QUINT-PS/24DC/24DC/10 2320092 PHOENIX CONTACT DC/DC converters
QUINT-PS/24DC/24DC/10
2320092
PHOENIX CONTACT
1 Pcs.
Automation > DC-power supply
Power Supplies (PS)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A DC/DC converter, such as the Phoenix Contact QUINT-PS/24DC/24DC/10, conditions and stabilizes direct current voltage levels to protect downstream automation devices from line fluctuations and voltage drops. These modules are standard installations in industrial control cabinets.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Voltage type (supply voltage) (EF002991): DC
- 1st secondary output voltage (EF006792): 18 V
- Max. output current 1 (EF008284): 12.5 A
- Secondary voltage adjustable (EF007002): Yes
- Nominal value output voltage 1 (EF009393): 24 V
- Nominal value output current 1 (EF009396): 10 A
- Short-circuit-proof (EF007332): Yes
- Rated supply voltage DC (EF007078): 18 V
- Output voltage stabilized (EF003092): Yes
- Power output (EF003034): 240 W
- Stabilized (EF005302): Yes
- Type of electric connection (EF003961): Screw connection
- Suitable for rail mounting (EF003972): Yes
- Wall mounting possible (EF003973): No
- Modular version (EF001126): No
- Built-in height (EF000332): 130 mm
More info
▲Key Commercial Data
| Orderkey | 2320092 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 248 (C-4-2017) |
| GTIN | 4046356481885 |
| Weight per Piece (excluding packing) | 900.000 g |
| Custom tariff number | 85044030 |
| Country of origin | CN (China) |
Dimensions
| Width | 48 mm |
|---|---|
| Height | 130 mm |
| Depth | 125 mm |
| Width with alternative assembly | 122 mm |
| Height with alternative assembly | 130 mm |
| Depth with alternative assembly | 51 mm |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C derating, 2.5 %/K, startup at -40°C type-tested) |
| Ambient temperature (start-up type tested) | -40 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Degree of pollution | 2 |
Input data
| Nominal input voltage range | 24 V DC |
|---|---|
| Input voltage range | 18 V DC ... 32 V DC |
| Current consumption | 14 A (24 V, IBOOST) |
| Inrush surge current | < 15 A (typical) |
| Mains buffering | > 12 ms (24 V DC) |
| Input fuse | 25 A (internal (device protection)) |
| Choice of suitable circuit breakers | 16 A ... 20 A (Characteristics B, C, D, K) |
| Type of protection | Transient surge protection |
| Protective circuit/component | Varistor |
Output data
| Nominal output voltage | 24 V DC ±1 % |
|---|---|
| Setting range of the output voltage (USet) | 18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted) |
| Nominal output current (IN) | 10 A (-25 °C ... 60 °C) |
| POWER BOOST (IBoost) | 12.5 A (-25°C ... 40°C permanent, UOUT= 24 V DC ) |
| Selective Fuse Breaking (ISFB) | 60 A (12 ms) |
| Derating | 60 °C ... 70 °C (2.5%/K) |
| Connection in parallel | Yes, for redundancy and increased capacity |
| Connection in series | yes |
| Feedback resistance | 35 V DC |
| Output overvoltage protection | < 35 V DC |
| Max. capacitive load | unlimited |
| Active current limitation | Approx. 18 A |
| Control deviation | < 1 % (change in load, static 10 % ... 90 %) |
| < 2 % (change in load, dynamic 10 % ... 90 %) | |
| < 0.1 % (change in input voltage ±10 %) | |
| Residual ripple | < 20 mVPP |
| Peak switching voltages nominal load | < 10 mVPP(20 MHz) |
| Maximum power dissipation in no-load condition | 1.6 W |
| Power loss nominal load max. | 24 W |
General
| Net weight | 0.9 kg |
|---|---|
| Efficiency | > 92 % |
| Insulation voltage input/output | 1.5 kV (type test) |
| 1 kV (routine test) | |
| Protection class | III |
| Degree of protection | IP20 |
| MTBF (IEC 61709, SN 29500) | |
| > 763000 h (40 °C) | |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| Assembly instructions | alignable: PN≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically alignable: PN<50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom |
Connection data, input
| Connection method | Pluggable screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
| Stripping length | 8 mm |
| Screw thread | M3 |
Connection data, output
| Connection method | Pluggable screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
| Stripping length | 7 mm |
| Screw thread | M3 |
Connection data for signaling
| Conductor cross section solid min. | 0.2 mm² |
|---|---|
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
| Screw thread | M3 |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Noise immunity | EN 61000-6-2:2005 |
| Connection in acc. with standard | CUL |
| Standards/regulations | EN 61000-4-2 |
| Contact discharge | 4 kV (Test Level 2) |
| Standards/regulations | EN 61000-4-3 |
| Frequency range | 80 MHz ... 1 GHz |
| Test field strength | 10 V/m (Test Level 3) |
| Frequency range | 1.4 GHz ... 2 GHz |
| Test field strength | 3 V/m (Test Level 2) |
| Standards/regulations | EN 61000-4-4 |
| Comments | Criterion B |
| Standards/regulations | EN 61000-6-3 |
| EN 61000-4-6 | |
| Frequency range | 0.15 MHz ... 80 MHz |
| Voltage | 10 V (Test Level 3) |
| Standard - Electrical safety | EN 60950-1/VDE 0805 (SELV) |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
| Standard – Safety extra-low voltage | EN 60950-1 (SELV) |
| EN 60204 (PELV) | |
| Standard - Safe isolation | DIN VDE 0100-410 |
| Shipbuilding approval | DNV GL (EMC B) |
| UL approvals | UL/C-UL listed UL 508 |
| UL/C-UL Recognized UL 60950-1 | |
| UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) | |
| Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Vibration (operation) | < 5 Hz, amplitude ±1.6 mm (according to IEC 60068-2-6) |
| 5 Hz ... 100 Hz, 4g, 90 min. | |
| Rail applications | EN 50121-4 |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 25; |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |