View larger
QUINT4-UPS/1AC/1AC/1KVA 2320283 PHOENIX CONTACT Uninterruptible power supply
QUINT4-UPS/1AC/1AC/1KVA
2320283
PHOENIX CONTACT
1 Pcs.
Automation > UPS
Power Supplies (PS)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An uninterruptible power supply such as the Phoenix Contact QUINT4-UPS/1AC/1AC/1KVA safeguards industrial control panels and automation networks from unexpected power interruptions. Compact DIN-rail power backups ensure uninterrupted logic execution and data retention during micro-breaks.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Input voltage (EF003840): 90 V
- Output voltage (EF003933): 100 V
- Voltage type (EF000187): AC
- Height (EF000040): 130 mm
- Width (EF000008): 290 mm
- Depth (EF000049): 125 mm
- Weight (EF000167): 5.151 kg
More info
▲Key Commercial Data
| Orderkey | 2320283 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 281 (C-4-2017) |
| GTIN | 4055626244563 |
| Weight per Piece (excluding packing) | 5,530.000 g |
| Custom tariff number | 85371091 |
| Country of origin | DE (Germany) |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -25 °C ... 60 °C (> 50 °C Derating: 2.5 %/K) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C (with charged energy storage device) |
| Max. permissible relative humidity (operation) | ≤ 95 % |
| Climatic class | 3K3 (EN 60721) |
| Degree of pollution | 2 |
| Installation height | ≤ 3000 m (> 2000 m, observe derating) |
Input data
| Nominal input voltage | 100 V AC -10 % / +20 % |
|---|---|
| 110 V AC -10 % / +20 % | |
| 120 V AC -10 % / +20 % | |
| 130 V AC -10 % / +20 % | |
| 200 V AC -20 % / +20 % | |
| 210 V AC -20 % / +20 % | |
| 220 V AC -20 % / +20 % | |
| 230 V AC -20 % / +15 % | |
| 240 V AC -20 % / +10 % | |
| Input voltage range | 90 V AC ... 264 V AC |
| AC frequency range | 45 Hz ... 65 Hz |
| Buffer period | 1 h (38 AH) |
| Permissible backup fuse | B16 230 V AC |
| Power factor (cos phi) | 0.9 |
Output data
| Nominal output voltage | 100 V AC |
|---|---|
| 110 V AC | |
| 120 V AC | |
| 130 V AC | |
| 200 V AC | |
| 210 V AC | |
| 220 V AC | |
| 230 V AC | |
| 240 V AC | |
| Nominal output current (IN) | 7.8 A (100 V AC) |
| 8.1 A (110 V AC) | |
| 8.3 A (120 V AC) | |
| 7.7 A (130 V AC) | |
| 5 A (200 V AC) | |
| 4.8 A (210 V AC) | |
| 4.5 A (220 V AC) | |
| 4.3 A (230 V AC) | |
| 4.2 A (240 V AC) | |
| POWER BOOST (IBoost) | 13 A (120 V AC) |
| 7 A (230 V AC) | |
| Derating | > 50 °C ... 60 °C (2.5%/K) |
| Connection in parallel | Yes, 2 |
| Connection in series | No |
| Maximum power dissipation in no-load condition | typ. 17 W (120 V AC) |
| typ. 25 W (230 V AC) |
General
| Net weight | 5 kg |
|---|---|
| Efficiency | > 92 % (120 V AC) |
| > 94 % (230 V AC) | |
| Protection class | I |
| Degree of protection | IP20 |
| MTBF (IEC 61709, SN 29500) | 217546 h (230 V AC, at 40 °C) |
Connection data, input
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 6 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 4 mm² |
| Conductor cross section AWG min. | 30 |
| Conductor cross section AWG max. | 10 |
| Stripping length | 8 mm |
Connection data, output
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 6 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 4 mm² |
| Conductor cross section AWG min. | 30 |
| Conductor cross section AWG max. | 10 |
| Stripping length | 8 mm |
Connection data for signaling
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 30 |
| Conductor cross section AWG max. | 12 |
| Stripping length | 8 mm |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Noise immunity | Noise immunity according to EN 62040-2-2006 |
| Standards/regulations | EN 61000-4-2 |
| Contact discharge | 4 kV (Test Level 2) |
| Standards/regulations | EN 61000-4-3 |
| Frequency range | 80 MHz ... 1 GHz |
| Test field strength | 10 V/m |
| Standards/regulations | EN 61000-4-4 |
| Comments | Criterion B |
| Standards/regulations | EN 61000-4-6 |
| Frequency range | 0.15 MHz ... 80 MHz |
| Voltage | 10 V |
| Conducted noise emission | EN 62040-02 (Class C2) |
| Standards/regulations | EN 61000-4-8 |
| Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
| UL approvals | UL/C-UL Recognized UL 1778 |
| Shock | 15g in all directions (EN 60068-2-27) |
| Vibration (operation) | 5 Hz ... 100 Hz, 0.7g (EN 60068-2-6) |
| Overvoltage category (EN 60950-1) | II |