PHOENIX CONTACT REL-MR-12DC/21-21/C1D2 REL-MR-12DC/21-21/C1D2 2906988 PHOENIX CONTACT Single relay View larger
Images are for illustrative purposes only. Please refer to data sheet for details

REL-MR-12DC/21-21/C1D2 2906988 PHOENIX CONTACT Single relay

REL-MR-12DC/21-21/C1D2

2906988

PHOENIX CONTACT

10 Pcs.

Single relay Plug-in miniature power relay, RT III sealed with power contacts, 2 switched contacts, input voltage: 12 V DC, in combination with the corresponding PLC socket approved according to ATEX/IECEx (zone 2) and Ex zone class I, div. 2. Plug-in miniature power relay, RT III sealed with power contacts, 2 changeover contacts, input voltage: 12 V DC, in connection with the corresponding PLC base approved in accordance with ATEX/IECEx (zone 2) and Ex zone class I, div. 2.

Automation > Switching relay
Industrial Relays

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

The Phoenix Contact REL-MR-12DC/21-21/C1D2 2906988 PHOENIX CONTACT Single relay functions as a core electromechanical switching unit designed to handle electrical load management within automated manufacturing installations. Single relays provide dependable circuit isolation and switching capabilities for general automation needs.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Product type: Single relay
  • Operating mode: 100% operating factor
  • Mechanical service life: 3x 10 7 cycles
  • Data management status Date of last data management: 02.05.2024
  • Article revision: 01
  • Insulation characteristics Insulation: Basic insulation
  • Overvoltage category: III
  • Pollution degree: 3
  • Service life electrical: see diagram
  • Maximum power dissipation for nominal condition: 0.4 W
  • Test voltage (Winding/contact): 5 kV AC (50 Hz, 1 min., winding/contact)
  • Test voltage (Contact/contact): 2.5 kV AC (50 Hz, 1 min., contact/contact)
  • Coil side Nominal input voltage U N: 12 V DC
  • Input voltage range: 9.4 V DC ... 29.8 V DC
  • Input voltage range in reference to U N: see diagram
  • Drive and function: monostable

More info

▲
Technical data

Product properties
Product typeSingle relay
Operating mode100% operating factor
Mechanical service life3x 107cycles
Data management status
Date of last data management02.05.2024
Article revision01
Insulation characteristics
InsulationBasic insulation
Overvoltage categoryIII
Pollution degree3

Electrical properties
Service life electricalsee diagram
Maximum power dissipation for nominal condition0.4 W
Test voltage (Winding/contact)5 kV AC (50 Hz, 1 min., winding/contact)
Test voltage (Contact/contact)2.5 kV AC (50 Hz, 1 min., contact/contact)

Input data
Coil side
Nominal input voltage UN12 V DC
Input voltage range9.4 V DC ... 29.8 V DC
Input voltage range in reference to UNsee diagram
Drive and functionmonostable
Drive (polarity)non-polarized
Typical input current at UN33 mA
Typical response time7 ms
Typical release time3 ms
Coil resistance360 Ω ±10 % (at 20 °C)

Output data
Switching
Contact switching type2 changeover contacts
Type of switch contactSingle contact
Contact materialAgNi
Maximum switching voltage250 V AC/DC
Minimum switching voltage5 V (at 10 mA)
Limiting continuous current8 A
Maximum inrush current25 A (20 ms)
Min. switching current10 mA (At 5 V)
Interrupting rating (ohmic load) max.190 W (at 24 V DC)
85 W (at 48 V DC)
60 W (at 60 V DC)
44 W (at 110 V DC)
60 W (at 220 V DC)
2000 VA (for 250 V AC)
Switching capacity2 A (at 24 V, DC13)
0.2 A (at 250 V, DC13)
3 A (at 24 V, AC15)
3 A (at 120 V, AC15)
3 A (at 250 V, AC15)

Connection data
Connection methodPlug / solder connection

Dimensions
Dimensional drawing
Width12.7 mm
Height29 mm
Depth15.7 mm

Material specifications
Colororange (RAL 2003)

Environmental and real-life conditions
Ambient conditions
Degree of protectionRT III
Ambient temperature (operation)-40 °C ... 85 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C

Approvals
Corrosive gas test
IdentificationISA-S71.04. G3 Harsh Group
EN 60068-2-60

Standards and regulations
Standards/regulationsIEC 60664
EN 50178

Mounting
Assembly noteCan be aligned without spacing (> 70 °C ≥ 2.5 mm)
Mounting positionany