View larger
PSR-SCP- 24DC/URM4/5X1/2X2 1442021 PHOENIX CONTACT Expansion of 1 or 2 channel contacts, 5 NO contacts, 1 NC..
PSR-SCP-24DC/URM4/5X1/2X2
1442021
PHOENIX CONTACT
1 Pcs.
Automation > Device for monitoring of safety-related circuits
Safety
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Phoenix Contact PSR-SCP-24DC/URM4/5X1/2X2 safety relay acts as an expansion module designed to increase the number of available safety contacts in industrial control loops. Such devices integrate with primary safety controllers to safely interrupt hazardous machine operations when faults occur or emergency stops are triggered.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product Type: Safety Relay
- Product Family: PSRclassic
- application: Expansion module
- Mechanical service life: approx.10 7 Status Change Periodicities
- Relay Type: Electromechanical relay with forced conduction contacts according to IEC/EN 61810-3
- Times Typical Excitation Time with U s: < 25 ms (with Us/with excitation via A11/A12)
- Typical Opening Time: < 20 ms (with Us/with excitation via A11/A12)
- Recovery Time: < 1 sec
- Maximum Dissipated Power with Nominal Condition: 16.7 W (U s = 26.4 V, I L ² = 72 A², P Total Max = 2.3 W + 14.4 W)
- Nominal Operating Type: Working time 100%
- Sizing/Insulation Transient Voltage: See the chapter Coordination of insulations
- Digital: A11, A12 Ticket Description: Safety-oriented
- Number of Entries: 2
- Input Voltage Range Signal "1": 19.2 V ... 26.4 V DC
- Total permissible line resistance max.: 50 Ω
- Protection Circuit: Suppressor diode
More info
▲| Product Type | Safety Relay |
| Product Family | PSRclassic |
| application | Expansion module |
| Mechanical service life | approx.107Status Change Periodicities |
| Relay Type | Electromechanical relay with forced conduction contacts according to IEC/EN 61810-3 |
| Times | |
| Typical Excitation Time with Us | < 25 ms (with Us/with excitation via A11/A12) |
| Typical Opening Time | < 20 ms (with Us/with excitation via A11/A12) |
| Recovery Time | < 1 sec |
| Maximum Dissipated Power with Nominal Condition | 16.7 W (Us= 26.4 V, IL² = 72 A², PTotal Max= 2.3 W + 14.4 W) |
| Nominal Operating Type | Working time 100% |
| Creepage lines and air gaps between circuits | |
| Sizing Insulation Voltage | 250 V |
| 250 V | |
| Sizing/Insulation Transient Voltage | See the chapter Coordination of insulations |
| Digital: A11, A12 | |
| Ticket Description | Safety-oriented |
| Number of Entries | 2 |
| Input Voltage Range Signal "1" | 19.2 V ... 26.4 V DC |
| Total permissible line resistance max. | 50 Ω |
| Protection Circuit | Suppressor diode |
| Current absorption | Typ. 39 mA |
| Relay: Trip circuits (23/24 ... 63/64) | |
| Description of the output | each 2 NO in series, safety-oriented, potential-free |
| Number of outputs | 5 |
| Contact Switching Type | 5 Release Intensity Circuits |
| Contact Material | AgSnO2 |
| Switching voltage | min. 10 V |
| max. 250 V AC | |
| Min. switching power | min. 100 mW |
| Input current | min. 10 mA |
| max. 6 A | |
| Breaking capacity according to IEC 60947-5-1 | 3 A (AC15) |
| 5 A (DC13) | |
| Constant Current Limit | 6 A (observe derating) |
| Square. Current Sum | 72 A2(observe derating) |
| Switching frequency | max. 1 Hz |
| Mechanical service life | 10x 106operations |
| Output fuse | 10 A gL/gG |
| 4 A gL/gG (for low-demand applications) | |
| Relay: Signalling circuit (71/72) | |
| Description of the output | 2 NC in parallel, without safety orientation, floating |
| Number of outputs | 1 |
| Contact Switching Type | 1 x Signal Circuit |
| Contact Material | AgSnO2 |
| Switching voltage | min. 5 V AC/DC |
| max. 250 V AC/DC | |
| Min. switching power | min. 50 mW |
| Input current | min. 10 mA |
| max. 6 A | |
| Breaking capacity according to IEC 60947-5-1 | 1.5 A (AC15) |
| 5 A (DC13) | |
| Constant Current Limit | 6 A |
| Square. Current Sum | 36 A2 |
| Switching frequency | max. 1 Hz |
| Mechanical service life | 10x 106operations |
| Output fuse | 6 A (gL/gG) |
| Relay: Acknowledgment Circuit (11/12) | |
| Description of the output | 2 NC in series, floating |
| Number of outputs | 1 |
| Contact Switching Type | 1 acknowledgment circuit |
| Contact Material | AgSnO2 |
| Switching voltage | max. 250 V AC/DC |
| min. 10 V | |
| Min. switching power | min. 100 mW |
| Input current | max. 3 A |
| Breaking capacity according to IEC 60947-5-1 | 1.5 A (AC15) |
| 3 A (DC13) | |
| Constant Current Limit | 3 A |
| Square. Current Sum | 9 A2 |
| Switching frequency | max. 1 Hz |
| Output fuse | 3 A (gL/gG) |
| Connection technology | |
| Plug | Yes |
| Connecting Conductors | |
| Connection type | Screw connection |
| Rigid conductor section | 0.2 mm² ... 2.5 mm² |
| Flexible conductor section | 0.2 mm² ... 2.5 mm² |
| AWG Wire Section | 24 ... 12 |
| Length to be de-insulated | 7 mm |
| Screw thread | M3 |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
| Operating voltage display | 2 x Green LEDs |
| Width | 35 mm |
| Height | 99 mm |
| Depth | 114.5 mm |
| Shell material | Polyamide |
| Technical Safety Data | |
| Stop Category | 0 |
| Technical safety data: EN ISO 13849 | |
| category | 4 (in combination with suitable evaluation device) |
| Performance Level (PL) | e (in combination with appropriate evaluation device) |
| Technical safety data: IEC 61508 - high demand | |
| Safety Integrity Level (SIL) | 3 (in combination with suitable evaluation device) |
| Technical safety data: IEC 61508 - low demand | |
| Safety Integrity Level (SIL) | 3 (in combination with suitable evaluation device) |
| Technical safety data: EN IEC 62061 | |
| Safety Integrity Level (SIL) | 3 (in combination with suitable evaluation device) |
| Environmental conditions | |
| Protection Index | IP20 |
| Minimum degree of protection of the installation site | IP54 |
| Ambient Temperature (Service) | -20 °C ... 55 °C (observe derating) |
| Ambient Temperature (Storage/Transport) | -40 °C ... 70 °C |
| Fixing height | ≤ 2000 m (via NN) |
| Max. permissible air humidity (storage/transport) | 75% (On average, occasionally 85%, non-condensing) |
| Max. permissible air humidity (service) | 75% (On average, occasionally 85%, non-condensing) |
| Crash | 35% |
| Vibration (service) | 10 Hz ... 150 Hz, amplitude 0.15 mm, 2g |
| Ce | |
| Marked | CE Compliance |
| Creepage lines and air gaps between circuits | |
| Standards/Specifications | EN 60947-1 |
| Type of mounting | Rail mounting |
| Installation instructions | Observe derating |
| Position for mounting | Vertical or horizontal |
| Connection type | Screw connection |