Relays

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

The Phoenix Contact REL-SR-24DC/2X21/FG X safety relay is a specialized switching device designed for fail-safe monitoring circuits in industrial safety machinery. Safety relays enforce reliable fault detection and ensure that hazardous equipment ceases operation immediately when a protective circuit is interrupted.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • General: The outputs are not suitable for switching different outer conductors.
  • Product type: Single relay
  • Application: Forcibly guided contacts
  • Operating mode: 100% operating factor
  • Mechanical service life: approx. 10 7 cycles
  • Overvoltage category: III
  • Pollution degree: 2
  • Overvoltage category: III
  • Pollution degree: 2
  • Maximum power dissipation for nominal condition: 0.7 W
  • Test voltage (Winding/contact): 4 kV rms (50 Hz, 1 min.)
  • Test voltage (): 1.5 kV rms (50 Hz, 1 min.)
  • Test voltage (Changeover contact/changeover contact): 2.5 kV rms (50 Hz, 1 min.)
  • Rated surge voltage: 4 kV
  • Rated surge voltage: 6 kV
  • Coil side Nominal input voltage U N: 24 V DC

More info

▲
Technical data

Notes
GeneralThe outputs are not suitable for switching different outer conductors.
GeneralAt least a basic level of insulation is maintained against adjacent modules in the DIN rail direction. If the application has higher requirements on the insulation (reinforced insulation), then these must be realized through suitable measures (e.g. partition plates).

Product properties
Product typeSingle relay
ApplicationForcibly guided contacts
Operating mode100% operating factor
Mechanical service lifeapprox. 107cycles
Insulation characteristics: Air clearances and creepage distances between the power circuits
InsulationBasic insulation
Overvoltage categoryIII
Pollution degree2
Insulation characteristics: Air clearances and creepage distances between coil and contact side
InsulationReinforced insulation
Overvoltage categoryIII
Pollution degree2

Electrical properties
Maximum power dissipation for nominal condition0.7 W
Test voltage (Winding/contact)4 kVrms(50 Hz, 1 min.)
Test voltage ()1.5 kVrms(50 Hz, 1 min.)
Test voltage (Changeover contact/changeover contact)2.5 kVrms(50 Hz, 1 min.)
Air clearances and creepage distances between the power circuits
Rated insulation voltage250 V AC
Rated surge voltage4 kV
Air clearances and creepage distances between coil and contact side
Rated insulation voltage250 V AC
Rated surge voltage6 kV

Input data
Coil side
Nominal input voltage UN24 V DC
Input voltage range19.2 V DC ... 26.4 V DC
Input voltage range in reference to UNsee diagram
Drive and functionmonostable
Drive (polarity)non-polarized
Typical input current at UN30 mA
Input power dissipation for UN0.72 W
Typical response time15 ms
Typical release time10 ms
Coil voltage24 V DC
Protective circuitFreewheeling diode
Status displayYellow LED

Output data
Switching
Contact switching type2 changeover contacts, forcibly actuated
Type of switch contactSingle contact
Contact materialAgSnO
Maximum switching voltage250 V AC/DC
Limiting continuous current6 A
Interrupting rating (ohmic load) max.144 W (24 V DC)
58 W (48 V DC)
60 V DC
54 W (110 V DC)
55 W (220 V DC)
1500 VA (250 V AC)
Force-guided contacts in accordance with EN 61810-3Type B

Connection data
Cross section AWG(converted acc. to IEC)

Dimensions
Width12.6 mm
Height29 mm
Depth26.3 mm

Environmental and real-life conditions
Ambient conditions
Degree of protection (Relay)RT II (Relay)
Degree of protection (Installation location)IP54 (Installation location)
Ambient temperature (operation)-25 °C ... 60 °C
Ambient temperature (storage/transport)-25 °C ... 85 °C
Altitude≤ 2000 m

Standards and regulations
Standards/regulationsEN 61810-1
EN 61810-3
Air clearances and creepage distances between the power circuits
Standards/regulationsEN 60947-5-1
Air clearances and creepage distances between coil and contact side
Standards/regulationsEN 60947-5-1

Mounting
Mounting typePlug-in mounting
Assembly instructionsin rows with zero spacing