View larger
PT 6-T P/P HV 1028589 PHOENIX CONTACT Terminal interruptible, rated voltage: 1000 V, nominal current: 32 A, ..
PT 6-T P/P HV
1028589
PHOENIX CONTACT
50 Pcs.
Automation > (Knife) disconnect terminal block
Modular TBs
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Operating as a terminal interruptible, rated voltage: 1000 v, nominal current: 32 a, .. the Phoenix Contact PT 6-T P/P HV 1028589 provides dependable wire termination and signal interruption capabilities for industrial control architecture. Terminal blocks allow technicians to isolate segments for testing without disconnecting permanent field wiring. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product Type: Sectional terminal block
- Product Family: PT
- Number of connections: 2
- Number of rows: 1
- Potential: 1
- Data Maintenance Status Article Review: 03
- Insulation Properties Surge Category: Iii
- Degree of pollution: 3
- Dimensioning Transient Voltage: 8 kV
- Maximum Dissipated Power with Nominal Condition: 1.31 W
- Number of connections per floor: 2
- Nominal Section: 6 mm²
- Peel Length: 10 mm ... 12 mm
- Male Gauge: A5
- Standard-compliant connection: IEC 60947-7-1
- Rigid conductor section: 0.5 mm² ... 10 mm²
More info
▲| General | |
| Observation | In the overhead connection, the user must ensure that the necessary sections to surfaces that conduct electricity are met. |
| You can check the rated current and the maximum load current on the rating curve. | |
| Product Type | Sectional terminal block |
| Product Family | PT |
| Number of connections | 2 |
| Number of rows | 1 |
| Potential | 1 |
| Data Maintenance Status | |
| Article Review | 03 |
| Insulation Properties | |
| Surge Category | Iii |
| Degree of pollution | 3 |
| Dimensioning Transient Voltage | 8 kV |
| Maximum Dissipated Power with Nominal Condition | 1.31 W |
| Number of connections per floor | 2 |
| Nominal Section | 6 mm² |
| Peel Length | 10 mm ... 12 mm |
| Male Gauge | A5 |
| B5 | |
| Standard-compliant connection | IEC 60947-7-1 |
| Rigid conductor section | 0.5 mm² ... 10 mm² |
| AWG Conductor Section | 20 ... 8 (Converted according to IEC) |
| Flexible conductor section | 0.5 mm² ... 10 mm² |
| Flexible Wire Section [AWG] | 20 ... 8 (Converted according to IEC) |
| Flexible cable section (toe cap without plastic sleeve) | 0.5 mm² ... 10 mm² |
| Flexible cable section (toe cap with plastic sleeve) | 0.5 mm² ... 10 mm² |
| 2 conductors with the same cross-section, flexible with TWIN toe cap with plastic sleeve | 0.5 mm² ... 2.5 mm² If TWIN bushings are used, we recommend a minimum standard bushing length of 13 mm. |
| Nominal current | 32 A |
| Maximum Charging Current | 32 A (with rigid 10 mm² cable cross-section) |
| Nominal voltage | 1000 V |
| Nominal Section | 6 mm² |
| Directly pluggable connection section | |
| Rigid conductor section | 1 mm² ... 10 mm² |
| Flexible cable section (toe cap without plastic sleeve) | 1.5 mm² ... 6 mm² |
| Flexible cable section (toe cap with plastic sleeve) | 1.5 mm² ... 6 mm² |
| Width | 10.2 mm |
| Height | 91 mm |
| Depth | 63.1 mm |
| Depth in NS 32 | 69.3 mm |
| Depth at NS 35/7.5 | 64.3 mm |
| Depth at NS 35/15 | 71.8 mm |
| Colour | grey (RAL 7042) |
| Flammability class according to UL 94 | V0 |
| Insulating material group | I |
| Insulating material | PA |
| Static use of cold insulating material | -60 °C |
| Relative Insulating Material Temperature Index (Elec., UL 746 B) | 130 °C |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
| Heat Emission Calorimeter NFPA 130 (ASTM E 1354) | 28 MJ/kg |
| Flammability of NFPA 130 Surfaces (ASTM E 162) | approved |
| NFPA 130 Specific Optical Flue Gas Density (ASTM E 662) | approved |
| NFPA 130 Flue Gas Toxicity (SMP 800C) | approved |
| Impulse Voltage Test | |
| Test Voltage Nominal Value | 9.8 kV |
| Result | Approved Test |
| Heating Verification | |
| Heating test requirement | Temperature rise ≤ 45 K |
| Result | Approved Test |
| Permissible short-term current 4 mm² | 0.48 kA |
| Result | Approved Test |
| Dielectric Strength with Operating Frequency | |
| Test Voltage Nominal Value | 2.2 kV |
| Result | Approved Test |
| Mechanical data | |
| Open sidewall | No |
| Plug Cycles | 250 |
| Mechanical resistance | |
| Result | Approved Test |
| Fixing on the bracket | |
| Rail/Fixing Surface | NS 32/NS 35 |
| Nominal Value Test Force | 5 N |
| Result | Approved Test |
| Checking for damage to conductors and loosening | |
| Rotation speed | 10 r.p.m. |
| Rotations | 135 |
| Conductor Section/Weight | 0.5 mm2/0.3 kg |
| 6 mm2/1.4 kg | |
| 10 mm2/2 kg | |
| Result | Approved Test |
| Life | |
| Plug Cycles | 50 |
| Aging | |
| Temperature Cycles | 192 |
| Result | Approved Test |
| Needle Flame Test | |
| Performance Time | 30 sec |
| Result | Approved Test |
| Broadband Oscillation/Noise | |
| Test Specification | DIN EN 50155 (VDE 0115-200):2018-05 |
| Spectrum | Category 2 durability test, on the bogie |
| frequency | f1= 5 Hz to f2= 250 Hz |
| ASD Level | 6.12 (m/s²)²/Hz |
| Acceleration | 3.12g |
| Test duration per axis | 5 h |
| Test Directions | X, Y, and Z axes |
| Result | Approved Test |
| Crash | |
| Test Specification | DIN EN 50155 (VDE 0115-200):2018-05 |
| Shock Type | Semi-sinusoid |
| Acceleration | 30g |
| Duration of the crash | 18 ms |
| Number of collisions per steering | 3 |
| Test Directions | X, Y, and Z axes (pos. and neg.) |
| Result | Approved Test |
| Environmental conditions | |
| Ambient Temperature (Service) | -60 °C ... 110 °C (Operating temperature range incl. self-heating, max. short-term operating temperature; see RTI Elec.) |
| Ambient Temperature (Storage/Transport) | -25 °C ... 60 °C (for a short time, no more than 24 hours, -60 °C to +70 °C) |
| Ambient Temperature (Mounting) | -5 °C ... 70 °C |
| Ambient Temperature (Drive) | -5 °C ... 70 °C |
| Permissible air humidity (service) | 20 % ... 90 % |
| Permissible air humidity (storage/transport) | 30 % ... 70 % |
| Standard-compliant connection | IEC 60947-7-1 |
| Type of mounting | NS 35/7.5 |
| NS 35/15 | |
| NS 32 |