View larger
QUINT4-PS/3AC/24DC/5 2904620 PHOENIX CONTACT Power supply unit
QUINT4-PS/3AC/24DC/5
2904620
PHOENIX CONTACT
1 Pcs.
Automation > DC-power supply
Power Supplies (PS)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Phoenix Contact QUINT4-PS/3AC/24DC/5 power supply unit provides three-phase conversion performance, ensuring uninterrupted direct current delivery for industrial instrumentation. Such DIN-rail supplies are deployed extensively in electrical cabinets to protect automation networks against voltage fluctuations and drops.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Voltage type (supply voltage) (EF002991): AC
- 1st secondary output voltage (EF006792): 24 V
- Max. output current 1 (EF008284): 10 A
- Secondary voltage adjustable (EF007002): Yes
- Nominal value output voltage 1 (EF009393): 24 V
- Nominal value output current 1 (EF009396): 5 A
- Short-circuit-proof (EF007332): Yes
- Rated supply voltage AC 50 Hz (EF007076): 400 V
- Rated supply voltage AC 60 Hz (EF007077): 400 V
- Rated supply voltage DC (EF007078): 260 V
- Output voltage stabilized (EF003092): Yes
- Power consumption (EF000346): 283 VA
- Power output (EF003034): 120 W
- Stabilized (EF005302): Yes
- Type of electric connection (EF003961): Screw connection
- Suitable for rail mounting (EF003972): Yes
More info
▲Key Commercial Data
| Orderkey | 2904620 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 208 (C-4-2017) |
| GTIN | 4046356985369 |
| Weight per Piece (excluding packing) | 850.000 g |
| Custom tariff number | 85044030 |
| Country of origin | TH (Thailand) |
Dimensions
| Width | 36 mm |
|---|---|
| Height | 130 mm |
| Depth | 125 mm |
| Width with alternative assembly | 122 mm |
| Height with alternative assembly | 130 mm |
| Depth with alternative assembly | 39 mm |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
| Ambient temperature (start-up type tested) | -40 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Degree of pollution | 2 |
| Installation height | ≤ 5000 m (> 2000 m, observe derating) |
Input data
| Nominal input voltage range | 3x 400 V AC ... 500 V AC |
|---|---|
| 2x 400 V AC ... 500 V AC | |
| ± 300 V DC | |
| Input voltage range | 3x 400 V AC ... 500 V AC -20 % ... +10 % |
| 2x 400 V AC ... 500 V AC -10 % ... +10 % | |
| ± 300 V DC -25 % ... +30 % | |
| AC frequency range | 50 Hz ... 60 Hz -10 % ... +10 % |
| Discharge current to PE | < 3.5 mA |
| Current consumption | 3x 0.53 A (400 V AC) |
| 3x 0.44 A (480 V AC) | |
| 2x 0.9 A (400 V AC) | |
| 2x 0.66 A (480 V AC) | |
| 3x 0.45 A (500 V AC) | |
| 2x 0.8 A (500 V AC) | |
| Nominal power consumption | 283 VA |
| Inrush surge current | typ. 11 A (at 25 °C) |
| Mains buffering | typ. 34 ms (3x 400 V AC) |
| typ. 50 ms (3x 480 V AC) | |
| Choice of suitable circuit breakers | 3x 6 A (Characteristic B, C or comparable) |
| Type of protection | Transient surge protection |
| Protective circuit/component | Varistor, gas-filled surge arrester |
Output data
| Nominal output voltage | 24 V DC |
|---|---|
| Setting range of the output voltage (USet) | 24 V DC ... 29.5 V DC (constant capacity) |
| Nominal output current (IN) | 5 A |
| Static Boost (IStat.Boost) | 6.25 A |
| Dynamic Boost (IDyn.Boost) | 10 A (5 s) |
| Selective Fuse Breaking (ISFB) | 30 A (15 ms) |
| Derating | > 60 °C (2.5%/K) |
| Connection in parallel | Yes, for redundancy and increased capacity |
| Connection in series | yes |
| Feedback resistance | ≤ 35 V DC |
| Protection against surge voltage on the output | ≤ 32 V DC |
| Control deviation | < 0.5 % (Static load change 10 % ... 90 %) |
| < 2 % (Dynamic load change 10 % ... 90 %, (10 Hz)) | |
| < 0.25 % (change in input voltage ±10 %) | |
| Residual ripple | < 30 mVPP(with nominal values) |
| Output power | 120 W |
| Typical response time | 300 ms (from SLEEP MODE) |
| Maximum power dissipation in no-load condition | < 3 W (400 V AC) |
| < 4 W (480 V AC) | |
| Power loss nominal load max. | < 15 W (400 V AC) |
| < 17 W (480 V AC) |
General
| Net weight | 0.6 kg |
|---|---|
| Efficiency | typ. 89 % (400 V AC) |
| typ. 87.5 % (480 V AC) | |
| Insulation voltage input/output | 4 kV AC (type test) |
| 2.4 kV AC (routine test) | |
| Insulation voltage input / PE | 4 kV AC (type test) |
| 2.4 kV AC (routine test) | |
| Insulation voltage output / PE | 0.5 kV DC (type test) |
| 0.5 kV DC (routine test) | |
| Protection class | I |
| Degree of protection | IP20 |
| MTBF (IEC 61709, SN 29500) | > 1560000 h (25 °C) |
| > 914000 h (40 °C) | |
| > 413000 h (60 °C) | |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| Assembly instructions | alignable: PN≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically alignable: PN<50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom |
Connection data, input
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 6 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 4 mm² |
| Conductor cross section AWG min. | 30 |
| Conductor cross section AWG max. | 10 |
| Stripping length | 8 mm |
Connection data, output
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 30 |
| Conductor cross section AWG max. | 12 |
| Stripping length | 6.5 mm |
Connection data for signaling
| Connection method | Push-in connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 1.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 1.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 16 |
| Stripping length | 8 mm |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Noise emission | Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply) |
| Noise immunity | Immunity according to EN 61000-6-1 (residential), EN 61000-6-2 (industrial), and EN 61000-6-5 (power station equipment zone), IEC/EN 61850-3 (energy supply) |
| Standards/regulations | EN 61000-4-2 |
| Contact discharge | 4 kV (Test Level 2) |
| Standards/regulations | EN 61000-4-3 |
| Frequency range | 80 MHz ... 1 GHz |
| Test field strength | 10 V/m (Test Level 3) |
| Frequency range | 1.4 GHz ... 2 GHz |
| Test field strength | 3 V/m (Test Level 2) |
| Standards/regulations | EN 61000-4-4 |
| Comments | Criterion B |
| Standards/regulations | EN 61000-4-6 |
| Frequency range | 0.15 MHz ... 80 MHz |
| Voltage | 10 V (Test Level 3) |
| Conducted noise emission | EN 55016 EN 61000-6-4 (Class A) |
| Standards/regulations | EN 61000-4-8 |
| EN 61000-4-11 | |
| EN 61000-4-9 | |
| EN 61000-4-12 | |
| EN 61000-4-16 | |
| EN 61000-4-18 | |
| Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
| Standard - Safety of transformers | EN 61558-2-16 (air clearances and creepage distances only) |
| Standard - Electrical safety | IEC 60950-1/VDE 0805 (SELV) |
| Standard - power supply devices for low voltage with DC output | EN 61204-3 |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
| Standard – Safety extra-low voltage | IEC 60950-1 (SELV) |
| EN 60204-1 (PELV) | |
| Standard - Safe isolation | DIN VDE 0100-410 |
| Standard – Limitation of mains harmonic currents | EN 61000-3-2 |
| Shipbuilding approval | DNV GL, PRS, BV, LR, ABS |
| UL approvals | UL Listed UL 508 |
| UL/C-UL Recognized UL 60950-1 | |
| UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) | |
| Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Vibration (operation) | 5 Hz ... 100 Hz resonance search 2.3g, 90 min., resonance frequency 2.3g, 90 min. (according to DNV GL Class C) |
| Approval - requirement of the semiconductor industry with regard to mains voltage dips | SEMI F47-0706; EN 61000-4-11 |
| Rail applications | EN 50121-3-2 |
| Overvoltage category (EN 60950-1) | II (≤ 5000 m) |
| Overvoltage category (EN 61010-1) | II (≤ 5000 m) |
| Overvoltage category (EN 62477-1) | III (≤ 2000 m) |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 25; |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |