View larger
QUINT4-UPS/24DC/24DC/20/USB 2907072 PHOENIX CONTACT Uninterruptible power supply
QUINT4-UPS/24DC/24DC/20/USB
2907072
PHOENIX CONTACT
1 Pcs.
Automation > UPS
Power Supplies (PS)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Delivering stable backup power to critical instrumentation, the Phoenix Contact QUINT4-UPS/24DC/24DC/20/USB operates as a robust uninterruptible power supply. These modules ensure continuous operation of DC-powered control loops during temporary grid failures.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Input voltage (EF003840): 18 V
- Output voltage (EF003933): 18 V
- USB interface (EF002039): Yes
- With communication interface RS-232 (EF007312): No
- SNMP (EF005284): No
- Voltage type (EF000187): DC
- Height (EF000040): 130 mm
- Width (EF000008): 40 mm
- Depth (EF000049): 125 mm
- Weight (EF000167): 0.51973 kg
More info
▲Key Commercial Data
| Orderkey | 2907072 |
|---|---|
| Packing unit | 1 pc |
| GTIN | 4055626171289 |
| Weight per Piece (excluding packing) | 698.000 g |
| Custom tariff number | 85371091 |
| Country of origin | CN (China) |
Dimensions
| Width | 40 mm |
|---|---|
| Height | 130 mm |
| Depth | 125 mm |
| Width with alternative assembly | 123 mm |
| Height with alternative assembly | 130 mm |
| Depth with alternative assembly | 42 mm |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
| Ambient temperature (start-up type tested) | -40 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
| Climatic class | 3K3 (EN 60721) |
| Degree of pollution | 2 |
| Installation height | ≤ 4000 m |
Input data
| Input voltage | 24 V DC |
|---|---|
| Input voltage range | 18 V DC ... 30 V DC |
| Electric strength, max. | 35 V DC |
| Internal input fuse | no |
| Inrush surge current | ≤ 8 A (≤ 4 ms) |
| Reverse polarity protection | yes |
| Fixed connect threshold | 22 V DC |
| Switch-on time | max. 3 s |
| Voltage drop, input/output | 0.4 V DC |
Output data (general)
| Short-circuit-proof | yes |
|---|---|
| No-load proof | yes |
| Switch-over time | 0 ms |
| UPS connection in parallel | no |
| UPS connection in series | no |
| Energy storage device connection in parallel | Yes, 5 (observe line protection) |
| Energy storage device connection in series | no |
| Efficiency | typ. 98 % |
Output data (mains operation)
| Output voltage range | 18 V DC ... 30 V DC |
|---|---|
| 18 V DC ... 32 V DC | |
| Static Boost (IStat.Boost) | 25 A |
| Dynamic Boost (IDyn.Boost) | 30 A (5 s) |
| Selective Fuse Breaking (ISFB) | 120 A (15 ms) |
Output data (battery operation)
| Output voltage range | 19 V DC ... 32 V DC |
|---|---|
| Static Boost (IStat.Boost) | 25 A |
| Dynamic Boost (IDyn.Boost) | 30 A (5 s) |
| Selective Fuse Breaking (ISFB) | 120 A (15 ms) |
Energy storage (battery)
| Battery technology | VRLA, VRLA-WTR, LI-ION |
|---|---|
| End-of-charge voltage (temperature-compensated) | 25 V DC ... 32 V DC |
| End-of-charge voltage | 32 V DC |
| Max. capacity | 135 Ah |
| Nominal capacity (without additional charger) | 3 Ah ... 100 Ah |
| Charging current (configurable) | 5 A |
| Charging time | 202.5 h |
| Buffer time | 19 min. (12 Ah) |
| Temperature compensation (configurable) | 42 mV/K |
| Charge characteristic curve | IU0U |
| Deep discharge protection | 19.2 V DC |
| Temperature sensor | yes |
| IQ-Technology | yes |
General data
| Inflammability class in acc. with UL 94 (housing / terminal blocks) | V0 |
|---|---|
| MTBF (IEC 61709, SN 29500) | > 1405000 h (25 °C) |
| > 910000 h (40 °C) | |
| > 481200 h (60 °C) | |
| Weight | 0.6 kg |
| Environmental protection directive | RoHS |
| WEEE | |
| Reach |
Connection data, input
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 6 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 4 mm² |
| Single conductor/terminal point, stranded, with ferrule, min. | 0.2 mm² |
| Single conductor/terminal point, stranded, with ferrule, max. | 4 mm² |
| Conductor cross section AWG min. | 30 |
| Conductor cross section AWG max. | 10 |
| Stripping length | 8 mm |
| Tightening torque, min | 0.5 Nm |
| Tightening torque max | 0.6 Nm |
Connection data, output
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 6 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 4 mm² |
| Single conductor/terminal point, stranded, with ferrule, min. | 0.2 mm² |
| Single conductor/terminal point, stranded, with ferrule, max. | 4 mm² |
| Conductor cross section AWG min. | 30 |
| Conductor cross section AWG max. | 10 |
| Stripping length | 8 mm |
| Tightening torque, min | 0.5 Nm |
| Tightening torque max | 0.6 Nm |
Connection data for battery
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 30 |
| Conductor cross section AWG max. | 12 |
| Stripping length | 6.5 mm |
| Tightening torque, min | 0.5 Nm |
| Tightening torque max | 0.6 Nm |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Noise emission | Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply) |
| Noise immunity | Immunity according to EN 61000-6-2 (industrial) |
| Standards/regulations | EN 61000-4-2 |
| Contact discharge | 4 kV (Test Level 2) |
| Standards/regulations | EN 61000-4-3 |
| Frequency range | 80 MHz ... 1 GHz |
| Test field strength | 10 V/m (Test Level 3) |
| Frequency range | 1.4 GHz ... 2 GHz |
| Test field strength | 3 V/m (Test Level 2) |
| Standards/regulations | EN 61000-4-4 |
| Comments | Criterion B |
| Standards/regulations | EN 61000-4-6 |
| Frequency range | 0.15 MHz ... 80 MHz |
| Voltage | 10 V (Test Level 3) |
| Standards/regulations | EN 61000-4-8 |
| Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
| Standard – Safety extra-low voltage | IEC 61010-1 (SELV) |
| IEC 61010-2-201 (PELV) | |
| UL approvals | UL/C-UL Listed UL 61010-1 |
| UL/C-UL Listed UL 61010-2-201 | |
| UL/C-UL Listed ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location) | |
| Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Vibration (operation) | 2.3g |