View larger
QUINT4-PS/1AC/48DC/5 2904610 PHOENIX CONTACT Power supply unit
QUINT4-PS/1AC/48DC/5
2904610
PHOENIX CONTACT
1 Pcs.
Automation > DC-power supply
Power Supplies (PS)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Phoenix Contact QUINT4-PS/1AC/48DC/5 power supply unit converts standard AC line inputs into regulated direct current to drive automation hardware, sensors, and actuators. Industrial power supplies maintain steady voltage levels to ensure uninterrupted system performance.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Voltage type (supply voltage) (EF002991): AC
- 1st secondary output voltage (EF006792): 48 V
- Max. output current 1 (EF008284): 10 A
- Secondary voltage adjustable (EF007002): Yes
- Nominal value output voltage 1 (EF009393): 48 V
- Nominal value output current 1 (EF009396): 5 A
- Short-circuit-proof (EF007332): Yes
- Rated supply voltage AC 50 Hz (EF007076): 100 V
- Rated supply voltage AC 60 Hz (EF007077): 100 V
- Rated supply voltage DC (EF007078): 110 V
- Output voltage stabilized (EF003092): Yes
- Power consumption (EF000346): 271 VA
- Power output (EF003034): 240 W
- Stabilized (EF005302): Yes
- Type of electric connection (EF003961): Screw connection
- Suitable for rail mounting (EF003972): Yes
More info
▲Key Commercial Data
| Orderkey | 2904610 |
|---|---|
| Packing unit | 1 pc |
| GTIN | 4055626355061 |
| Weight per Piece (excluding packing) | 1,117.800 g |
| Custom tariff number | 85044030 |
| Country of origin | TH (Thailand) |
Dimensions
| Width | 50 mm |
|---|---|
| Height | 130 mm |
| Depth | 125 mm |
| Width with alternative assembly | 122 mm |
| Height with alternative assembly | 130 mm |
| Depth with alternative assembly | 53 mm |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
| Ambient temperature (start-up type tested) | -40 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Degree of pollution | 2 |
| Installation height | ≤ 5000 m (> 2000 m, observe derating) |
Input data
| Nominal input voltage range | 100 V AC ... 240 V AC |
|---|---|
| 110 V DC ... 250 V DC | |
| Input voltage range | 100 V AC ... 240 V AC -15 % ... +10 % |
| 110 V DC ... 250 V DC -18 % ... +40 % | |
| Dielectric strength maximum | 300 V AC 60 s |
| AC frequency range | 50 Hz ... 60 Hz -10 % ... +10 % |
| Discharge current to PE | < 3.5 mA |
| Current consumption | 3.4 A (100 V AC) |
| 2.8 A (120 V AC) | |
| 1.5 A (230 V AC) | |
| 1.5 A (240 V AC) | |
| Nominal power consumption | 271 VA |
| Inrush surge current | typ. 16.1 A (at 25 °C) |
| Mains buffering | typ. 43 ms (120 V AC) |
| typ. 43 ms (230 V AC) | |
| Input fuse | 8 A (slow-blow, internal) |
| Choice of suitable circuit breakers | 10 A ... 16 A (Characteristic B, C, D, K or comparable) |
| Type of protection | Transient surge protection |
| Protective circuit/component | Varistor, gas-filled surge arrester |
Output data
| Nominal output voltage | 48 V DC |
|---|---|
| Setting range of the output voltage (USet) | 48 V DC ... 56 V DC (constant capacity) |
| Nominal output current (IN) | 5 A |
| Static Boost (IStat.Boost) | 6.25 A |
| Dynamic Boost (IDyn.Boost) | 10 A (5 s) |
| Selective Fuse Breaking (ISFB) | 30 A (15 ms) |
| Derating | > 60 °C (2.5%/K) |
| Connection in parallel | Yes, for redundancy and increased capacity |
| Connection in series | yes |
| Feedback resistance | ≤ 60 V DC |
| Control deviation | < 0.5 % (Static load change 10 % ... 90 %) |
| < 4 % (Dynamic load change 10 % ... 90 %, (10 Hz)) | |
| < 0.25 % (change in input voltage ±10 %) | |
| Residual ripple | < 80 mVPP(with nominal values) |
| Output power | 240 W |
| Typical response time | 300 ms (from SLEEP MODE) |
| Maximum power dissipation in no-load condition | < 3 W (120 V AC) |
| < 3 W (230 V AC) | |
| Power loss nominal load max. | < 19 W (120 V AC) |
| < 16 W (230 V AC) |
General
| Net weight | 1 kg |
|---|---|
| Efficiency | typ. 92.3 % (120 V AC) |
| typ. 93.5 % (230 V AC) | |
| Insulation voltage input/output | 4 kV AC (type test) |
| 2 kV AC (routine test) | |
| Insulation voltage input / PE | 3.5 kV AC (type test) |
| 2.4 kV AC (routine test) | |
| Insulation voltage output / PE | 0.5 kV DC (type test) |
| 0.5 kV DC (routine test) | |
| Protection class | I |
| Degree of protection | IP20 |
| MTBF (IEC 61709, SN 29500) | > 1242000 h (25 °C) |
| > 784000 h (40 °C) | |
| > 374000 h (60 °C) | |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| Assembly instructions | alignable: PN≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically alignable: PN<50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom |
Connection data, input
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 14 |
| Stripping length | 6.5 mm |
Connection data, output
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 14 |
| Stripping length | 6.5 mm |
Connection data for signaling
| Connection method | Push-in connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 1.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 1.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 16 |
| Stripping length | 8 mm |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Standard - Safety of transformers | EN 61558-2-16 (air clearances and creepage distances only) |
| Standard - Electrical safety | IEC 60950-1/VDE 0805 (SELV) |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
| Standard – Safety extra-low voltage | IEC 60950-1 (SELV) |
| EN 60204-1 (PELV) | |
| Standard - Safe isolation | DIN VDE 0100-410 |
| Standard – Limitation of mains harmonic currents | EN 61000-3-2 |
| Shipbuilding approval | DNV GL, PRS, BV, LR, ABS |
| UL approvals | UL Listed UL 508 |
| UL/C-UL Recognized UL 60950-1 | |
| UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) | |
| Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Vibration (operation) | 5 Hz ... 100 Hz resonance search 2.3g, 90 min., resonance frequency 2.3g, 90 min. (according to DNV GL Class C) |
| Approval - requirement of the semiconductor industry with regard to mains voltage dips | SEMI F47-0706; EN 61000-4-11 |
| Rail applications | EN 50121-3-2 |
| Overvoltage category (EN 60950-1) | II (≤ 5000 m) |
| Overvoltage category (EN 61010-1) | II (≤ 5000 m) |
| Overvoltage category (EN 62477-1) | III (≤ 2000 m) |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 25; |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |