QUINT4-PS/1AC/12DC/7.5/PT 2904607 PHOENIX CONTACT Primary-switched power supply unit serves as a reliable DC power source in industrial control panels, converting mains voltage to a stable low-voltage output for sensors, actuators, and logic controllers. Power supply units of this type provide continuous, regulated energy to maintain consistent operation across automated machinery.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- 1st secondary output voltage (EF006792): 12 V
- Max. output current 1 (EF008284): 12.75 A
- Secondary voltage adjustable (EF007002): Yes
- Nominal value output voltage 1 (EF009393): 12 V
- Nominal value output current 1 (EF009396): 7.5 A
- Short-circuit-proof (EF007332): Yes
- Rated supply voltage AC 50 Hz (EF007076): 100 V
- Rated supply voltage AC 60 Hz (EF007077): 100 V
- Rated supply voltage DC (EF007078): 110 V
- Output voltage stabilized (EF003092): Yes
- Power consumption (EF000346): 96.3 VA
- Power output (EF003034): 90 W
- Stabilized (EF005302): Yes
- Suitable for rail mounting (EF003972): Yes
- Wall mounting possible (EF003973): No
- Modular version (EF001126): No
More info
▲Key Commercial Data
| Orderkey | 2904607 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 253 (C-4-2019) |
| GTIN | 4055626255767 |
| Weight per Piece (excluding packing) | 380.000 g |
| Custom tariff number | 85044030 |
| Country of origin | DE (Germany) |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
| Ambient temperature (start-up type tested) | -40 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Degree of pollution | 2 |
| Installation height | ≤ 5000 m (> 2000 m, observe derating) |
Input data
| Input voltage range | 100 V AC ... 240 V AC -15 % ... +10 % |
|---|---|
| 110 V DC ... 250 V DC -20 % ... +40 % | |
| Dielectric strength maximum | 300 V AC 60 s |
| Frequency range (fN) | 50 Hz ... 60 Hz -10 % ... +10 % |
| Discharge current to PE | < 0.25 mA (264 V AC, 60 Hz) |
| Current consumption | 1 A (100 V AC) |
| 0.85 A (120 V AC) | |
| 0.46 A (230 V AC) | |
| 0.44 A (240 V AC) | |
| Nominal power consumption | 96.3 VA |
| Inrush current | typ. 11.4 A (at 25 °C) |
| Mains buffering time | typ. 48 ms (120 V AC) |
| typ. 48 ms (230 V AC) | |
| Input fuse | 3.15 A (slow-blow, internal) |
| Recommended breaker for input protection | 6 A ... 16 A (Characteristic B, C or comparable) |
| Type of protection | Transient surge protection |
| Protective circuit/component | Varistor |
Output data
| Nominal output voltage | 12 V DC |
|---|---|
| Setting range of the output voltage (USet) | 12 V DC ... 15 V DC (constant capacity) |
| Nominal output current (IN) | 7.5 A |
| Dynamic Boost (IDyn.Boost) | 12.75 A (≤ 60 °C (5 s)) |
| Connection in parallel | Yes, for redundancy and increased capacity |
| Connection in series | yes |
| Feedback voltage resistance | ≤ 25 V DC |
| Protection against overvoltage at the output (OVP) | ≤ 18 V DC |
| Control deviation | < 0.3 % (Static load change 10 % ... 90 %) |
| < 3 % (Dynamic load change 10 % ... 90 %, (10 Hz)) | |
| < 0.1 % (change in input voltage ±10 %) | |
| Residual ripple | < 35 mVPP(with nominal values) |
| Output power | 90 W |
| Typical response time | 300 ms |
| Maximum power dissipation in no-load condition | < 0.6 W (230 V AC) |
| < 0.6 W (120 V AC) | |
| Power loss nominal load max. | < 8.1 W (120 V AC) |
| < 7.1 W (230 V AC) |
General
| Net weight | 0.3 kg |
|---|---|
| Efficiency | typ. 91.5 % (120 V AC) |
| typ. 92.5 % (230 V AC) | |
| Insulation voltage input/output | 4 kV AC (type test) |
| 3 kV AC (routine test) | |
| Protection class | II |
| Degree of protection | IP20 |
| MTBF (IEC 61709, SN 29500) | > 1221000 h (25 °C) |
| > 671000 h (40 °C) | |
| > 248000 h (60 °C) |
Connection data, input
| Connection method | Push-in connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 14 |
| Stripping length | 10 mm |
Connection data, output
| Connection method | Push-in connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 14 |
| Stripping length | 10 mm |
Connection data for signaling
