View larger
PT 4-PE/L/HESILED 60 (5X20) 3002604 PHOENIX CONTACT Fuse modular terminal block
PT 4-PE/L/HESILED 60 (5X20)
3002604
PHOENIX CONTACT
50 Pcs.
Automation > Fuse terminal block
Modular TBs
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Protect industrial control loops and machinery wiring with the Phoenix Contact PT 4-PE/L/HESILED 60 (5X20) 3002604 fuse modular terminal block. Multi-level terminal assemblies are widely deployed in modern control cabinets to save panel space while routing power, ground, and fused signals through a unified rail-mounted interface. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Connectable conductor cross section solid-core (EF007337): 0.2 mm²
- Rated current In (EF008250): 6.3 A
- Rated voltage (EF000228): 60 V
- Number of levels (EF002659): 3
- Mounting method (EF000003): DIN rail (top hat rail) 35 mm
- Width (EF000008): 6.15 mm
- Height (EF000040): 119.5 mm
- Depth (EF000049): 82.58 mm
- Closing plate required (EF002525): Yes
- Colour (EF000007): Black
More info
▲Key Commercial Data
| Orderkey | 3002604 |
|---|---|
| Packing unit | 50 pc |
| Minimum order quantity | 50 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 96 (C-1-2017) |
| GTIN | 4055626369693 |
| Weight per Piece (excluding packing) | 31.800 g |
| Custom tariff number | 85369095 |
| Country of origin | CN (China) |
General
| Note | The current is determined by the fuse used, the voltage by the selected LED. If the fuse is faulty, the downstream circuit will not be disconnected. |
|---|---|
| Number of levels | 3 |
| Number of connections | 5 |
| Nominal cross section | 4 mm² |
| Color | black |
| Insulating material | PA |
| Flammability rating according to UL 94 | V0 |
| Maximum power dissipation for nominal condition | 1.6 W (the value is multiplied when connecting multiple levels) |
| Fuse | G / 5 x 20 |
| Fuse type | Glass / ceramics / ... |
| Rated surge voltage | 6 kV |
| Degree of pollution | 3 |
| Overvoltage category | III |
| Insulating material group | I |
| Maximum power dissipation | max. 1.6 W (With single arrangement of the fuse terminal block in the event of overload) |
| max. 1.6 W (With interconnected arrangement of several fuse terminal blocks in the event of overload) | |
| max. 4 W (With single arrangement of the fuse terminal block in the event of a short-circuit) | |
| max. 2.5 W (With interconnected arrangement of several fuse terminal blocks in the event of a short-circuit) | |
| LED voltage range | 30 V AC/DC ... 60 V AC/DC |
| LED current range | 0.4 mA ... 0.86 mA |
| Connection in acc. with standard | IEC 60947-7-3 |
| Maximum load current | 32 A |
| Nominal current IN | 28 A |
| Nominal voltage UN | 500 V |
| Connection in acc. with standard | IEC 60947-7-3 |
| Maximum load current (upper level) | 6.3 A (the current is determined by the fuse used) |
| Nominal current IN(upper level) | 6.3 A |
| Nominal voltage UN | 60 V (the voltage is determined by the light indicator.) |
| Rated operating voltage | 250 V |
| Open side panel | Yes |
| Shock protection test specification | DIN EN 50274 (VDE 0660-514):2002-11 |
| Back of the hand protection | guaranteed |
| Finger protection | guaranteed |
| Oscillation, broadband noise test result | Test passed |
| Test specification, oscillation, broadband noise | DIN EN 50155 (VDE 0115-200):2008-03 |
| Test spectrum | Service life test category 1, class B, body mounted |
| Test frequency | f1= 5 Hz to f2= 150 Hz |
| ASD level | 0.964 (m/s2)2/Hz |
| Acceleration | 0.58 g |
| Test duration per axis | 5 h |
| Test directions | X-, Y- and Z-axis |
| Shock test result | Test passed |
| Test specification, shock test | DIN EN 50155 (VDE 0115-200):2008-03 |
| Shock form | Half-sine |
| Acceleration | 5 g |
| Shock duration | 30 ms |
| Number of shocks per direction | 3 |
| Test directions | X-, Y- and Z-axis (pos. and neg.) |
| Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
| Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 130 °C |
| Static insulating material application in cold | -60 °C |
| Behavior in fire for rail vehicles (DIN 5510-2) | Test passed |
| Flame test method (DIN EN 60695-11-10) | V0 |
| Oxygen index (DIN EN ISO 4589-2) | >32 % |
| NF F16-101, NF F10-102 Class I | 2 |
| NF F16-101, NF F10-102 Class F | 2 |
| Surface flammability NFPA 130 (ASTM E 162) | passed |
| Specific optical density of smoke NFPA 130 (ASTM E 662) | passed |
| Smoke gas toxicity NFPA 130 (SMP 800C) | passed |
| Calorimetric heat release NFPA 130 (ASTM E 1354) | 28 MJ/kg |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
Connection data
| Conductor cross section solid min. | 0.2 mm² |
|---|---|
| Conductor cross section solid max. | 6 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 4 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 10 |
| Conductor cross section flexible, with ferrule without plastic sleeve min. | 0.25 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve max. | 4 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve min. | 0.25 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve max. | 4 mm² |
| Connection method | Push-in connection |
| Stripping length | 10 mm ... 12 mm |
| Internal cylindrical gage | A4 |
Standards and Regulations
| Connection in acc. with standard | IEC 60947-7-3 |
|---|---|
| IEC 60947-7-3 | |
| Flammability rating according to UL 94 | V0 |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |