View larger
PTFIX 10/18X4-NS35A GY 3273768 PHOENIX CONTACT Block for distribution, nominal voltage: 800 V, rated current..
PTFIX 10/18X4-NS35A GY
3273768
PHOENIX CONTACT
8 Pcs.
Automation > Feed-through terminal block
FIX block System
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact PTFIX 10/18X4-NS35A GY block for distribution streamlines power distribution across multiple terminal points within complex control panel architectures. Distribution blocks eliminate the need for jumper wires by consolidating feeds into a single compact unit. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- General Observation: The maximum charging current of the various terminal points must not be exceeded.
- Product Type: Distribution terminal
- Number of connections: 19
- Number of rows: 1
- Potential: 1
- Data Maintenance Status Article Review: 01
- Insulation Properties Surge Category: Iii
- Degree of pollution: 3
- Dimensioning Transient Voltage: 6 kV
- Maximum Dissipated Power with Nominal Condition: 1.02 W
- Feeding: Yes
- Number of connections per floor: 19
- Nominal Section: 4 mm²
- AWG Sizing Section: 10
- Derivation Peel Length: 10 mm ... 12 mm
- Male Gauge: A4
More info
▲| General | |
| Observation | The maximum charging current of the various terminal points must not be exceeded. |
| For applications for power distribution, IEC 60364-4-43:2008 must be observed, as amended + correction Oct. 2008 (DIN VDE 0100-430:2010-10) part 433.2 et seq. | |
| Product Type | Distribution terminal |
| Number of connections | 19 |
| Number of rows | 1 |
| Potential | 1 |
| Data Maintenance Status | |
| Article Review | 01 |
| Insulation Properties | |
| Surge Category | Iii |
| Degree of pollution | 3 |
| Dimensioning Transient Voltage | 6 kV |
| Maximum Dissipated Power with Nominal Condition | 1.02 W |
| Feeding | Yes |
| Number of connections per floor | 19 |
| Nominal Section | 4 mm² |
| AWG Sizing Section | 10 |
| Derivation | |
| Peel Length | 10 mm ... 12 mm |
| Male Gauge | A4 |
| Standard-compliant connection | IEC 60947-7-1 |
| Rigid conductor section | 0.2 mm² ... 6 mm² |
| AWG Conductor Section | 24 ... 10 (Converted according to IEC) |
| Flexible conductor section | 0.2 mm² ... 4 mm² |
| Flexible Wire Section [AWG] | 24 ... 12 (Converted according to IEC) |
| Flexible cable section (toe cap without plastic sleeve) | 0.2 mm² ... 4 mm² |
| Flexible cable section (toe cap with plastic sleeve) | 0.2 mm² ... 4 mm² |
| 2 conductors with the same cross-section, flexible with TWIN toe cap with plastic sleeve | 0.5 mm² ... 1 mm² |
| Nominal current | 32 A |
| Maximum Charging Current | 57 A |
| Maximum Sum Current | 63 A |
| Nominal voltage | 800 V |
| Collective connection | |
| Peel Length | 12 mm ... 14 mm |
| Standard-compliant connection | IEC 60998-2-2 |
| Rigid conductor section | 0.5 mm² ... 10 mm² |
| AWG Conductor Section | 20 ... 6 (Converted according to IEC) |
| Flexible conductor section | 0.5 mm² ... 10 mm² |
| Flexible Wire Section [AWG] | 20 ... 8 (Converted according to IEC) |
| Flexible cable section (toe cap without plastic sleeve) | 0.5 mm² ... 10 mm² |
| Flexible cable section (toe cap with plastic sleeve) | 0.5 mm² ... 10 mm² |
| Flexible cable section (2 conductors with the same section with TWIN ferrule with plastic sleeve) | 0.5 mm² ... 4 mm² |
| 2 conductors with the same cross-section, flexible with TWIN toe cap with plastic sleeve | 0.5 mm² ... 4 mm² |
| Nominal current | 57 A |
| Maximum Charging Current | 57 A |
| Nominal Section | 10 mm² |
| Branch Directly pluggable connection section | |
| Rigid conductor section | 0.5 mm² ... 6 mm² |
| Rigid Wire Section [AWG] | 20 ... 10 (Converted according to IEC) |
| Flexible cable section (toe cap without plastic sleeve) | 0.75 mm² ... 4 mm² |
| Flexible cable section (toe cap with plastic sleeve) | 0.5 mm² ... 4 mm² |
