PTFIX 10/6X4-NS35-FE 3273612 PHOENIX CONTACT Block for distribution, rated voltage: 450 V, nominal current: ..
PTFIX 10/6X4-NS35-FE
3273612
PHOENIX CONTACT
8 Pcs.
Automation > Feed-through terminal block
FIX block System
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A Phoenix Contact PTFIX 10/6X4-NS35-FE block for distribution is engineered to handle higher-capacity power distribution requirements within heavy-duty industrial control panels. Distribution blocks distribute incoming electrical energy across multiple output terminals while keeping wiring tidy and safe.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- General notes note: The maximum load current of the individual connection points must not be exceeded.
- Product Type: Distribution terminal
- Number of connections: 7
- Number of rows: 1
- Potential: 1
- Data maintenance status Article review: 01
- Insulation characteristics Overvoltage Category: Iii
- Degree of pollution: 3
- Sizing Impulse Voltage: 6 kV
- Maximum power dissipation under nominal conditions: 1.02 W
- Feeding: Yes
- Number of connections per plan: 7
- Nominal cross-section: 4 mm²
- AWG Sizing Section: 10
- Grip Length of the section to be stripped: 10 mm ... 12 mm
- Gauge Pad: A4
More info
▲| General notes | |
| note | The maximum load current of the individual connection points must not be exceeded. |
| For power distribution applications, IEC 60364-4-43:2008, as amended + Corrigendum Ott. 2008 (DIN VDE 0100-430:2010-10) section 433.2 ff! | |
| Product Type | Distribution terminal |
| Number of connections | 7 |
| Number of rows | 1 |
| Potential | 1 |
| Data maintenance status | |
| Article review | 01 |
| Insulation characteristics | |
| Overvoltage Category | Iii |
| Degree of pollution | 3 |
| Sizing Impulse Voltage | 6 kV |
| Maximum power dissipation under nominal conditions | 1.02 W |
| Feeding | Yes |
| Number of connections per plan | 7 |
| Nominal cross-section | 4 mm² |
| AWG Sizing Section | 10 |
| Grip | |
| Length of the section to be stripped | 10 mm ... 12 mm |
| Gauge Pad | A4 |
| Standard-compliant connection | IEC 60947-7-1 |
| Rigid conductor cross-section | 0.2 mm² ... 6 mm² |
| Conductor cross-section AWG | 24 ... 10 (converted according to IEC) |
| Flexible conductor cross-section | 0.2 mm² ... 4 mm² |
| Flexible conductor cross-section [AWG] | 24 ... 12 (converted according to IEC) |
| Flexible conductor cross-section (cable lug without insulation collar) | 0.2 mm² ... 4 mm² |
| Flexible conductor cross-section (plastic lug and collar) | 0.2 mm² ... 4 mm² |
| 2 conductors of identical cross-section flexible with TWIN ferrule with plastic collar | 0.5 mm² ... 1 mm² |
| Rated current | 41 A |
| Maximum load current | 41 A (with 6 mm² conductor connection) |
| Maximum cumulative current | 63 A |
| Nominal voltage | 800 V |
| Nominal cross-section | 4 mm² |
| Collective connection | |
| Length of the section to be stripped | 12 mm ... 14 mm |
| Standard-compliant connection | IEC 60947-7-1 |
| Rigid conductor cross-section | 0.5 mm² ... 10 mm² |
| Conductor cross-section AWG | 24 ... 10 (converted according to IEC) |
| Flexible conductor cross-section | 0.5 mm² ... 10 mm² |
| Flexible conductor cross-section [AWG] | 24 ... 12 (converted according to IEC) |
| Flexible conductor cross-section (cable lug without insulation collar) | 0.5 mm² ... 10 mm² |
| Flexible conductor cross-section (plastic lug and collar) | 0.5 mm² ... 10 mm² |
| 2 conductors of identical cross-section flexible with TWIN ferrule with plastic collar | 0.75 mm² ... 2.5 mm² |
| Rated current | 57 A |
| Maximum load current | 57 A (with a conductor cross-section of 10 mm²) |
| Maximum cumulative current | 63 A (The maximum load current of the individual connection points must not be exceeded.) |
| Nominal voltage | 800 V |
| Nominal cross-section | 10 mm² |
| Socket Direct plug-in connection sections | |
| Rigid conductor cross-section | 0.5 mm² ... 6 mm² |
| Solid conductor cross-section [AWG] | 20 ... 10 (converted according to IEC) |
| Flexible conductor cross-section (cable lug without insulation collar) | 0.75 mm² ... 4 mm² |
