View larger
QUINT4-S-ORING/12-24DC/1X40/VP 1043418 PHOENIX CONTACT Active QUINT single redundancy module for DIN rail mo..
QUINT4-S-ORING/12-24DC/1X40/VP
1043418
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection module
Power Supplies (PS)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact QUINT4-S-ORING/12-24DC/1X40/VP active QUINT single redundancy module provides reliable load sharing and decoupling for sensitive 12V to 24V DC industrial power distribution architectures. Active redundancy units minimize power loss and provide visual operational status feedback. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Voltage type (operating voltage) (EF005294): DC
- Operating voltage DC (EF008208): 8 V
- With LED indication (EF005950): Yes
More info
▲Key Commercial Data
| Orderkey | 1043418 |
|---|---|
| Packing unit | 1 |
| Catalog page | Page 305 (C-4-2019) |
| GTIN | 4055626607474 |
| Custom tariff number | 85049090 |
Dimensions
| Width | 32 mm |
|---|---|
| Height | 130 mm |
| Depth | 125 mm |
| Width with alternative assembly | 122 mm |
| Height with alternative assembly | 130 mm |
| Depth with alternative assembly | 35 mm |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -40 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Max. permissible relative humidity (operation) | ≤ 100 % (at 25 °C, non-condensing) |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Degree of pollution | 2 |
| Installation height | ≤ 5000 m (> 2000 m, observe derating) |
Input data
| Nominal input voltage range | 12 V DC ... 24 V DC |
|---|---|
| Input voltage range | 8 V DC ... 27.5 V DC (SELV) |
| Current consumption | 40 A |
| Nominal input current | 40 A (-40 °C ... 60 °C) |
Output data
| Output voltage range | 8 V DC ... 27.5 V DC |
|---|---|
| Nominal output current (IN) | 40 A |
| Static Boost (IStat.Boost) | 45 A |
| Dynamic Boost (IDyn.Boost) | 60 A (5 s) |
| Selective Fuse Breaking (ISFB) | 215 A (15 ms) |
| Derating | 60 °C ... 70 °C (2.5%/K) |
| Connection in series | No |
| Protection against overvoltage at the output (OVP) | ≤ 30 V DC |
| Power loss nominal load max. | 6.5 W (IOUT= 40 A) |
| 6 W (IOUT= 40 A) |
General
| Net weight | 0.4 kg |
|---|---|
| Efficiency | typ. 99 % (12 V DC) |
| typ. 99.2 % (24 V DC) | |
| Protection class | III |
| Degree of protection | IP20 |
| MTBF (IEC 61709, SN 29500) | > 13486000 h (25 °C) |
| > 7314000 h (40 °C) | |
| > 3379000 h (60 °C) | |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| Assembly instructions | alignable: PN≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically alignable: PN<50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom |
Connection data, input
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.5 mm² |
| Conductor cross section solid max. | 16 mm² |
| Conductor cross section flexible min. | 0.5 mm² |
| Conductor cross section flexible max. | 16 mm² |
| Conductor cross section AWG min. | 20 |
| Conductor cross section AWG max. | 6 |
| Stripping length | 10 mm |
| Screw thread | M4 |
Connection data, output
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.5 mm² |
| Conductor cross section solid max. | 16 mm² |
| Conductor cross section flexible min. | 0.5 mm² |
| Conductor cross section flexible max. | 16 mm² |
| Conductor cross section AWG min. | 20 |
| Conductor cross section AWG max. | 6 |
| Stripping length | 10 mm |
| Screw thread | M4 |
Connection data for signaling
| Connection method | Push-in connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 1.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 1.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 16 |
| Stripping length | 8 mm |
Standards
| Standard - Electrical safety | EN 60950-1/VDE 0805 (SELV) |
|---|---|
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
| Standard – Safety extra-low voltage | IEC 60950-1 (SELV) and EN 60204-1 (PELV) |
| Standard - Safe isolation | DIN VDE 0100-410 |
| Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment | EN 50178 |
Conformance/approvals
| UL approvals | UL/C-UL listed UL 508 |
|---|---|
| UL/C-UL Recognized UL 60950-1 | |
| UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) |
EMC data
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
| Conducted noise emission | EN 55016 |
| EN 61000-6-3 (Class B) | |
| Noise emission | EN 55016 |
| EN 61000-6-3 (Class B) | |
| DNV GL conducted interference | Class A |
| Additional text | Area power distribution |
| DNV GL noise radiation | Class B |
| Additional text | Bridge and deck area |
| Electrostatic discharge | EN 61000-4-2 |
| Contact discharge | 8 kV (Test Level 4) |
| Discharge in air | 15 kV (Test Level 4) |
| Electromagnetic HF field | EN 61000-4-3 |
| Frequency range | 80 MHz ... 1 GHz |
| Test field strength | 20 V/m (Test Level 3) |
| Frequency range | 1 GHz ... 6 GHz |
| Test field strength | 10 V/m (Test Level 3) |
| Frequency range | 1 GHz ... 6 GHz |
| Test field strength | 10 V/m (Test Level 3) |
| Comments | Criterion A |
| Fast transients (burst) | EN 61000-4-4 |
| Input | 2 kV (Test Level 4 - asymmetrical) |
| Output | 2 kV (Test Level 4 - asymmetrical) |
| Signal | 2 kV (Test Level 4 - asymmetrical) |
| Comments | Criterion A |
| Input | 1 kV (Test Level 4 - symmetrical) |
| 2 kV (Test Level 4 - asymmetrical) | |
| Output | 1 kV (Test Level 2 - symmetrical) |
| 2 kV (Test Level 3 - asymmetrical) | |
| Signal | 1 kV (Test Level 2 - asymmetrical) |
| Comments | Criterion A |
| I/O/S | asymmetrical |
| Frequency range | 0.15 MHz ... 80 MHz |
| Voltage | 10 V (Test Level 3) |
| Comments | Criterion A |
| Frequency | 16.67 Hz |
| 50 Hz | |
| 60 Hz | |
| Test field strength | 30 A/m |
| Additional text | 60 s |
| Comments | Criterion A |
| Criterion A | Normal operating behavior within the specified limits. |
| Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |