View larger
REL-FO/L-230AC/1X21 1308317 PHOENIX CONTACT Plug-in miniature relay, FASTON connection, 1 switch, status ind..
REL-FO/L-230AC/1X21
1308317
PHOENIX CONTACT
10 Pcs.
Automation > Switching relay
Industrial Relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Utilized for galvanic isolation and signal multiplication, a Phoenix Contact Plug-in miniature relay bridges the gap between low-power control electronics and higher-voltage field loads. These electromechanical devices ensure safe and dependable switching cycles inside modern control systems.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product type: Single relay
- Product family: ESSENTIAL edition
- Operating mode: 100% operating factor
- Mechanical service life: approx. 3x 10 7 cycles
- Relay type: Electromechanical relay
- Overvoltage category: II
- Pollution degree: 3
- Maximum power dissipation for nominal condition: 0.9 W
- Test voltage (Winding/contact): 5 kV rms (50 Hz, 1 min., winding/contact)
- Test voltage (): 1 kV rms (50 Hz, 1 min., open contact)
- Rated surge voltage: 2.5 kV
- Coil side Nominal input voltage U N: 230 V AC
- Input voltage range: 184 V AC ... 253 V AC
- Mains frequency: 50/60 Hz
- Drive and function: monostable
- Drive (polarity): non-polarized
More info
▲| General | Do not use to separate SELV/PELV circuits from other circuits, because safe isolation is not guaranteed. (applies to the optocoupler variants) |
| General | The system installer must ensure the touch protection of the product (at voltages > 25 V AC/60 V DC). The product is a built-in device without protection against direct contact. |
| Product type | Single relay |
| Product family | ESSENTIAL edition |
| Operating mode | 100% operating factor |
| Mechanical service life | approx. 3x 107cycles |
| Relay type | Electromechanical relay |
| Insulation characteristics: Air clearances and creepage distances between the power circuits | |
| Insulation | Basic insulation |
| Overvoltage category | II |
| Pollution degree | 3 |
| Maximum power dissipation for nominal condition | 0.9 W |
| Test voltage (Winding/contact) | 5 kVrms(50 Hz, 1 min., winding/contact) |
| Test voltage () | 1 kVrms(50 Hz, 1 min., open contact) |
| Air clearances and creepage distances between the power circuits | |
| Rated insulation voltage | 250 V AC |
| Rated surge voltage | 2.5 kV |
| Coil side | |
| Nominal input voltage UN | 230 V AC |
| Input voltage range | 184 V AC ... 253 V AC |
| Mains frequency | 50/60 Hz |
| Drive and function | monostable |
| Drive (polarity) | non-polarized |
| Typical input current at UN | 4.5 mA (50 Hz) |
| Input power dissipation for UN | 1 W |
| Typical response time | 2 ms ... 15 ms |
| Typical release time range | 5 ms ... 20 ms |
| Status display | Yellow LED |
| Coil resistance | 24100 Ω ±10 % |
| Switching | |
| Contact switching type | 1 changeover contact |
| Type of switch contact | Single contact |
| Contact material | AgSnO |
| Maximum switching voltage | 250 V AC/DC |
| Minimum switching voltage | 5 V (100 mA) |
| Limiting continuous current | 12 A |
| Maximum inrush current | 24 A (20 ms, N/O contacts) |
| Inrush current, minimum | 100 mA (5 V) |
| Interrupting rating (ohmic load) max. | 288 W (24 V DC) |
| 360 W (30 V DC) | |
| 3000 VA (250 V AC) | |
| Cross section AWG | (converted acc. to IEC) |
| Connection method | FASTON connection |
| Width | 13 mm |
| Height | 31.1 mm |
| Depth | 30 mm |
| Ambient conditions | |
| Degree of protection (Relay) | RT II (Relay) |
| Degree of protection (Installation location) | IP54 (Installation location) |
| Ambient temperature (operation) | -40 °C ... 70 °C |
| Ambient temperature (storage/transport) | -40 °C ... 70 °C |
| Altitude | ≤ 2000 m |
| Standards/regulations | IEC 61810-1 |
| IEC 60664-1 | |
| Air clearances and creepage distances between the power circuits | |
| Standards/regulations | IEC 60664-1 |
| Mounting position | any |