| Flexible conductor cross-section (plastic lug and collar) | 0.5 mm² ... 4 mm² |
| Collective connection Direct pluggable connection sections | |
| Rigid conductor cross-section | 1.5 mm² ... 10 mm² |
| Flexible conductor cross-section (cable lug without insulation collar) | 2.5 mm² ... 10 mm² |
| Flexible conductor cross-section (plastic lug and collar) | 1 mm² ... 10 mm² |
| width | 28.6 mm |
| height | 58.1 mm |
| Depth on NS 15 | 30.4 mm |
| Depth on NS 35/7.5 | 32.4 mm |
| Color | multicoloured |
| black (RAL 9005) | |
| yellow (RAL 1018) | |
| Combustibility class according to UL 94 | V0 |
| Insulation Material Group | The |
| Insulation material | PA |
| Cold static insulation material insert | -60 °C |
| Temperature index for insulation material (DIN EN 60216-1 (VDE 0304-21)) | 130 °C |
| Insulation Material Relative Temperature Index (Elec., UL 746 B) | 130 °C |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
| Heat development calorimetric cone NFPA 130 (ASTM E 1354) | 28 MJ/kg |
| Surface Flammability NFPA 130 (ASTM E 162) | Exceeded |
| NFPA 130 (ASTM E 662) Specific Optical Density of Fumes | Exceeded |
| NFPA 130 Fume Toxicity (SMP 800C) | Exceeded |
| Impulse voltage test | |
| Test voltage rated value | 9.8 kV |
| Result | Test passed |
| Ambient Temperature Test | |
| Heating verification requirement | Temperature rise ≤ 45 K |
| Result | Test passed |
| Short-term current resistance 10 mm² | 1.2 kA |
| Result | Test passed |
| Dielectric strength at mains frequency | |
| Test voltage rated value | 2 kV |
| Result | Test passed |
| Mechanical data | |
| Open side wall | no |
| Mechanical resistance | |
| Result | Test passed |
| Mounting on the stand | |
| Support rail/fixing support | NS 35/NS 15 |
| Test force rated value | 5 N |
| Result | Test passed |
| note | When sequencing multiple blocks, it is recommended that a DIN rail adapter be placed under the connection point or a flanged element between the blocks for each block. |
| For variants with 6 or 7 connections, simply insert a DIN rail adapter centrally to each block and the flange elements every two blocks. | |
| When using the PTFIX-NS35 DIN rail adapter, an aligned block can only be stacked in half. | |
| Conductor Integrity and Stability Test | |
| Rotational speed | 10 rpm |
| Turns | 135 |
| Conductor cross-section/weight | 0.5 mm2/0.3 kg |
| 10 mm2/2 kg | |
| Result | Test passed |
| Conductor Integrity and Stability Test | |
| Rotational speed | 10 rpm |
| Turns | 135 |
| Conductor cross-section/weight | 0.2 mm2/0.2 kg |
| 4 mm2/0.9 kg | |
| 6 mm2/1.4 kg | |
| Result | Test passed |
| Aging | |
| Temperature Cycling | 192 |
| Result | Test passed |
| Needle flame test | |
| Duration of application | 30 s |
| Result | Test passed |
| Broadband vibration/noise | |
| Test Specification | DIN EN 50155 (VDE 0115-200):2008-03 |
| Spectrum | Category 2 Electrical Life Check, Trolley Mounted |
| Frequency | f1= 5 Hz up to f2= 250 Hz |
| ASD Level | 6.12 (m/s²)²/Hz |
| Acceleration | 3.12g |
| Test duration per axle | 5 h |
| Test Directions | X, Y, and Z axis |
| Result | Test passed |
| Shock | |
| Test Specification | DIN EN 50155 (VDE 0115-200):2008-03 |
| Shock Form | Semi-sinusoidal |
| Acceleration | 30g |
| Shock Duration | 18 ms |
| Number of shocks per direction | 3 |
| Test Directions | X, Y and Z axis (pos. and neg.) |
| Result | Test passed |
| Environmental conditions | |
| Ambient temperature (operating) | -60 °C ... 110 °C (Operating temperature range including self-heating, short-term maximum operating temperature cf. RTI Elec.) |
| Ambient temperature (storage/transport) | -25 °C ... 60 °C (for short duration, no longer than 24 h, -60 °C to +70 °C) |
| Ambient temperature (mounting) | -5 °C ... 70 °C |
| Ambient Temperature (Activation) | -5 °C ... 70 °C |
| Permissible humidity (operation) | 20 % ... 90 % |
| Permissible humidity (storage/transport) | 30 % ... 70 % |
| Standard-compliant connection | IEC 60947-7-1 |
| IEC 60947-7-1 |
| Mounting type | NS 35/7.5 |
| NS 35/15 |