PHOENIX CONTACT PSR-SPP-24DC/ESD/5X1/1X2/T10S PSR-SPP- 24DC/ESD/5X1/1X2/T10S 2981509 PHOENIX CONTACT Safety relays View larger
Images are for illustrative purposes only. Please refer to data sheet for details

PSR-SPP- 24DC/ESD/5X1/1X2/T10S 2981509 PHOENIX CONTACT Safety relays

PSR-SPP-24DC/ESD/5X1/1X2/T10S

2981509

PHOENIX CONTACT

1 Pcs.

Safety relays Safety relay for emergency stop monitoring and safety doors up to SIL 3 or cat. 4, PLe according to EN ISO 13849, automatic or manual activation, 3 NO contacts, 1 NC contact, 2 NO contacts with 10.0 s disconnect delay, plug-in push-in terminal block

Automation > Device for monitoring of safety-related circuits
Safety

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Managing fault conditions and emergency circuits in automated environments, the Phoenix Contact PSR-SPP- 24DC/ESD/5X1/1X2/T10S safety relays ensure reliable machine shutdown. These devices process signals from various safety sensors and logic units, executing protective stop commands to safeguard operating personnel and machinery.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Model (EF000010): Basic device
  • Suitable for rail mounting (EF003972): No
  • With detachable clamps (EF003340): Yes
  • Type of electric connection (EF003961): Spring clamp connection
  • Suitable for monitoring of position switches (EF007270): Yes
  • Suitable for monitoring of valves (EF007272): No
  • Suitable for monitoring of tactile sensors (EF007271): No
  • Suitable for monitoring of magnetic switches (EF007266): Yes
  • Suitable for monitoring of proximity switches (EF007267): No
  • With start input (EF003342): No
  • With muting function (EF004057): No
  • With feedback circuit (EF003343): Yes
  • Release-delay (EF001129): 0.6 s
  • With approval for BG BIA (EF004145): No
  • With approval according to UL (EF001783): No
  • Width (EF000008): 45 mm

More info

▲

Key Commercial Data

Orderkey2981509
Packing unit1 pc
GTIN4017918981105
Weight per Piece (excluding packing)452.000 g
Custom tariff number85371098
Country of originDE (Germany)

Note

Utilization restrictionEMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width45 mm
Height112 mm
Depth114.5 mm

Ambient conditions

Ambient temperature (operation)-20 °C ... 55 °C (observe derating)
Ambient temperature (storage/transport)-40 °C ... 70 °C
Max. permissible relative humidity (operation)75 % (on average, 85% infrequently, non-condensing)
Max. permissible humidity (storage/transport)75 % (on average, 85% infrequently, non-condensing)
Maximum altitude≤ 2000 m (Above sea level)

Input data

Rated control circuit supply voltage US24 V DC -15 % / +10 %
Rated control supply current IStyp. 150 mA
Power consumption at UStyp. 3.6 W
Inrush current200 mA (at US)
< 40 mA (with Us/Ixto S10)
< 150 mA (with Us/Ixto S12)
> -60 mA (with Us/Ixto S22)
< 40 mA (with Us/Ixto S34)
< 40 mA (with Us/Ixto S35)
Current consumption< 40 mA (with Us/Ixto S10)
< 40 mA (with Us/Ixto S12)
> -40 mA (with Us/Ixto S22)
0 mA (with Us/Ixto S34)
< 5 mA (with Us/Ixto S35)
Voltage at input/start and feedback circuit24 V DC -15 % / +10 %
Typical response time< 600 ms (automatic start)
< 70 ms (manual start)
Typ. starting time with Us< 600 ms (when controlled via A1)
Typical release time< 20 ms (when controlled via S11/S12 and S21/S22)
< 20 ms (when controlled via A1)
Concurrence input 1/2∞
Recovery time< 1 s
Operating voltage display1 x green LED
Status display4 x green LEDs
Protective circuitSurge protection Suppressor diode
Maximum switching frequency0.5 Hz
Max. permissible overall conductor resistanceapprox. 11 Ω (Input and start circuits at US)
Delay timeK3(t), K4(t) fixed depending on model
Filter time1 ms (at A1 in the event of voltage dips at Us)
max. 1.5 ms (at S10, S12; test pulse width)
7.5 ms (at S10, S12; test pulse rate)
Test pulse rate = 5 x Test pulse width

Output data

Contact type5 enabling current paths
1 signaling current path
Contact materialAgSnO2
Maximum switching voltage250 V AC/DC (Observe the load curve)
Minimum switching voltage5 V AC/DC
Limiting continuous current6 A (N/O contact, pay attention to the derating)
6 A (N/C contact)
Maximum inrush current20 A (Δt  100 ms, undelayed contacts)
8 A (delayed contacts)
Inrush current, minimum10 mA
Sq. Total current55 A2(observe derating)
Interrupting rating (ohmic load) max.144 W (24 V DC, τ = 0 ms)
288 W (48 V DC, τ = 0 ms)
110 W (110 V DC, τ = 0 ms, delayed contacts: 77 W)
88 W (220 V DC, τ = 0 ms)
1500 VA (250 V AC, τ = 0 ms, delayed contacts: 2000 VA)
Maximum interrupting rating (inductive load)42 W (24 V DC, τ = 40 ms, delayed contacts: 48 W)
42 W (48 V DC, τ = 40 ms, delayed contacts: 40 W)
42 W (110 V DC, τ = 40 ms, delayed contacts: 35 W)
42 W (220 V DC, τ = 40 ms, delayed contacts: 33 W)
Switching capacity min.50 mW
Mechanical service life10x 106cycles
Switching capacity (360/h cycles)4 A (24 V DC)
4 A (230 V AC)
Output fuse10 A gL/gG (N/O contact)
6 A gL/gG (N/C contact)

General

Relay typeElectromechanical relay with forcibly guided contacts in accordance with EN 50205
Nominal operating mode100% operating factor
Net weight452 g
Mounting positionany
Mounting typeDIN rail mounting
Degree of protectionIP20
IP54
Min. degree of protection of inst. locationIP54
Housing materialPBT
Housing coloryellow

Connection data

Connection methodSpring-cage connection
pluggableYes
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.1.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.1.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.16
Stripping length8 mm

Safety-related characteristic data

Stop category0
1
DesignationIEC 61508 - High demand
Safety Integrity Level (SIL)3 (for delayed contacts SIL 2)
DesignationIEC 61508 - Low demand
Safety Integrity Level (SIL)3 (for delayed contacts SIL 2)
DesignationEN ISO 13849
Performance level (PL)e (for delayed contacts PL d)
Category4 (Undelayed contacts)
3 (delayed contacts)
DesignationEN 62061
Safety Integrity Level Claim Limit (SIL CL)3 (for delayed contacts SILCL 2)

Standards and Regulations

DesignationAir clearances and creepage distances between the power circuits
Standards/regulationsDIN EN 50178/VDE 0160
Rated insulation voltage250 V AC
Rated surge voltage/insulationBasic insulation 4 kV:
between all current paths and housing
Safe isolation, reinforced insulation 6 kV:
between 13/14, 23/24, 33/34, and the remaining current paths
between 13/14, 23/24, 33/34 among one another
Degree of pollution2
Overvoltage categoryIII
Shock15g
Vibration (operation)10 Hz ...150 Hz, 2g
ConformanceCE-compliant

Environmental Product Compliance

China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.