PHOENIX CONTACT PTU 35/4X10 PTU 35/4X10 3002371 PHOENIX CONTACT Potential collective terminal View larger
Images are for illustrative purposes only. Please refer to data sheet for details

PTU 35/4X10 3002371 PHOENIX CONTACT Potential collective terminal

PTU 35/4X10

3002371

PHOENIX CONTACT

25 Pcs.

Potential collective terminal Collective potential terminal, nominal voltage: 1000 V, nominal current: 101 A, number of connections: 5, connection type: Screw connection, Sizing cross-section: 35 mm², cross-section: 1.5 mm² - 50 mm², Push-in connection, Sizing cross-section: 10 mm², cross-section: 0.5 mm² - 10 mm², mounting class: NS 35/7.5, NS 35/15, color: gray Potential collective terminal, In the end application, the applicable safety regulations for overload and short-circuit protection on the connected conductors must be considered., nom. voltage: 1000 V, nominal current: 57 A, Load contact, connection method: Push-in connection, Rated cross section: 10 mm2, cross section: 0.5 mm2 - 16 mm2, Line contact, connection method: Screw connection, Rated cross section: 35 mm2, cross section: 1.5 mm2 - 50 mm2, mounting: NS 35/7,5, NS 35/15, color: gray

Automation > Feed-through terminal block
Modular TBs

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Phoenix Contact PTU 35/4X10 is a potential collective terminal designed for organizing and distributing electrical potentials within industrial control panels and power distribution systems. Terminal blocks of this type securely link multiple conductors in a centralized junction, ensuring reliable signal or power routing across complex wiring layouts. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Rated current In (EF008250): 57 A
  • Rated voltage (EF000228): 1000 V
  • Number of levels (EF002659): 1
  • Number of clamp positions per level (EF002660): 5
  • Mounting method (EF000003): DIN rail (top hat rail) 35 mm
  • Width (EF000008): 19.4 mm
  • Height (EF000040): 79.9 mm
  • Depth (EF000049): 50.3 mm
  • Closing plate required (EF002525): No
  • Colour (EF000007): Grey

More info

▲

Key Commercial Data

Orderkey3002371
Packing unit25 pc
Minimum order quantity25 pc
NoteMade to Order (non-returnable)
GTIN4055626430881
Weight per Piece (excluding packing)9.990 g
Custom tariff number85369010
Country of originIN (India)

General

NoteIn the end application, the applicable safety regulations for overload and short-circuit protection on the connected conductors must be considered.
Number of levels1
Number of connections5
Nominal cross section16 mm²
Colorgray
Insulating materialPA
Flammability rating according to UL 94V0
Rated surge voltage8 kV
Degree of pollution2
Overvoltage categoryIII
Insulating material groupI
Maximum power dissipation for nominal condition4.06 W (the value is multiplied when connecting multiple levels)
Connection methodScrew connection
Connection in acc. with standardIEC 60947-7-1
Maximum load current101 A (The maximum load current must not be exceeded by the total current of all connected conductors.)
Nominal current IN101 A
Nominal voltage UN1000 V
Connection methodPush-in connection
Connection in acc. with standardIEC 60947-7-1
Maximum load current57 A
Nominal current IN57 A
Nominal voltage UN1000 V
Open side panelNo
Back of the hand protectionguaranteed
Finger protectionguaranteed
Result of surge voltage testTest passed
Surge voltage test setpoint9.8 kV
Result of power-frequency withstand voltage testTest passed
Power frequency withstand voltage setpoint2.2 kV
Result of the test for mechanical stability of terminal points (5 x conductor connection)Test passed
Result of bending testTest passed
Bending test rotation speed10 rpm
Bending test turns135
Bending test conductor cross section/weight2.5 mm² / 0.7 kg
10 mm² / 2 kg
35 mm² / 6.8 kg
Tensile test resultTest passed
Conductor cross section tensile test2.5 mm²
Tractive force setpoint50 N
Conductor cross section tensile test10 mm²
Tractive force setpoint90 N
Conductor cross section tensile test35 mm²
Tractive force setpoint190 N
Result of tight fit on supportTest passed
Tight fit on carrierNS 35
Setpoint5 N
Result of voltage-drop testTest passed
Requirements, voltage drop≤ 1.6 mV
Result of temperature-rise testTest passed
Short circuit stability resultTest passed
Conductor cross section short circuit testing10 mm²
Short-time current1.2 kA
Conductor cross section short circuit testing16 mm²
Short-time current1.92 kA
Conductor cross section short circuit testing35 mm²
Short-time current4.2 kA
Result of aging testTest passed
Ageing test for screwless modular terminal block temperature cycles192
Result of thermal testTest passed
Proof of thermal characteristics (needle flame) effective duration30 s
Oscillation, broadband noise test resultTest passed
Test specification, oscillation, broadband noiseDIN EN 50155 (VDE 0115-200):2008-03
Test spectrumService life test category 2, bogie-mounted
Test frequencyf1= 5 Hz to f2= 250 Hz
ASD level6.12 (m/s2)2/Hz
Acceleration3.12 g
Test duration per axis5 h
Test directionsX-, Y- and Z-axis
Shock test resultTest passed
Test specification, shock testDIN EN 50155 (VDE 0115-200):2008-03
Shock formHalf-sine
Acceleration30g
Shock duration18 ms
Number of shocks per direction3
Test directionsX-, Y- and Z-axis (pos. and neg.)
Relative insulation material temperature index (Elec., UL 746 B)130 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))130 °C
Static insulating material application in cold-60 °C
Behavior in fire for rail vehicles (DIN 5510-2)Test passed
Flame test method (DIN EN 60695-11-10)V0
Oxygen index (DIN EN ISO 4589-2)>32 %
NF F16-101, NF F10-102 Class I2
NF F16-101, NF F10-102 Class F2
Surface flammability NFPA 130 (ASTM E 162)passed
Specific optical density of smoke NFPA 130 (ASTM E 662)passed
Smoke gas toxicity NFPA 130 (SMP 800C)passed
Calorimetric heat release NFPA 130 (ASTM E 1354)28 MJ/kg
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26HL 1 - HL 3