| Connection method | Push-in connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 14 |
| Stripping length | 10 mm |
Standards
| Standard - Safety of transformers | EN 61558-2-16 |
|---|---|
| Standard - safety for equipment for measurement, control, and laboratory use | IEC 61010-1 |
| Standard – Safety extra-low voltage | IEC 61010-1 (SELV) |
| IEC 61010-2-201 (PELV) | |
| Standard - Safe isolation | IEC 61558-2-16 |
| Standard – Limitation of mains harmonic currents | EN 61000-3-2 |
Conformance/approvals
| UL approvals | UL Listed UL 61010-1 |
|---|---|
| UL Listed UL 61010-2-201 | |
| ANSI/UL 121201 Class I, Division 2, Groups A, B, C, D (Hazardous Location) | |
| SIQ | CB-Scheme (IEC 61010-1, IEC 61010-2-201) |
EMC data
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Conducted noise emission | EN 55016 |
| EN 61000-6-3 (Class B) | |
| Noise emission | EN 55016 |
| EN 61000-6-3 (Class B) | |
| Harmonic currents | EN 61000-3-2 |
| EN 61000-3-2 (Class A) | |
| Flicker | EN 61000-3-3 |
| Electrostatic discharge | EN 61000-4-2 |
| Contact discharge | 8 kV (Test Level 4) |
| Discharge in air | 15 kV (Test Level 4) |
| Electromagnetic HF field | EN 61000-4-3 |
| Frequency range | 80 MHz ... 1 GHz |
| Test field strength | 20 V/m (Test Level 3) |
| Frequency range | 1 GHz ... 6 GHz |
| Test field strength | 10 V/m (Test Level 3) |
| Comments | Criterion A |
| Fast transients (burst) | EN 61000-4-4 |
| Input | 4 kV (Test Level 4 - asymmetrical) |
| Output | 4 kV (Test Level 4 - asymmetrical) |
| Signal | 4 kV (Test Level 4 - asymmetrical) |
| Comments | Criterion A |
| Surge voltage load (surge) | EN 61000-4-5 |
| Input | 2 kV (Test Level 4 - symmetrical) |
| 4 kV (Test Level 4 - asymmetrical) | |
| Output | 1 kV (Test Level 3 - symmetrical) |
| 2 kV (Test Level 3 - asymmetrical) | |
| Signal | 0.5 kV (Test Level 2 - symmetrical) |
| Comments | Criterion A |
| I/O/S | asymmetrical |
| Frequency range | 0.15 MHz ... 80 MHz |
| Voltage | 10 V (Test Level 3) |
| Comments | Criterion A |
| Frequency | 16.67 Hz |
| 50 Hz | |
| 60 Hz | |
| Test field strength | 100 A/m |
| Additional text | 60 s |
| Comments | Criterion A |
| Frequency | 50 Hz |
| 60 Hz | |
| Test field strength | 1 kA/m |
| Additional text | 3 s |
| Frequency | 0 Hz |
| Test field strength | 300 A/m |
| Additional text | DC, 60 s |
| Voltage dips | EN 61000-4-11 |
| Voltage | 100 V AC |
| Frequency | 60 Hz |
| Voltage dip | 70 % |
| Number of periods | 0.5 / 1 / 30 periods |
| Additional text | Test Level 2 |
| Comments | Criterion A |
| Voltage dip | 40 % |
| Number of periods | 5 / 10 / 50 periods |
| Additional text | Test Level 2 |
| Comments | Criterion B |
| Voltage dip | 0 % |
| Number of periods | 0.5 / 1 / 5 / 50 periods |
| Additional text | Test Level 2 |
| Comments | Criterion B |
| Pulse-shape magnetic field | EN 61000-4-9 |
| Test field strength | 1000 A/m |
| Comments | Criterion A |
| Attenuated sinusoidal oscillations (ring wave) | EN 61000-4-12 |
| Input | 2 kV (symmetrical) |
| 4 kV (asymmetrical) | |
| Comments | Criterion A |
| Asymmetrical conducted disturbance variables | EN 61000-4-16 |
| Test level 1 | 16.67 Hz 50 Hz 60 Hz 150 Hz 180 Hz (Test Level 3) |
| Voltage | 30 V (10 s) |
| Test level 2 | 16.67 Hz 50 Hz 60 Hz (Test Level 2) |
| Voltage | 300 V (1 s) |
| Comments | Criterion A |
| Attenuated oscillating wave | EN 61000-4-18 |
| Voltage | 1 kV (symmetrical) |
| 2.5 kV (asymmetrical) | |
| 1 kV (symmetrical) | |
| Comments | Criterion A |
| Criterion A | Normal operating behavior within the specified limits. |
| Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
| Criterion C | Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements. |
Classifications
eCl@ss
| eCl@ss 5.1 | 27242213 |
|---|---|
| eCl@ss 6.0 | 27049000 |
| eCl@ss 7.0 | 27049002 |
| eCl@ss 8.0 | 27049002 |
| eCl@ss 9.0 | 27040701 |
UNSPSC
| UNSPSC 13.2 | 39121004 |
|---|---|
| UNSPSC 18.0 | 39121004 |
| UNSPSC 19.0 | 39121004 |
| UNSPSC 20.0 | 39121004 |
| UNSPSC 21.0 | 39121004 |