QUINT4-DIODE/12-24DC/2X20/1X40 2907719 PHOENIX CONTACT Diode
QUINT4-DIODE/12-24DC/2X20/1X40
2907719
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection module
Power Supplies (PS)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact QUINT4-DIODE/12-24DC/2X20/1X40 diode provides safe decoupling and redundancy management for 12V to 24V DC power systems. Diode modules are commonly implemented in industrial power distribution panels to isolate circuits and prevent backfeed damage. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Voltage type (operating voltage) (EF005294): DC
- Operating voltage DC (EF008208): 10 V
- With LED indication (EF005950): No
More info
▲Key Commercial Data
| Orderkey | 2907719 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 264 (C-4-2017) |
| GTIN | 4055626231211 |
| Weight per Piece (excluding packing) | 953.000 g |
| Custom tariff number | 85049091 |
| Country of origin | CN (China) |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -40 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Degree of pollution | 2 |
| Installation height | ≤ 2000 m |
Input data
| Nominal input voltage range | 12 V DC ... 24 V DC |
|---|---|
| 12 V DC ... 24 V DC | |
| Input voltage range | 10 V DC ... 30 V DC |
| 10 V DC ... 30 V DC | |
| Nominal input current | 2x 20 A (-40 °C ... 60 °C) |
| 1x 40 A (-40 °C ... 60 °C) | |
| Maximum input current | 2x 30 A (-40 °C ... 40 °C) |
| 1x 60 A (-40 °C ... 40 °C) | |
| Nominal input current | 2x 20 A (-25 °C ... 60 °C) |
| 1x 40 A (-25 °C ... 60 °C) | |
| Maximum input current | 2x 30 A (-25°C ... 40°C) |
| 1x 60 A (-25°C ... 40°C) |
Output data
| Output voltage range | 12 V DC ... 24 V DC |
|---|---|
| Nominal output current (IN) | 40 A (Increasing power) |
| 20 A (Redundancy) | |
| Derating | 60 °C ... 70 °C (2.5%/K) |
| Connection in series | No |
| Power loss nominal load max. | 10 W (IOUT= 20 A) |
General
| Net weight | 0.75 kg |
|---|---|
| Efficiency | > 97 % |
| Insulation voltage input/output | type test |
| routine test | |
| Insulation voltage input / PE | type test |
| routine test | |
| Protection class | III |
| Degree of protection | IP20 |
| MTBF (IEC 61709, SN 29500) | |
| 40000000 h (40 °C) | |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| Assembly instructions | alignable: PN≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically alignable: PN<50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom |
Connection data, input
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.5 mm² |
| Conductor cross section solid max. | 16 mm² |
| Conductor cross section flexible min. | 0.5 mm² |
| Conductor cross section flexible max. | 16 mm² |
| Conductor cross section AWG min. | 10 |
| Conductor cross section AWG max. | 6 |
| Stripping length | 10 mm |
| Screw thread | M4 |
Connection data, output
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.5 mm² |
| Conductor cross section solid max. | 16 mm² |
| Conductor cross section flexible min. | 0.5 mm² |
| Conductor cross section flexible max. | 16 mm² |
| Conductor cross section AWG min. | 10 |
| Conductor cross section AWG max. | 6 |
| Stripping length | 10 mm |
| Screw thread | M4 |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Low Voltage Directive | Conformance with LV directive 2006/95/EC |
| Standard - Electrical safety | EN 60950-1/VDE 0805 (SELV) |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
| Standard – Safety extra-low voltage | IEC 60950-1 (SELV) and EN 60204-1 (PELV) |
| Standard - Safe isolation | DIN VDE 0100-410 |
| Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment | EN 50178 |
| UL approvals | UL/C-UL listed UL 508 |
| UL/C-UL Recognized UL 60950-1 | |
| UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) | |
| Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Vibration (operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
| 15 Hz ... 150 Hz, 2.3g, 90 min. | |
| ATEX | II 3G Ex nA IIC T4 Gc |
| KEMA 10 ATEX 0165X | |
| IECEx | Ex nA IIC T4 Gc |
| IECEx KEM 10.0091 |