Dimensions

Width19.4 mm
Length79.9 mm
Height NS 35/7,550.3 mm
Height NS 35/1557.8 mm

Connection data

Connection methodScrew connection
Connection in acc. with standardIEC 60947-7-1
Screw threadM6
Tightening torque, min3.2 Nm
Tightening torque max3.7 Nm
Stripping length18 mm
Conductor cross section solid min.10 mm²
Conductor cross section solid max.35 mm²
Conductor cross section AWG min.8
Conductor cross section AWG max.2
Conductor cross section flexible min.10 mm²
Conductor cross section flexible max.35 mm²
Min. AWG conductor cross section, flexible8
Max. AWG conductor cross section, flexible2
Conductor cross section flexible, with ferrule without plastic sleeve min.10 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max.35 mm²
Conductor cross section flexible, with ferrule with plastic sleeve min.10 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max.35 mm²
2 conductors with same cross section, solid min.1.5 mm²
2 conductors with same cross section, solid max.16 mm²
Two conductors with the same cross section, AWG solid min.16
Two conductors with the same cross section, AWG solid max.6
2 conductors with same cross section, stranded min.1.5 mm²
2 conductors with same cross section, stranded max.10 mm²
Two conductors with the same cross section, AWG stranded, min.16
Two conductors with the same cross section, AWG stranded, max.8
2 conductors with same cross section, stranded, ferrules without plastic sleeve, min.1.5 mm²
2 conductors with same cross section, stranded, ferrules without plastic sleeve, max.10 mm²
Conductor cross section solid min.1 mm²
Conductor cross section solid max.16 mm²
Conductor cross section AWG min.16
Conductor cross section AWG max.6
Conductor cross section flexible min.4 mm²
Conductor cross section flexible max.10 mm²
Internal cylindrical gageB9
Connection methodPush-in connection
Connection in acc. with standardIEC 60947-7-1
Conductor cross section solid min.2.5 mm²
Conductor cross section solid max.16 mm²
Conductor cross section AWG min.20
Conductor cross section AWG max.6
Conductor cross section flexible min.2.5 mm²
Conductor cross section flexible max.10 mm²
Min. AWG conductor cross section, flexible20
Max. AWG conductor cross section, flexible8
Conductor cross section flexible, with ferrule without plastic sleeve min.2.5 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max.10 mm²
Conductor cross section flexible, with ferrule with plastic sleeve min.2.5 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max.10 mm²

Standards and Regulations

Connection in acc. with standardIEC 60947-7-1
IEC 60947-7-1
Flammability rating according to UL 94V0
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26HL 1 - HL 3

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.