Phoenix Contact REL-IR4/DP-220DC/4X21 is a single relay engineered for continuous operation in complex electrical distribution and automation architectures. Control relays serve to multiply contacts, isolate sensitive electronics from high-voltage transients, and execute logic switching routines. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product type: Single relay
- Operating mode: 100% operating factor
- Mechanical service life: approx. 2x 10 7 cycles
- Data management status Date of last data management: 02.05.2024
- Article revision: 03
- Insulation characteristics Insulation: Basic insulation
- Overvoltage category: II
- Pollution degree: 2
- Service life electrical: see diagram
- Maximum power dissipation for nominal condition: 0.88 W
- Test voltage (Winding/contact): 2.5 kV rms (50 Hz, 1 min., winding/contact)
- Test voltage (Changeover contact/changeover contact): 2 kV rms (50 Hz, 1 min., changeover contact/changeover contact)
- Rated insulation voltage: 250 V AC
- Rated surge voltage: 2.5 kV
- Coil side Nominal input voltage U N: 220 V DC
- Input voltage range: 171.6 V DC ... 429 V DC
More info
▲| Product type | Single relay |
| Operating mode | 100% operating factor |
| Mechanical service life | approx. 2x 107cycles |
| Data management status | |
| Date of last data management | 02.05.2024 |
| Article revision | 03 |
| Insulation characteristics | |
| Insulation | Basic insulation |
| Overvoltage category | II |
| Pollution degree | 2 |
| Service life electrical | see diagram |
| Maximum power dissipation for nominal condition | 0.88 W |
| Test voltage (Winding/contact) | 2.5 kVrms(50 Hz, 1 min., winding/contact) |
| Test voltage (Changeover contact/changeover contact) | 2 kVrms(50 Hz, 1 min., changeover contact/changeover contact) |
| Rated insulation voltage | 250 V AC |
| Rated surge voltage | 2.5 kV |
| Coil side | |
| Nominal input voltage UN | 220 V DC |
| Input voltage range | 171.6 V DC ... 429 V DC |
| Input voltage range in reference to UN | see diagram |
| Drive and function | monostable |
| Drive (polarity) | polarized |
| Typical input current at UN | 4 mA |
| Non-operate voltage | ≤ 132 V DC |
| Safe operate voltage | ≥ 176 V DC |
| Typical response time | 13 ms |
| Typical release time | 14 ms |
| Protective circuit | Freewheeling diode |
| Status display | no |
| Switching | |
| Contact switching type | 4 changeover contacts |
| Type of switch contact | Single contact |
| Contact material | AgNi |
| Maximum switching voltage | 250 V AC/DC |
| Minimum switching voltage | 5 V (At 24 mA) |
| Limiting continuous current | 6 A |
| Min. switching current | 5 mA (at 24 V) |
| Interrupting rating (ohmic load) max. | 144 W (at 24 V DC) |
| 124 W (at 48 V DC) | |
| 108 W (at 60 V DC) | |
| 52 W (at 110 V DC) | |
| 48 W (at 220 V DC) | |
| 1500 VA (for 250 V AC) | |
| Switching capacity | 2 A (at 24 V, DC13) |
| 1 A (at 230 V, AC15) | |
| Connection method | Plug-in connection |
| Width | 21.2 mm |
| Height | 27.5 mm |
| Depth | 35.6 mm |
| Ambient conditions | |
| Degree of protection | RT I |
| Ambient temperature (operation) | 70 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Corrosive gas test | |
| Identification | ISA-S71.04. G3 Harsh Group |
| EN 60068-2-60 | |
| Standards/regulations | IEC 60664 |
| IEC 61810 |
| Mounting position | any |