View larger
PT 2+1-S-48DC/FM 2817958 PHOENIX CONTACT Type 3 surge protection device
PT 2+1-S-48DC/FM
2817958
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for terminal equipment
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Designed for multi-stage instrumentation protection, the Phoenix Contact PT 2+1-S-48DC/FM type 3 surge protection device secures sensitive DC circuits from transient overvoltages. These components mount easily on standard DIN rails within control cabinets to ensure system reliability.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Max. continuous voltage AC (EF004198): 60 V
- Voltage protection level L-N (EF004236): 0.12 kV
- Mounting method (EF000003): DIN rail (top hat rail) 35 mm
- With remote signalling contact (EF000422): Yes
- Signalling at the device (EF004241): Optic
- Category type 3 (EF004231): Yes
- Degree of protection (IP) (EF005474): IP20
More info
▲Key Commercial Data
| Orderkey | 2817958 |
|---|---|
| Packing unit | 10 pc |
| Catalog page | Page 72 (C-4-2017) |
| GTIN | 4017918574987 |
| Weight per Piece (excluding packing) | 63.460 g |
| Custom tariff number | 85363090 |
| Country of origin | DE (Germany) |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -40 °C ... 80 °C |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Permissible humidity (operation) | 5 % ... 95 % |
General
| EN type | T3 |
|---|---|
| Number of ports | One |
| Mode of protection | L-N |
| L-PE | |
| N-PE | |
| (L+) - (L-) | |
| (L+/L-) - PE | |
| Mounting type | DIN rail: 35 mm |
| Color | jet black RAL 9005 |
| Housing material | PA 6.6 |
| Degree of pollution | 2 |
| Flammability rating according to UL 94 | V-0 |
| Type | DIN rail module, two-section, divisible |
| Surge protection fault message | Optical, remote indicator contact |
Protective circuit
| Nominal voltage UN | 48 V DC |
|---|---|
| Maximum continuous voltage UC | 60 V DC |
| Rated load current IL | 26 A (30 °C) |
| Residual current IPE | ≤ 10 µA |
| Nominal discharge current In(8/20) µs | 500 A |
| Combination wave UOC | 1 kV (2 Ω) |
| 6 kV (12 Ω) | |
| Voltage protection level Up | ≤ 120 V |
| Response time tA(L-N) | ≤ 1 ns |
| Response time tA(L-PE) | ≤ 1 ns |
| Short-circuit current rating ISCCR | 200 A (without backup fuse for Uc) |
| Max. backup fuse with branch wiring | 50 A (gG) |
| Maximum backup fuse for through wiring | 25 A (gG) |
Indicator/remote signaling
| Switching function | N/C contact |
|---|---|
| Operating voltage | 7 V DC ... 70 V DC (open collector) |
| Operating current | 5 mA DC ... 15 mA (open collector) |
| Connection method | Screw connection |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
| Screw thread | M3 |
| Tightening torque | 0.8 Nm |
| Stripping length | 8 mm |
Connection data
| Connection method | Screw connection |
|---|---|
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
| Screw thread | M3 |
| Tightening torque | 0.8 Nm |
| Stripping length | 8 mm |