View larger
UNO-DIODE/5-24DC/2X10/1X20 2905489 PHOENIX CONTACT Redundancy module
UNO-DIODE/5-24DC/2X10/1X20
2905489
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection module
Power Supplies (PS)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Phoenix Contact UNO-DIODE/5-24DC/2X10/1X20 is a redundancy module utilized in DC power distribution systems to decouple power supplies and ensure uninterrupted operation. Redundancy modules are vital in critical automation loops where dual power paths are required to prevent downtime in the event of a primary power supply failure. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Voltage type (operating voltage) (EF005294): DC
- Operating voltage DC (EF008208): 4.5 V
- With LED indication (EF005950): No
More info
▲Key Commercial Data
| Orderkey | 2905489 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 267 (C-4-2017) |
| GTIN | 4046356954594 |
| Weight per Piece (excluding packing) | 200.000 g |
| Custom tariff number | 85049091 |
| Country of origin | DE (Germany) |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -25 °C ... 70 °C (> 55 °C Derating: 2.5 %/K) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Degree of pollution | 2 |
Input data
| Nominal input voltage range | 5 V DC ... 24 V DC |
|---|---|
| Input voltage range | 4.5 V DC ... 30 V DC |
| Nominal input current | 2x 10 A (-25 °C ... 55 °C) |
| 1x 20 A (-25 °C ... 55 °C) |
Output data
| Nominal output current (IN) | 20 A |
|---|---|
| Derating | 55 °C ... 70 °C (2.5%/K) |
| Connection in series | No |
| Power loss nominal load max. | 5 W (IOUT= 10 A) |
General
| Net weight | 0.2 kg |
|---|---|
| Efficiency | > 97 % |
| Insulation voltage input/output | 1 kV AC (type test) |
| 0.5 kV AC (routine test) | |
| Protection class | III |
| Degree of protection | IP20 |
| MTBF (IEC 61709, SN 29500) | |
| > 60600000 h (40 °C) | |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| Assembly instructions | alignable: 0 mm horizontally, 30 mm vertically |
Connection data, input
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 14 |
| Stripping length | 8 mm |
| Screw thread | M3 |
Connection data, output
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 14 |
| Stripping length | 8 mm |
| Screw thread | M3 |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Noise immunity | EN 61000-6-2:2005 |
| Connection in acc. with standard | CUL |
| Standards/regulations | EN 61000-4-2 |
| Contact discharge | 4 kV (Test Level 2) |
| Standards/regulations | EN 61000-4-3 |
| Frequency range | 80 MHz ... 1 GHz |
| Test field strength | 10 V/m |
| Frequency range | 1.4 GHz ... 2 GHz |
| Test field strength | 3 V/m |
| Standards/regulations | EN 61000-4-4 |
| Comments | Criterion B |
| Standards/regulations | EN 61000-6-3 |
| EN 61000-4-6 | |
| Frequency range | 0.15 MHz ... 80 MHz |
| Voltage | 10 V (Test Level 3) |
| Standards/regulations | EN 61000-4-11 |
| Low Voltage Directive | Conformance with LV directive 2006/95/EC |
| Standard - Electrical safety | IEC 60950-1/VDE 0805 (SELV) |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
| Standard – Safety extra-low voltage | IEC 60950-1 (SELV) and EN 60204-1 (PELV) |
| UL approvals | UL/C-UL listed UL 508 |
| UL/C-UL Recognized UL 60950-1 | |
| Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Vibration (operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
| 15 Hz ... 150 Hz, 2.3g, 90 min. |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 25; |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |