Designed for robust electrical defense, the Phoenix Contact PT 2X1VA/S1-230AC-ST surge protection plug provides reliable clamping of overvoltages in industrial instrumentation environments. These pluggable safety elements are integrated into modular base systems to protect automation instrumentation and control loops from electrical surges. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Nominal voltage DC (EF008799): 230 V
More info
▲Key Commercial Data
| Orderkey | 2880024 |
|---|---|
| Packing unit | 10 pc |
| Minimum order quantity | 10 pc |
| Note | Made to Order (non-returnable) |
| GTIN | 4017918956899 |
| Weight per Piece (excluding packing) | 27.280 g |
| Custom tariff number | 85369010 |
| Country of origin | DE (Germany) |
Dimensions
| Height | 44.8 mm |
|---|---|
| Width | 17.5 mm |
| Depth | 51.7 mm |
| Horizontal pitch | 1 Div. |
| Complete module height | 90 mm |
| Complete module width | 17.7 mm |
| Complete module depth | 65.5 mm |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 85 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Degree of protection | IP20 |
General
| Housing material | PA 6.6 |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | jet black RAL 9005 |
| Mounting type | on base element |
| Type | Male |
| Direction of action | Line-Line & Line-Earth Ground |
| Arrester can be tested with CHECKMASTER from software version: | From SW rev. 2.20 |
Additional descriptions
| Note | Technical data is valid in association with the following specified base elements: |
|---|---|
| PT -BE/ FM 2839282 |
Protective circuit
| IEC test classification | C1 |
|---|---|
| C2 | |
| C3 | |
| D1 | |
| Nominal voltage UN | 230 V AC (50/60 Hz) |
| Maximum continuous voltage UC | 320 V DC |
| 320 V AC (50/60 Hz) | |
| Rated current | 26 A AC (30 °C) |
| 1 A DC | |
| Operating effective current ICat UC | ≤ 200 µA AC |
| ≤ 10 µA DC | |
| Residual current IPE | ≤ 400 µA AC |
| ≤ 20 µA DC | |
| Nominal discharge current In(8/20) µs (line-earth) | 2.5 kA |
| Pulse discharge current Iimp(10/350) µs | 500 A (per path) |
| Total discharge current Itotal(8/20) µs | 5 kA |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 850 V |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 850 V |
| Voltage protection level Up(line-earth) | ≤ 850 V (C1 - 1.4 kV / 0.7 kA) |
| ≤ 1050 V (C2 - 5 kV/2,5 kA) | |
| ≤ 820 V (C3 - 100 A) | |
| Response time tA(line-earth) | ≤ 25 ns |
| Input attenuation aE, asym. | typ. 0.3 dB (≤ 500 kHz / 150 Ω) |
| Cut-off frequency fg (3 dB), asym. (GND) in 150 Ohm system | typ. 1.7 MHz |
| Capacity (line-earth) | typ. 2 nF |
| Surge protection fault message | none |
| Max. required back-up fuse | 25 A AC (gL/gG) |
| 1 A DC (T) | |
| Impulse durability (line-earth) | C1 - 1,4 kV / 0,7 kA |
| C2 - 5 kV/2.5 kA | |
| C3 - 100 A | |
| D1 - 500 A |
Connection data
| Connection method | Screw connection (in connection with the base element) |
|---|---|
| Screw thread | M3 |
| Tightening torque | 0.8 Nm |
| Stripping length | 8 mm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
Standards and Regulations
| Standards/specifications | IEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012 |
|---|---|
| EN 61643-21 2001 + A1:2009 + A2:2013 |