View larger
QUINT-UPS/ 24DC/12DC/5/24DC/10 2320461 PHOENIX CONTACT Uninterruptible power supply
QUINT-UPS/ 24DC/12DC/5/24DC/10
2320461
PHOENIX CONTACT
1 Pcs.
Automation > UPS
Power Supplies (PS)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact QUINT-UPS/ 24DC/12DC/5/24DC/10 is an uninterruptible power supply built to secure DC-powered automation lines against voltage dropouts and complete power failures. DC backup modules are essential for keeping programmable logic controllers and sensors active during grid anomalies. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Input voltage (EF003840): 18 V
- Output voltage (EF003933): 24 V
- SNMP (EF005284): No
- Voltage type (EF000187): DC
- Height (EF000040): 130 mm
- Width (EF000008): 35 mm
- Depth (EF000049): 125 mm
- Weight (EF000167): 0.6 kg
- Bridging time full load (EF000428): 10800 min
More info
▲Key Commercial Data
| Orderkey | 2320461 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 276 (C-4-2017) |
| GTIN | 4046356731515 |
| Weight per Piece (excluding packing) | 744.800 g |
| Custom tariff number | 85371091 |
| Country of origin | CN (China) |
Dimensions
| Width | 35 mm |
|---|---|
| Height | 130 mm |
| Depth | 125 mm |
| Width with alternative assembly | 123 mm |
| Height with alternative assembly | 130 mm |
| Depth with alternative assembly | 39 mm |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -25 °C ... 70 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Max. permissible relative humidity (operation) | ≤ 95 % (25 °C, non-condensing) |
| Climatic class | 3K3 (in acc. with EN 60721) |
Input data
| Input voltage | 24 V DC |
|---|---|
| Nominal input voltage | 18 V DC ... 30 V DC |
| Input voltage range | 18 V DC ... 30 V DC |
| Current consumption (maximum) | 16 A (maximum, mains operation) |
| Current consumption (charging process) | 4 A (Charging, mains operation) |
| Fixed connect threshold | ≤ 22 V DC |
| Variable connect threshold | 1 V/0.1 s |
Output data (24 V DC mains operation)
| Nominal output voltage | 24 V DC |
|---|---|
| Output voltage range (depends on the input voltage) | 18 V DC ... 30 V DC (UOUT= UIN- 0.5 V DC) |
| Nominal output current (IN) | 10 A (-25 °C ... 60 °C) |
| POWER BOOST (IBoost) | 15 A (-25°C ... 40°C) |
| Selective Fuse Breaking (ISFB) | 60 A (-25 °C ... 60 °C) |
Output data (12 V DC mains operation)
| Nominal output voltage | 12 V DC |
|---|---|
| Nominal output current (IN) | 5 A (-25 °C ... 60 °C) |
| POWER BOOST (IBoost) | 7.5 A (-25°C ... 40°C) |
Output data (24 V DC battery operation)
| Nominal output voltage | 24 V DC |
|---|---|
| Output voltage range (depends on the input voltage) | 19.2 V DC ... 27.6 V DC (UOUT= UBAT- 0.5 V DC) |
| Nominal output current (IN) | 10 A (-25 °C ... 60 °C) |
| POWER BOOST (IBoost) | 15 A (-25°C ... 40°C) |
| Selective Fuse Breaking (ISFB) | 65 A (-25 °C ... 60 °C) |
Output data (12 V DC battery operation)
| Nominal output voltage | 12 V DC |
|---|---|
| Nominal output current (IN) | 5 A (-25 °C ... 60 °C) |
| POWER BOOST (IBoost) | 7.5 A (-25°C ... 40°C) |
General output data
| Total power P12V+ P24V | max. 360 W |
|---|---|
| Efficiency 12 V DC | > 93 % (Mains operation, with charged energy storage) |
| Efficiency 24 V DC | > 98 % (Mains operation, with charged energy storage) |
General
| IQ technology | Yes |
|---|---|
| Net weight | 0.6 kg |
| Protection class | III |
| MTBF (IEC 61709, SN 29500) | > 652000 h (40 °C) |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| Assembly instructions | alignable: horizontal 5 mm, vertical 50 mm |
Connection data, input
| Connection method | Pluggable screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 16 |
| Conductor cross section AWG max. | 12 |
| Stripping length | 7 mm |
| Screw thread | M4 |
Connection data, output
| Connection method | Pluggable screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 16 |
| Conductor cross section AWG max. | 12 |
| Stripping length | 7 mm |
| Screw thread | M4 |
Connection data for signaling
| Connection method | Pluggable screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
| Stripping length | 7 mm |
| Screw thread | M4 |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Noise immunity | EN 61000-6-2:2005 |
| Connection in acc. with standard | CUL |
| Standards/regulations | EN 61000-4-2 |
| Contact discharge | 4 kV (Test Level 2) |
| Standards/regulations | EN 61000-4-3 |
| Frequency range | 80 MHz ... 1 GHz |
| Test field strength | 10 V/m |
| Frequency range | 1.4 GHz ... 2 GHz |
| Test field strength | 3 V/m |
| Standards/regulations | EN 61000-4-4 |
| Comments | Criterion B |
| Standards/regulations | EN 61000-6-3 |
| EN 61000-4-6 | |
| Frequency range | 0.15 MHz ... 80 MHz |
| Voltage | 10 V (Test Level 3) |
| Low Voltage Directive | Conformance with LV directive 2006/95/EC |
| Standard - Electrical safety | EN 60950-1/VDE 0805 (SELV) |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
| UL approvals | UL Listed UL 508 |
| UL/C-UL Recognized UL 60950-1 | |
| Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Vibration (operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
| 15 Hz ... 150 Hz, 2.3g tv= 90 min. | |
| Rail applications | EN 50121-4 |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 25; |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |