PHOENIX CONTACT RAD-PT100-4-IFS RAD-PT100-4-IFS 2904035 PHOENIX CONTACT I/O extension module View larger
Images are for illustrative purposes only. Please refer to data sheet for details

RAD-PT100-4-IFS 2904035 PHOENIX CONTACT I/O extension module

RAD-PT100-4-IFS

2904035

PHOENIX CONTACT

1 Pcs.

I/O extension module Radioline: I/O expansion module, 4 x Pt 100 inputs (-50 °C ... +250 °C) Radioline I/O Expansion Module, 4 Pt 100 Inputs (-50°C to +250°C)

Automation > Fieldbus, decentr. periphery - analogue I/O module
Safety

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

A Phoenix Contact RAD-PT100-4-IFS I/O extension module is designed to expand wireless or modular automation systems by collecting specialized sensor inputs from industrial equipment. Such expansion units facilitate scalable data acquisition in distributed remote monitoring and control applications.

Pricing, availability, and lead time are confirmed per enquiry through an RFQ.

  • Voltage type (supply voltage) (EF002991): DC
  • Input, current (EF003204): No
  • Input, voltage (EF003205): No
  • Input, resistor (EF003206): No
  • Input, resistance thermometer (EF003207): No
  • Input, thermocouple (EF003208): No
  • Input signal, configurable (EF003209): No
  • Output, current (EF003212): No
  • Output, voltage (EF003213): No
  • Output signal configurable (EF003214): No
  • Number of analogue inputs (EF001994): 0
  • Number of analogue outputs (EF001995): 0
  • Analogue inputs configurable (EF008518): No
  • Analogue outputs configurable (EF008519): No
  • Number of HW-interfaces industrial Ethernet (EF003020): 0
  • Number of interfaces PROFINET (EF006932): 0

More info

▲

Key Commercial Data

Orderkey2904035
Packing unit1 pc
Catalog pagePage 463 (C-6-2017)
GTIN4046356781961
Weight per Piece (excluding packing)217.800 g
Custom tariff number85177000
Country of originDE (Germany)

Note

Utilization restrictionEMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width17.5 mm
Height113 mm
Depth114.5 mm
Dimensional drawing

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 70 °C
-40 °F ... 158 °F
Ambient temperature (storage/transport)-40 °C ... 85 °C
-40 °F ... 185 °F
Permissible humidity (operation)20 % ... 85 %
Permissible humidity (storage/transport)20 % ... 85 %
Altitude2000 m
Vibration (operation)in accordance with IEC 60068-2-6: 5g, 10 Hz ... 150 Hz
Shock16g, 11 ms

General

Overvoltage categoryII
Mounting positionany
Assembly instructionson standard DIN rail NS 35 in accordance with EN 60715
Degree of pollution2
Housing materialPA 6.6-FR
Flammability rating according to UL 94V0
MTTF1249 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day))
506 Years (Telcordia standard, 40°C temperature, 34.25% operating cycle (5 days a week, 12 hours a day))
194 Years (Telcordia standard, temperature 40 °C, operating cycle 100 % (7 days a week, 24 hours a day))

Supply

Supply voltage range19.2 V DC ... 30.5 V DC (DIN rail connector)
Max. current consumption≤ 38 mA (At 24 V DC, at 25°C)
Transient surge protectionYes

Analog inputs

Description of the inputPt 100 input
Number of inputs4
Temperature measuring range-50 °C ... 250 °C
Sensor input current1 mA (constant)
Max. permissible overall conductor resistance25 Ω
Measuring accuracy0.1% (From the measuring range final value)
Connection technology2, 3-wire
Process data channel16 Bit (per channel)

Connection data

Connection methodScrew connection
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.14
Stripping length7 mm
Tightening torque0.6 Nm
Screw threadM3

Status indicator

Status displayGreen LED (supply voltage, PWR)
Green LED (bus communication, DAT)
Red LED (periphery error, ERR)

Standards and Regulations

Electromagnetic compatibilityConformance with EMC Directive 2014/30/EU
Standard designationEMC Directive 2014/30/EU
Standards/regulationsEN 61000-6-2
Standard designationEMC Directive 2014/30/EU
Standards/regulationsEN 61000-6-4
Standard designationEx Directive (ATEX)
Standards/regulationsEN 60079-0
Standard designationEx Directive (ATEX)
Standards/regulationsEN-60079-15
Noise emissionEN 61000-6-4
Noise immunityEN 61000-6-2
Flammability rating according to UL 94V0
Shock16g, 11 ms
Vibration (operation)in accordance with IEC 60068-2-6: 5g, 10 Hz ... 150 Hz
ConformanceCE-compliant
ATEX II 3 G Ex nA IIC T4 Gc
IECExEx nA IIC T4 Gc
UL, USA/CanadaUL 508 Listed
Class I, Div. 2, Groups A, B, C, D T4A
Class I, Zone 2, IIC T4
Noxious gas testISA-S71.04-1985 G3 Harsh Group A

Environmental Product Compliance

REACh SVHCLead 7439-92-1
China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Articles in set

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.