View larger
PT 2X2- 5DC-ST 2838241 PHOENIX CONTACT Surge protection plug
PT 2X2-5DC-ST
2838241
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Phoenix Contact PT 2X2-5DC-ST 2838241 operates as a surge protection plug designed to defend low-voltage data loops from lightning and switching transients. Pluggable surge suppressors of this variety enable quick replacement and routine testing without disturbing the underlying field wiring infrastructure. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Nominal voltage DC (EF008799): 5 V
More info
▲Key Commercial Data
| Orderkey | 2838241 |
|---|---|
| Packing unit | 10 pc |
| Catalog page | Page 99 (C-4-2017) |
| GTIN | 4017918182656 |
| Weight per Piece (excluding packing) | 20.900 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Dimensions
| Height | 44.8 mm |
|---|---|
| Width | 17.5 mm |
| Depth | 51.7 mm |
| Horizontal pitch | 1 Div. |
| Complete module height | 90 mm |
| Complete module width | 17.7 mm |
| Complete module depth | 65.5 mm |
General
| Housing material | PA 6.6 |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | black |
| Standards for cearances and creepage distances | VDE 0110-1 |
| IEC 60664-1 | |
| Mounting type | on base element |
| Type | Male |
| Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
| Arrester can be tested with CHECKMASTER from software version: | From SW rev. 1.00 |
Protective circuit
| IEC test classification | C1 |
|---|---|
| C2 | |
| C3 | |
| D1 | |
| Nominal voltage UN | 5 V DC |
| Maximum continuous voltage UC | 6 V DC |
| 4 V AC | |
| Rated current | 450 mA (45°C) |
| Operating effective current ICat UC | ≤ 1 mA |
| Residual current IPE | ≤ 1 µA (with PT 2X2+F-BE) |
| ≤ 4 µA | |
| Nominal discharge current In(8/20) µs (line-line) | 10 kA |
| Nominal discharge current In(8/20) µs (line-earth) | 10 kA |
| Pulse discharge current Iimp(10/350) µs | 2.5 kA (per path) |
| Total discharge current Itotal(8/20) µs | 20 kA |
| Max. discharge current Imax(8/20) µs maximum (line-line) | 10 kA |
| Max. discharge current Imax(8/20) µs maximum (line-earth) | 10 kA |
| Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 12 V |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 450 V |
| Output voltage limitation at 1 kV/µs (line-line) static | ≤ 10 V |
| Residual voltage at In(line-line) | ≤ 10 V |
| Residual voltage at In(line-signalground) | ≤ 450 V |
| Residual voltage with Ian (10/1000) µs (line-line) | ≤ 12 V |
| Response time tA(line-line) | ≤ 1 ns |
| Response time tA(line-earth) | ≤ 100 ns |
| Input attenuation aE, sym. | 0.5 dB (≤ 200 kHz) |
| Input attenuation aE, asym. | |
| Cut-off frequency fg (3 dB), sym. in 50 Ohm system | typ. 1 MHz |
| Capacity (line-line) | 6 nF |
| Resistance in series | 2.2 Ω |
| Surge protection fault message | none |
| Impulse durability (line-line) | C2 - 10 kV/5 kA |
| Impulse durability (line-earth) | C2 - 10 kV/5 kA |
| D1 - 2.5 kA |
Connection data
| Connection method | Screw connection (in connection with the base element) |
|---|---|
| Screw thread | M3 |
| Tightening torque | 0.8 Nm |
| Stripping length | 8 mm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
Standards and Regulations
| Standards/regulations | IEC 61643-21 |
|---|---|
| DIN EN 61643-21 | |
| UL 497B | |
| Standards/specifications | IEC 61643-21 2000 |