View larger
PTFIX 10/18X4-NS35A BU 3273770 PHOENIX CONTACT Block for distribution, nominal voltage: 800 V, rated current..
PTFIX 10/18X4-NS35A BU
3273770
PHOENIX CONTACT
8 Pcs.
Automation > Feed-through terminal block
FIX block System
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact PTFIX 10/18X4-NS35A BU is a distribution terminal designed for organized power and signal routing within electrical panels and control enclosures. Terminal blocks of this classification allow technicians to securely manage multiple connections and branch circuits from a single feed point while maintaining clean installation geometry. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- General Observation: The maximum charging current of the various terminal points must not be exceeded.
- Product Type: Distribution terminal
- Number of connections: 19
- Number of rows: 1
- Potential: 1
- Data Maintenance Status Article Review: 01
- Insulation Properties Surge Category: Iii
- Degree of pollution: 3
- Dimensioning Transient Voltage: 6 kV
- Maximum Dissipated Power with Nominal Condition: 1.02 W
- Feeding: Yes
- Number of connections per floor: 19
- Nominal Section: 4 mm²
- AWG Sizing Section: 10
- Derivation Peel Length: 10 mm ... 12 mm
- Male Gauge: A4
More info
▲| General | |
| Observation | The maximum charging current of the various terminal points must not be exceeded. |
| For applications for power distribution, IEC 60364-4-43:2008 must be observed, as amended + correction Oct. 2008 (DIN VDE 0100-430:2010-10) part 433.2 et seq. | |
| Product Type | Distribution terminal |
| Number of connections | 19 |
| Number of rows | 1 |
| Potential | 1 |
| Data Maintenance Status | |
| Article Review | 01 |
| Insulation Properties | |
| Surge Category | Iii |
| Degree of pollution | 3 |
| Dimensioning Transient Voltage | 6 kV |
| Maximum Dissipated Power with Nominal Condition | 1.02 W |
| Feeding | Yes |
| Number of connections per floor | 19 |
| Nominal Section | 4 mm² |
| AWG Sizing Section | 10 |
| Derivation | |
| Peel Length | 10 mm ... 12 mm |
| Male Gauge | A4 |
| Standard-compliant connection | IEC 60947-7-1 |
| Rigid conductor section | 0.2 mm² ... 6 mm² |
| AWG Conductor Section | 24 ... 10 (Converted according to IEC) |
| Flexible conductor section | 0.2 mm² ... 4 mm² |
| Flexible Wire Section [AWG] | 24 ... 12 (Converted according to IEC) |
| Flexible cable section (toe cap without plastic sleeve) | 0.2 mm² ... 4 mm² |
| Flexible cable section (toe cap with plastic sleeve) | 0.2 mm² ... 4 mm² |
| 2 conductors with the same cross-section, flexible with TWIN toe cap with plastic sleeve | 0.5 mm² ... 1 mm² |
| Nominal current | 32 A |
| Maximum Charging Current | 57 A |
| Maximum Sum Current | 63 A |
| Nominal voltage | 800 V |
| Collective connection | |
| Peel Length | 12 mm ... 14 mm |
| Standard-compliant connection | IEC 60998-2-2 |
| Rigid conductor section | 0.5 mm² ... 10 mm² |
| AWG Conductor Section | 20 ... 6 (Converted according to IEC) |
| Flexible conductor section | 0.5 mm² ... 10 mm² |
| Flexible Wire Section [AWG] | 20 ... 8 (Converted according to IEC) |
| Flexible cable section (toe cap without plastic sleeve) | 0.5 mm² ... 10 mm² |
| Flexible cable section (toe cap with plastic sleeve) | 0.5 mm² ... 10 mm² |
| Flexible cable section (2 conductors with the same section with TWIN ferrule with plastic sleeve) | 0.5 mm² ... 4 mm² |
| 2 conductors with the same cross-section, flexible with TWIN toe cap with plastic sleeve | 0.5 mm² ... 4 mm² |
| Nominal current | 57 A |
| Maximum Charging Current | 57 A |
| Nominal Section | 10 mm² |
| Branch Directly pluggable connection section | |
| Rigid conductor section | 0.5 mm² ... 6 mm² |
| Rigid Wire Section [AWG] | 20 ... 10 (Converted according to IEC) |
| Flexible cable section (toe cap without plastic sleeve) | 0.75 mm² ... 4 mm² |
| Flexible cable section (toe cap with plastic sleeve) | 0.5 mm² ... 4 mm² |
| Collective connection Plug-in connection section | |
| Rigid conductor section | 0.5 mm² ... 16 mm² |
| Flexible cable section (toe cap without plastic sleeve) | 1 mm² ... 10 mm² |
| Flexible cable section (toe cap with plastic sleeve) | 1 mm² ... 10 mm² |
| Width | 64.8 mm |
| Height | 45.7 mm |
| Depth at NS 35/7.5 | 30.9 mm |
| Colour | blue (RAL 5015) |
| Flammability class according to UL 94 | V0 |
| Insulating material group | I |
| Insulating material | PA |
| Static use of cold insulating material | -60 °C |
| Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 130 °C |
| Relative Insulating Material Temperature Index (Elec., UL 746 B) | 130 °C |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
| Heat Emission Calorimeter NFPA 130 (ASTM E 1354) | 28 MJ/kg |
| Flammability of NFPA 130 Surfaces (ASTM E 162) | approved |
| NFPA 130 Specific Optical Flue Gas Density (ASTM E 662) | approved |
| NFPA 130 Flue Gas Toxicity (SMP 800C) | approved |
| Impulse Voltage Test | |
| Test Voltage Nominal Value | 9.8 kV |
| Result | Approved Test |
| Heating Verification | |
| Heating test requirement | Temperature rise ≤ 45 K |
| Result | Approved Test |
| Permissible short-term current 10 mm² | 1.2 kA |
| Result | Approved Test |
| Dielectric Strength with Operating Frequency | |
| Test Voltage Nominal Value | 2 kV |
| Result | Approved Test |
| Mechanical data | |
| Open sidewall | No |
| Mechanical resistance | |
| Result | Approved Test |
| Fixing on the bracket | |
| Rail/Fixing Surface | NS 35/NS 15 |
| Nominal Value Test Force | 5 N |
| Result | Approved Test |
| Observation | If multiple blocks are arranged in a row, it is recommended to place a DIN rail adapter under the connection point or a flange element between the blocks. |
| In variants with 6 or 7 connections, it is sufficient to place a rail adapter in the centre for each block and a flange element for every two blocks. | |
| In case of use of the PTFIX-NS35 rail adapter, a maximum of half of a block can protrude in a row. | |
| Checking for damage to conductors and loosening | |
| Rotation speed | 10 r.p.m. |
| Rotations | 135 |
| Conductor Section/Weight | 0.5 mm2/0.3 kg |
| 10 mm2/2 kg | |
| Result | Approved Test |
| Checking for damage to conductors and loosening | |
| Rotation speed | 10 r.p.m. |
| Rotations | 135 |
| Conductor Section/Weight | 0.2 mm2/0.2 kg |
| 4 mm2/0.9 kg | |
| 6 mm2/1.4 kg | |
| Result | Approved Test |
| Aging | |
| Temperature Cycles | 192 |
| Result | Approved Test |
| Needle Flame Test | |
| Performance Time | 30 sec |
| Result | Approved Test |
| Broadband Oscillation/Noise | |
| Test Specification | DIN EN 50155 (VDE 0115-200):2008-03 |
| Spectrum | Category 2 durability test, on the bogie |
| frequency | f1= 5 Hz to f2= 250 Hz |
| ASD Level | 6.12 (m/s²)²/Hz |
| Acceleration | 3.12g |
| Test duration per axis | 5 h |
| Test Directions | X, Y, and Z axes |
| Result | Approved Test |
| Crash | |
| Test Specification | DIN EN 50155 (VDE 0115-200):2008-03 |
| Shock Type | Semi-sinusoid |
| Acceleration | 30g |
| Duration of the crash | 18 ms |
| Number of collisions per steering | 3 |
| Test Directions | X, Y, and Z axes (pos. and neg.) |
| Result | Approved Test |
| Environmental conditions | |
| Ambient Temperature (Service) | -60 °C ... 110 °C (Operating temperature range incl. self-heating, max. short-term operating temperature; see RTI Elec.) |
| Ambient Temperature (Storage/Transport) | -25°C ... 60 °C (For a short time, no more than 24 hours, from -60 °C to +70 °C) |
| Ambient Temperature (Mounting) | -5 °C ... 70 °C |
| Ambient Temperature (Drive) | -5 °C ... 70 °C |
| Permissible air humidity (service) | 20 % ... 90 % |
| Permissible air humidity (storage/transport) | 30 % ... 70 % |
| Standard-compliant connection | IEC 60947-7-1 |
| IEC 60998-2-2 |
| Type of mounting | NS 35/7.5 |
| NS 35/15 |