| Collective connection Plug-in connection section | |
| Rigid conductor section | 0.5 mm² ... 16 mm² |
| Flexible cable section (toe cap without plastic sleeve) | 1 mm² ... 10 mm² |
| Flexible cable section (toe cap with plastic sleeve) | 1 mm² ... 10 mm² |
| Width | 64.8 mm |
| Height | 45.7 mm |
| Depth at NS 35/7.5 | 30.9 mm |
| Colour | grey (RAL 7042) |
| Flammability class according to UL 94 | V0 |
| Insulating material group | I |
| Insulating material | PA |
| Static use of cold insulating material | -60 °C |
| Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 130 °C |
| Relative Insulating Material Temperature Index (Elec., UL 746 B) | 130 °C |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
| Heat Emission Calorimeter NFPA 130 (ASTM E 1354) | 28 MJ/kg |
| Flammability of NFPA 130 Surfaces (ASTM E 162) | approved |
| NFPA 130 Specific Optical Flue Gas Density (ASTM E 662) | approved |
| NFPA 130 Flue Gas Toxicity (SMP 800C) | approved |
| Impulse Voltage Test | |
| Test Voltage Nominal Value | 9.8 kV |
| Result | Approved Test |
| Heating Verification | |
| Heating test requirement | Temperature rise ≤ 45 K |
| Result | Approved Test |
| Permissible short-term current 10 mm² | 1.2 kA |
| Result | Approved Test |
| Dielectric Strength with Operating Frequency | |
| Test Voltage Nominal Value | 2 kV |
| Result | Approved Test |
| Mechanical data | |
| Open sidewall | No |
| Mechanical resistance | |
| Result | Approved Test |
| Fixing on the bracket | |
| Rail/Fixing Surface | NS 35/NS 15 |
| Nominal Value Test Force | 5 N |
| Result | Approved Test |
| Observation | If multiple blocks are arranged in a row, it is recommended to place a DIN rail adapter under the connection point or a flange element between the blocks. |
| In variants with 6 or 7 connections, it is sufficient to place a rail adapter in the centre for each block and a flange element for every two blocks. | |
| In case of use of the PTFIX-NS35 rail adapter, a maximum of half of a block can protrude in a row. | |
| Checking for damage to conductors and loosening | |
| Rotation speed | 10 r.p.m. |
| Rotations | 135 |
| Conductor Section/Weight | 0.5 mm2/0.3 kg |
| 10 mm2/2 kg | |
| Result | Approved Test |
| Checking for damage to conductors and loosening | |
| Rotation speed | 10 r.p.m. |
| Rotations | 135 |
| Conductor Section/Weight | 0.2 mm2/0.2 kg |
| 4 mm2/0.9 kg | |
| 6 mm2/1.4 kg | |
| Result | Approved Test |
| Aging | |
| Temperature Cycles | 192 |
| Result | Approved Test |
| Needle Flame Test | |
| Performance Time | 30 sec |
| Result | Approved Test |
| Broadband Oscillation/Noise | |
| Test Specification | DIN EN 50155 (VDE 0115-200):2008-03 |
| Spectrum | Category 2 durability test, on the bogie |
| frequency | f1= 5 Hz to f2= 250 Hz |
| ASD Level | 6.12 (m/s²)²/Hz |
| Acceleration | 3.12g |
| Test duration per axis | 5 h |
| Test Directions | X, Y, and Z axes |
| Result | Approved Test |
| Crash | |
| Test Specification | DIN EN 50155 (VDE 0115-200):2008-03 |
| Shock Type | Semi-sinusoid |
| Acceleration | 30g |
| Duration of the crash | 18 ms |
| Number of collisions per steering | 3 |
| Test Directions | X, Y, and Z axes (pos. and neg.) |
| Result | Approved Test |
| Environmental conditions | |
| Ambient Temperature (Service) | -60 °C ... 110 °C (Operating temperature range incl. self-heating, max. short-term operating temperature; see RTI Elec.) |
| Ambient Temperature (Storage/Transport) | -25°C ... 60 °C (For a short time, no more than 24 hours, from -60 °C to +70 °C) |
| Ambient Temperature (Mounting) | -5 °C ... 70 °C |
| Ambient Temperature (Drive) | -5 °C ... 70 °C |
| Permissible air humidity (service) | 20 % ... 90 % |
| Permissible air humidity (storage/transport) | 30 % ... 70 % |
| Standard-compliant connection | IEC 60947-7-1 |
| IEC 60998-2-2 |
| Type of mounting | NS 35/7.5 |
| NS 35/15 |