View larger
PT 5-HF-24DC-ST 2906002 PHOENIX CONTACT Surge protection device
PT 5-HF-24DC-ST
2906002
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Phoenix Contact PT 5-HF-24DC-ST surge protection device offers targeted transient suppression for high-frequency measurement and control signals. Pluggable surge arresters allow engineers to quickly maintain and replace protective elements within industrial control cabinets without rewiring. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Nominal voltage AC (EF008798): 24 V
More info
▲Key Commercial Data
| Orderkey | 2906002 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 160 (C-4-2017) |
| GTIN | 4055626013398 |
| Weight per Piece (excluding packing) | 22.050 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 85 °C |
|---|---|
| Altitude | ≤ 2000 m |
| Degree of protection | IP20 |
General
| Housing material | PA 6.6 |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | black |
| Type | Male |
| Number of positions | 5 |
| Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
Protective circuit
| IEC test classification | C1 |
|---|---|
| C2 | |
| C3 | |
| D1 | |
| VDE requirement class | C1 |
| C2 | |
| C3 | |
| D1 | |
| Nominal voltage UN | 24 V DC |
| Maximum continuous voltage UC | 28 V DC |
| Rated current | 450 mA (45°C) |
| Operating effective current ICat UC | ≤ 5 µA |
| Residual current IPE | ≤ 5 µA (with PT 2X2-BE) |
| ≤ 1 µA (with PT 2X2+F-BE) | |
| Nominal discharge current In(8/20) µs (line-line) | 10 kA |
| Nominal discharge current In(8/20) µs (line-earth) | 10 kA (with PT 2X2+F-BE) |
| 10 kA (with PT 2X2-BE) | |
| Pulse discharge current Iimp(10/350) µs | 2.5 kA (with PT 2X2-BE) |
| 2.5 kA (with PT 2X2+F-BE) | |
| Total discharge current Itotal(8/20) µs | 20 kA |
| Nominal pulse current Ian (10/1000) µs (line-line) | 25 A |
| Voltage protection level Up(line-line) | ≤ 150 V (C1 - 1 kV/500 A) |
| ≤ 165 V (C2 - 10 kV / 5 kA) | |
| ≤ 450 V (C2 - 10 kA) | |
| ≤ 50 V (C3 - 25 A) | |
| Voltage protection level Up(line-earth) | ≤ 150 V (C1 - 1 kV/500 A) |
| ≤ 700 V (C1 - 1 kV / 500 A with PT 2X2+F-BE) | |
| ≤ 165 V (C2 - 10 kV / 5 kA) | |
| ≤ 900 V (C2 - 10 kV / 5 kA with PT 2X2+F-BE) | |
| ≤ 450 V (C2 - 10 kA) | |
| ≤ 1000 V (C2 - 10 kA with PT 2X2+F-BE) | |
| ≤ 50 V (C3 - 25 A) | |
| ≤ 800 V (C3 - 25 A with PT 2X2+F-BE) | |
| Voltage protection level Up(line-signalground) | ≤ 150 V (C1 - 1 kV/500 A) |
| ≤ 150 V (C1 - 1 kV / 500 A with PT 2X2+F-BE) | |
| ≤ 165 V (C2 - 10 kV / 5 kA) | |
| ≤ 165 V (C2 - 10 kV / 5 kA with PT 2X2-BE) | |
| ≤ 450 V (C2 - 10 kA) | |
| ≤ 450 V (C2 - 10 kV / 5 kA with PT 2X2-BE) | |
| ≤ 50 V (C3 - 25 A) | |
| ≤ 50 V (C3 - 25 A with PT 2X2-BE) | |
| Response time tA(line-line) | ≤ 500 ns |
| Response time tA(line-earth) | ≤ 500 ns |
| Input attenuation aE, sym. | typ. 0.3 dB (≤ 13 MHz/100 Ω) |
| Cut-off frequency fg (3 dB), sym. in 100 Ohm system | typ. 70 MHz |
| Capacity (line-line) | typ. 23 pF |
| Resistance in series | 2.2 Ω ±10 % |
| Max. required back-up fuse | 500 mA (T) |
Connection data
| Connection method | Screw connection (in connection with the base element) |
|---|---|
| Screw thread | M3 |
| Tightening torque | 0.8 Nm |
| Stripping length | 8 mm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
Connection, equipotential bonding
| Stripping length | 8 mm |
|---|---|
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 4 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |