View larger
PT 2X1-VF-120AC 2859327 PHOENIX CONTACT Surge protection device
PT 2X1-VF-120AC
2859327
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Designed for industrial power and signal applications, the Phoenix Contact PT 2X1-VF-120AC 2859327 serves as a surge protection device to intercept harmful voltage spikes. Engineers deploy these devices in distribution boards and control panels to prevent transient electrical energy from disrupting sensitive hardware. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Nominal voltage DC (EF008799): 120 V
More info
▲Key Commercial Data
| Orderkey | 2859327 |
|---|---|
| Packing unit | 10 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 114 (C-4-2017) |
| GTIN | 4017918974565 |
| Weight per Piece (excluding packing) | 62.140 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Dimensions
| Height | 44.8 mm |
|---|---|
| Width | 17.5 mm |
| Depth | 51.7 mm |
| Horizontal pitch | 1 Div. |
| Complete module height | 90 mm |
| Complete module width | 17.7 mm |
| Complete module depth | 65.5 mm |
General
| Housing material | PA 6.6 |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | black |
| Standards for cearances and creepage distances | IEC 60664-1 |
| DIN VDE 0110-1 | |
| Overvoltage category | III |
| Degree of pollution | 2 |
| Mounting type | DIN rail: 35 mm |
| Type | DIN rail module, two-section, divisible |
| Number of positions | 2 |
| Direction of action | Line-Line & Line-Earth Ground |
| Arrester can be tested with CHECKMASTER from software version: | SW Version 2.13 or later |
Protective circuit
| IEC test classification | C1 |
|---|---|
| C2 | |
| C3 | |
| Nominal voltage UN | 120 V AC |
| Maximum continuous voltage UC | 175 V AC |
| Rated current | 6 A |
| Operating effective current ICat UC | ≤ 2 µA |
| Residual current IPE | ≤ 4 µA |
| Nominal discharge current In(8/20) µs | 3 kA |
| Nominal discharge current In(8/20) µs (line-earth) | 3 kA |
| Pulse discharge current Iimp(10/350) µs | 300 A |
| Total discharge current Itotal(8/20) µs | 8 kA |
| Max. discharge current Imax(8/20) µs | 8 kA |
| Nominal pulse current Ian (10/1000) µs (line-earth) | 40 A |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 800 V |
| Residual voltage at In(line-earth) | ≤ 600 V |
| Residual voltage with Ian (10/1000) µs (line-earth) | ≤ 360 V |
| Energy absorption | 85 J |
| Voltage protection level Up | ≤ 1 kV (C2 - 2 kA) |
| Voltage protection level Up(line-line) | |
| Voltage protection level Up(line-earth) | ≤ 900 V (C1 - 500 A) |
| ≤ 950 V (C2 - 1 kA) | |
| ≤ 1 kV (C3 - 25 A) | |
| ≤ 1.1 kV (Iimp-300 A) | |
| Response time tA | ≤ 100 ns |
| Capacity | typ. 3 pF |
| Resistance in series | 0 Ω |
| Surge protection fault message | none |
| Max. required back-up fuse | 6 A (e.g. D01 gL/gG) |
| Impulse durability (line-earth) | C1 - 1 kV/500 A |
| C2 - 4 kV/2 kA | |
| C3 - 25 A |
Connection data
| Connection method | Screw connection |
|---|---|
| Connection method IN | Screw terminal blocks |
| Connection method OUT | Screw terminal blocks |
| Screw thread | M3 |
| Tightening torque | 0.8 Nm |
| Stripping length | 8 mm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
Remote indication contact
| Switching function | N/C contact |
|---|---|
| Maximum operating voltage Umax.AC | 120 V AC |
| Max. operating current Imax | 3 A |
Standards and Regulations
| Standards/regulations | EN 61643-21 |
|---|---|
| IEC 61643-21 | |
| Standards/specifications | EN 61643-21 2002 |