QUINT4-PS/1AC/24DC/2.5/PT 2909576 PHOENIX CONTACT Power supply unit hardware delivers efficient energy conversion for standard industrial control panels. DIN rail power supply units feed automated machinery systems with stable, continuous direct current to ensure reliable sensor and controller performance.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Voltage type (supply voltage) (EF002991): AC/DC
- 1st secondary output voltage (EF006792): 24 V
- Max. output current 1 (EF008284): 5 A
- Secondary voltage adjustable (EF007002): Yes
- Nominal value output voltage 1 (EF009393): 24 V
- Nominal value output current 1 (EF009396): 2.5 A
- Short-circuit-proof (EF007332): Yes
- Rated supply voltage AC 50 Hz (EF007076): 100 V
- Rated supply voltage AC 60 Hz (EF007077): 100 V
- Rated supply voltage DC (EF007078): 110 V
- Output voltage stabilized (EF003092): Yes
- Power consumption (EF000346): 71 VA
- Power output (EF003034): 60 W
- Stabilized (EF005302): Yes
- Suitable for rail mounting (EF003972): Yes
- Wall mounting possible (EF003973): No
More info
▲Key Commercial Data
| Orderkey | 2909576 |
|---|---|
| Packing unit | 1 pc |
| GTIN | 4055626356495 |
| Weight per Piece (excluding packing) | 311.100 g |
| Custom tariff number | 85044030 |
| Country of origin | DE (Germany) |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
| Ambient temperature (start-up type tested) | -40 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Degree of pollution | 2 |
| Installation height | ≤ 5000 m (> 2000 m, observe derating) |
Input data
| Input voltage range | 100 V AC ... 240 V AC -15 % ... +10 % |
|---|---|
| 110 V DC ... 250 V DC -20 % ... +40 % | |
| Dielectric strength maximum | 300 V AC 30 s |
| Discharge current to PE | < 0.25 mA (264 V AC, 60 Hz) |
| Current consumption | 0.85 A (100 V AC) |
| 0.7 A (120 V AC) | |
| 0.39 A (230 V AC) | |
| 0.37 A (240 V AC) | |
| Nominal power consumption | 71 VA |
| Inrush surge current | typ. 10 A (at 25 °C) |
| Mains buffering | typ. 54 ms (120 V AC) |
| typ. 54 ms (230 V AC) | |
| Input fuse | 3.15 A (slow-blow, internal) |
| Type of protection | Transient surge protection |
| Protective circuit/component | Varistor |
Output data
| Nominal output voltage | 24 V DC |
|---|---|
| Setting range of the output voltage (USet) | 24 V DC ... 28 V DC (constant capacity) |
| Nominal output current (IN) | 2.5 A |
| Static Boost (IStat.Boost) | 3.125 A (≤ 40 °C) |
| Dynamic Boost (IDyn.Boost) | 5 A (≤60 °C (5 s), Input <150 V AC Derating 0.5 %/V) |
| Derating | > 60 °C (2.5%/K) |
| Connection in parallel | Yes, for redundancy and increased capacity |
| Connection in series | yes |
| Feedback resistance | ≤ 35 V DC |
| Protection against surge voltage on the output | ≤ 32 V DC |
| Control deviation | < 0.5 % (Static load change 10 % ... 90 %) |
| < 2 % (Dynamic load change 10 % ... 90 %, (10 Hz)) | |
| < 0.1 % (change in input voltage ±10 %) | |
| Residual ripple | < 40 mVPP(with nominal values) |
| Output power | 60 W |
| Typical response time | 500 ms |
| Maximum power dissipation in no-load condition | < 1 W (230 V AC) |
| < 1 W (120 V AC) | |
| Power loss nominal load max. | < 5 W (230 V AC) |
| < 5 W (120 V AC) |
General
| Net weight | 0.244 kg |
|---|---|
| Efficiency | typ. 91.9 % (120 V AC) |
| typ. 92.6 % (230 V AC) | |
| Insulation voltage input/output | 4 kV AC (type test) |
| 3 kV AC (routine test) | |
| Protection class | II |
| Degree of protection | IP20 |
| MTBF (IEC 61709, SN 29500) | > 1347000 h (25 °C) |
| > 734000 h (40 °C) | |
| > 295000 h (60 °C) | |
| Assembly instructions | DIN rail mounting |
Connection data, input
| Connection method | Push-in technology |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 14 |
| Stripping length | 10 mm |
Connection data, output
| Connection method | Push-in technology |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 14 |
| Stripping length | 10 mm |
Connection data for signaling
| Connection method | Push-in technology |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 14 |
| Stripping length | 10 mm |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Standards/regulations | EN 61000-4-2 |
| Contact discharge | 4 kV (Test Level 2) |
| Standards/regulations | EN 61000-4-3 |
| Frequency range | 80 MHz ... 1 GHz |
| Test field strength | 10 V/m (Test Level 3) |
| Frequency range | 1.4 GHz ... 2 GHz |
| Test field strength | 3 V/m (Test Level 2) |
| Standards/regulations | EN 61000-4-4 |
| Comments | Criterion B |
| Standards/regulations | EN 61000-4-6 |
| Frequency range | 0.15 MHz ... 80 MHz |
| Voltage | 10 V (Test Level 3) |
| Conducted noise emission | EN 55016 EN 61000-6-4 (Class A) |
| Standards/regulations | EN 61000-4-8 |
| EN 61000-4-11 | |
| EN 61000-4-9 | |
| EN 61000-4-12 | |
| EN 61000-4-16 | |
| EN 61000-4-18 | |
| Standard - Safety of transformers | EN 61558-2-16 |
| Standard - Electrical safety | IEC 61010-2-201 (SELV) |
| Standard - power supply devices for low voltage with DC output | EN 61204-3 |
| Standard – Safety extra-low voltage | IEC 61010-1 (SELV) |
| IEC 61010-2-201 (PELV) | |
| Standard - Safe isolation | IEC 61558-2-16 |
| IEC 61010-2-201 | |
| Standard – Limitation of mains harmonic currents | EN 61000-3-2 |
| UL approvals | UL Listed UL 61010-1 |
| UL Listed UL 61010-2-201 | |
| UL 1310 Class 2 Power Units | |
| ANSI/UL 121201 Class I, Division 2, Groups A, B, C, D (Hazardous Location) | |
| Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Vibration (operation) | < 15 Hz, ±2.5 mm amplitude; 15 Hz ... 100 Hz: 2.3 g 90 Min. (in accordance with IEC 60068-2-6) |
| Overvoltage category (EN 61010-1) | II |
| Overvoltage category (EN 62477-1) | III (≤ 2000 m) |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 25; |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |