PT 2XEX(I)-24DC-ST 2838225 PHOENIX CONTACT Surge protection plug
PT 2XEX(I)-24DC-ST
2838225
PHOENIX CONTACT
10 Pcs.
Automation > Combined arrester for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact surge protection plug (part number PT 2XEX(I)-24DC-ST) provides reliable overvoltage protection for intrinsically safe measurement and control applications. These modular elements plug directly into base terminals inside control cabinets to protect sensitive automation hardware from electrical surges. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2838225
- Packing unit: 10 pc
- Catalog page: Page 132 (C-4-2017)
- GTIN: 4017918182861
- Weight per Piece (excluding packing): 21.090 g
- Custom tariff number: 85363010
- Country of origin: DE (Germany)
- Height: 44.8 mm
- Width: 17.5 mm
- Depth: 51.7 mm
- Horizontal pitch: 1 Div.
- Complete module height: 90 mm
- Complete module width: 17.7 mm
- Complete module depth: 65.5 mm
- Ambient temperature (operation): -40 °C ... 85 °C
- Ambient temperature (storage/transport): -40 °C ... 85 °C
More info
▲Key Commercial Data
| Orderkey | 2838225 |
|---|---|
| Packing unit | 10 pc |
| Catalog page | Page 132 (C-4-2017) |
| GTIN | 4017918182861 |
| Weight per Piece (excluding packing) | 21.090 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Dimensions
| Height | 44.8 mm |
|---|---|
| Width | 17.5 mm |
| Depth | 51.7 mm |
| Horizontal pitch | 1 Div. |
| Complete module height | 90 mm |
| Complete module width | 17.7 mm |
| Complete module depth | 65.5 mm |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 85 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Degree of protection | IP20 |
General
| Housing material | PA 6.6 |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | sky blue RAL 5015 |
| Mounting type | on base element |
| Type | Male |
| Number of positions | 4 |
| Direction of action | Line-Line & Line-Signal Ground/Shield & Signal Ground/Shield-Earth Ground |
| Arrester can be tested with CHECKMASTER from software version: | From SW rev. 1.00 |
Protective circuit
| IEC test classification | C1 |
|---|---|
| C2 | |
| C3 | |
| D1 | |
| Nominal voltage UN | 24 V DC |
| Maximum continuous voltage UC | 30 V DC |
| 21 V AC | |
| Rated current | 325 mA (40 °C) |
| Operating effective current ICat UC | ≤ 5 µA |
| Residual current IPE | ≤ 4 µA |
| Nominal discharge current In(8/20) µs (line-line) | 10 kA |
| Nominal discharge current In(8/20) µs (line-earth) | 10 kA |
| Pulse discharge current Iimp(10/350) µs (line-line) | 1 kA |
| Pulse discharge current Iimp(10/350) µs (line-earth) | 2 kA (in total) |
| Total discharge current Itotal(8/20) µs | 20 kA |
| Total discharge current Itotal(10/350) µs | 2 kA |
| Max. discharge current Imax(8/20) µs maximum (line-line) | 10 kA |
| Max. discharge current Imax(8/20) µs maximum (line-earth) | 20 kA (in total) |
| Nominal pulse current Ian (10/1000) µs (line-line) | 30 A |
| Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 45 V |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 1 kV |
| Output voltage limitation at 1 kV/µs (line-line) static | ≤ 45 V |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 1 kV |
| Residual voltage at In(line-line) | ≤ 45 V |
| Residual voltage with Ian (10/1000) µs (line-line) | ≤ 50 V |
| Voltage protection level Up(line-line) | ≤ 45 V (C1 - 0.5 kV / 250 A) |
| ≤ 50 V (C1 - 1 kV/500 A) | |
| ≤ 60 V (C2 - 2 kV/1 kA) | |
| ≤ 100 V (C2 - 10 kV / 5 kA) | |
| ≤ 50 V (C3 - 10 A) | |
| ≤ 50 V (C3 - 25 A) | |
| ≤ 150 V (D1 - 1 kA) | |
| Voltage protection level Up(line-earth) | ≤ 1 kV (C1 - 1 kV/500 A) |
| ≤ 1 kV (C2 - 2 kV/1 kA) | |
| ≤ 1 kV (C2 - 10 kV / 5 kA) | |
| ≤ 1 kV (D1 - 1 kA) | |
| Response time tA(line-line) | ≤ 1 ns |
| Response time tA(line-earth) | ≤ 100 ns |
| Input attenuation aE, sym. | typ. 0.5 dB (≤ 900 kHz / 50 Ω) |
| typ. 0.2 dB (≤ 300 kHz / 150 Ω) | |
| typ. 0.1 dB (≤ 60 kHz / 600 Ω) | |
| Cut-off frequency fg (3 dB), sym. in 50 Ohm system | typ. 4.5 MHz |
| Cut-off frequency fg (3 dB), sym. in 150 Ohm system | typ. 1.6 MHz |
| Cut-off frequency fg (3 dB), sym. in 600 Ohm system | typ. 400 kHz |
| Resistance in series | 2.2 Ω ±10 % |
| Surge protection fault message | none |
| Max. required back-up fuse | 315 mA (T) |
| Impulse durability (line-line) | C1 - 0.5 kV / 250 A |
| C1 - 1 kV/500 A | |
| C2 - 2 kV / 1 kA | |
| C2 - 10 kV/5 kA | |
| C3 - 10 A | |
| C3 - 25 A | |
| D1 - 1 kA | |
| Impulse durability (line-earth) | C1 - 1 kV/500 A |
| C2 - 2 kV/1 kA | |
| C2 - 10 kV/5 kA | |
| D1 - 1 kA | |
| Alternating current carrying capacity (line-earth) | 10 A - 1 s |
Connection data
| Connection method | Screw connection (in connection with the base element) |
|---|---|
| Screw thread | M3 |
| Tightening torque | 0.5 Nm |
| Stripping length | 8 mm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
Standards and Regulations
| Standards/specifications | EN 61643-21 A2:2013 |
|---|---|
| EN 60079-0 2012 | |
| EN 60079-11 2012 | |
| EN 60079-26 2007 | |
| IEC 61643-21 A2:2012 | |
| IEC 60079-0 2011 | |
| IEC 60079-11 2011 | |
| IEC 60079-26 2006 |
General
| Maximum inner capacitance Ci | 1.3 nF |
|---|---|
| Max. internal inductance Li | 1 µH |
| Maximum inner time factor (Ri/Li) | ≤ 0.2 µs |
| Max. input current Ii | 325 mA (T4 / ≤ 80°C) |
| 325 mA (T5 / ≤ 55 °C) | |
| 325 mA (T6 / ≤ 40 °C) | |
| Max. input voltage Ui | 30 V DC |
| max. input power Pi | 3 W |
| Ambient temperature (operation) | -40 °C ... 80 °C (T4) |
| -40 °C ... 55 °C (T5) | |
| -40 °C ... 40 °C (T6) |
Conformity / approvals
| ATEX | II 1G Ex ia IIC T4...T6 Ga |
|---|---|
| II 1D Ex ia IIIC T135°C...T85°C Da | |
| IECEx | Ex ia IIC T4...T6 Ga |
| Ex ia IIIC T135 °C...T85 °C Da |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |