View larger
PTCB E1 24DC/1-3A NO 2909909 PHOENIX CONTACT Electronic device circuit breaker
PTCB E1 24DC/1-3A NO
2909909
PHOENIX CONTACT
1 Pcs.
Automation > Device circuit breaker
Over Current Protection
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Protection of sensitive control circuits is handled reliably by the Phoenix Contact PTCB E1 24DC/1-3A NO electronic device circuit breaker. These components safeguard industrial automation networks against overcurrent conditions and short circuits, helping to prevent equipment damage and unplanned downtime in complex machinery layouts.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Number of poles (EF001391): 1
- Width (EF000008): 6.2 mm
- Height (EF000040): 105.8 mm
- Depth (EF000049): 55.6 mm
- Operating voltage (EF000111): 27.5 V
- Nominal current (EF000001): 24 A
- Active current limitation x IN (EF011922): 0
- Fuse type (EF011923): Electronic
- Fail safe element (EF011924): 4 A
- Switch-off time (EF011925): 0.01 ms
- Max. capacitive load (EF011926): 0.014 µF
- With remote signalling contact (EF000422): Yes
- Ambient temperature during operating (EF007515): -30 °C
More info
▲Key Commercial Data
| Orderkey | 2909909 |
|---|---|
| Packing unit | 1 pc |
| GTIN | 4055626408767 |
| Weight per Piece (excluding packing) | 27.580 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -25 °C ... 60 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 70 °C |
| Humidity test | 96 h, 95% RH, 40°C |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Shock (operation) | 30g (IEC 60068-2-27, Test Ea) |
| Vibration (operation) | 10 Hz ... 59.6 Hz (Amplitude ±0.35 mm; in accordance with IEC 60068-2-6, Test Fc) |
| 59.6 Hz … 150 Hz (Acceleration 5g; in accordance with IEC 60068-2-6, Test Fc) | |
| Degree of protection | IP20 |
General
| Flammability rating according to UL 94 | V-0 |
|---|---|
| Mounting type | DIN rail: 35 mm |
| Color | traffic grey A RAL 7042 |
| Number of positions | 1 |
| Protection class | III |
| Type | DIN rail module, one-piece |
Electrical data
| Fuse type | electronic |
|---|---|
| Rated surge voltage | 0.5 kV |
| Operating voltage | 18 V DC ... 27.5 V DC |
| Rated voltage | 24 V DC |
| Rated current IN | 24 A DC (Total current input) |
| 3 A DC () | |
| 1 / 2 / 3 A DC (adjustable) | |
| Measuring tolerance I | ± 15 % |
| Feedback resistance | max. 35 V DC |
| Fail-safe element | 4 A DC |
| Efficiency | > 99 % |
| Closed circuit current I0 | typ. 12 mA |
| Power dissipation | typ. 0.3 W (No-load operation) |
| < 0.9 W (Nominal operation) | |
| Module initialization time | 1 s |
| Waiting time after switch off of a channel | 5 s (at overload / short circuit) |
| Temperature derating | 21 A (Total current at 60°C) |
| 24 A (Total current at 50°C) | |
| 3 A (Channel current at 60°C) | |
| 3 A (Channel current at 50°C) | |
| Tripping method | E (electronic) |
| Required backup fuse | not required, integrated failsafe element |
| Dielectric strength | max. 35 V DC (Load circuit) |
| Voltage drop | 0.06 V (at 2 A) |
| MTBF (IEC 61709, SN 29500) | 28571428 h (at 25°C with 21% load) |
| 14084507 h (at 40°C with 34.25% load) | |
| 2053388 h (at 60°C with 100% load) | |
| Shutdown time load circuit | ≤ 10 ms (for short circuit > 2.0 x IN) |
| 1 s (1.2 ... 2.0 x IN) | |
| Undervoltage shutdown load circuit | ≤ 17.8 V DC (active) |
| ≥ 18.8 V DC (inactive) | |
| Surge voltage shutdown load circuit | ≥ 27.5 V DC (active) |
| ≤ 27 V DC (inactive) | |
| Max. capacitive load load circuit | 20000 µF (Depending on the current setting and the short-circuit current available) |
Remote indication contact
| Connection name | Remote indication circuit |
|---|---|
| Switching function | N/O contact |
| Stripping length | 10 mm |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 14 |
| Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve | 0.2 mm² ... 2.5 mm² |
| DC operating voltage | 0 V DC ... 30 V DC |
| DC operating current | 100 mA DC |
Connection data
| Connection name | Main circuit IN+ |
|---|---|
| Connection method | Push-in connection |
| Stripping length | 10 mm |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
| Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve | 0.2 mm² ... 2.5 mm² |
| Connection name | Main circuit IN- |
| Connection method | Push-in connection |
| Stripping length | 10 mm |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
| Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve | 0.2 mm² ... 2.5 mm² |
| Connection name | Main circuit OUT |
| Connection method | Push-in connection |
| Stripping length | 10 mm |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
| Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve | 0.2 mm² ... 2.5 mm² |
Standards and Regulations
| Standards/specifications | EN 61000-6-2 |
|---|---|
| EN 61000-6-3 | |
| EN 60068-2-78 | |
| EN 50178 | |
| EN 60068-2-6 | |
| EN 60068-2-27 | |
| UL 508 | |
| UL 2367 | |
| UL 1310 Class 2 Power Units |