View larger
PSR-PC32-2NO-1NC-24-230UC-SP 2700582 PHOENIX CONTACT Coupling relay
PSR-PC32-2NO-1NC-24-230UC-SP
2700582
PHOENIX CONTACT
1 Pcs.
Automation > Device for monitoring of safety-related circuits
Safety
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Ensuring galvanic isolation and safe switching in industrial control circuits, the Phoenix Contact PSR-PC32-2NO-1NC-24-230UC-SP coupling relay provides dependable signal transmission. Coupling relays bridge the gap between low-voltage control systems and high-voltage field equipment, protecting sensitive electronics from electrical surges and feedback.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Note on application Note on application: Only for industrial use
- Utilization restriction CCCex note: Use in potentially explosive areas is not permitted in China.
- Product type: Coupling relay
- Product family: PSRmini
- Application: Safe switch off
- Relay type: Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3
- Data management status Article revision: 04
- Times Typical response time: < 100 ms (with U s when controlled via A1)
- Typical release time: < 200 ms (with U s when controlled via A1)
- Recovery time: < 500 ms
- Maximum power dissipation for nominal condition: 5.7 W (at U S = 42 V AC, I L ² = 72 A²)
- Nominal operating mode: 100% operating factor
- Rated surge voltage/insulation: Basic insulation 4 kV between all current paths and housing
- Supply Designation: A1/A2
- Rated control circuit supply voltage U S: 24 V AC/DC ... 230 V AC/DC -15 % ... +10 %
- Rated control supply current I S: 75 mA (24 V DC)
More info
▲| Note on application | |
| Note on application | Only for industrial use |
| Utilization restriction | |
| CCCex note | Use in potentially explosive areas is not permitted in China. |
| Product type | Coupling relay |
| Product family | PSRmini |
| Application | Safe switch off |
| High demand | |
| Low demand | |
| Ex | |
| Relay type | Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3 |
| Data management status | |
| Article revision | 04 |
| Times | |
| Typical response time | < 100 ms (with Uswhen controlled via A1) |
| Typical release time | < 200 ms (with Uswhen controlled via A1) |
| Recovery time | < 500 ms |
| Maximum power dissipation for nominal condition | 5.7 W (at US= 42 V AC, IL² = 72 A²) |
| Nominal operating mode | 100% operating factor |
| Air clearances and creepage distances between the power circuits | |
| Rated insulation voltage | 250 V AC |
| Rated surge voltage/insulation | Basic insulation 4 kV between all current paths and housing |
| Safe isolation, reinforced insulation 2.5 kV between (93/94) and (31/32, 24V/GND) | |
| Safe isolation, reinforced insulation 6 kV: between (A1/A2) and (13/14) and (31/32, 24V/GND) between (A1/A2) and (93/94) between (13/14) and (93/94) | |
| Supply | |
| Designation | A1/A2 |
| Rated control circuit supply voltage US | 24 V AC/DC ... 230 V AC/DC -15 % ... +10 % |
| Rated control supply current IS | 75 mA (24 V DC) |
| 34 mA (48 V DC) | |
| 97 mA (42 V AC) | |
| 28 mA (120 V AC) | |
| 16 mA (230 V AC) | |
| Power consumption at US | 1.8 W (with DC) |
| 2.1 W (with AC) | |
| Apparent power | typ. 4.1 VA |
| Inrush current | typ. 16 A (Δt s) |
| < 5 mA (at terminal blocks 24V/GND at UD) | |
| Filter time | 10 ms (24 V DC, A1 in the event of voltage dips at Us) |
| max. 1.5 ms (at A1-A2; test pulse width; at 24 V DC) | |
| 7.5 ms (at A1-A2; test pulse rate; at 24 V DC) | |
| Test pulse rate = 5 x Test pulse width | |
| Protective circuit | Surge protection; Varistor 275 V |
| Supply | |
| Designation | 24V/GND |
| Diagnostic supply voltage UD | 24 V DC -15 % / +10 % |
| Input current at UD | < 5 mA (at terminal blocks 24V/GND at UD) |
| Protective circuit | Surge protection; 33 V suppressor diode |
| Reverse polarity protection | |
| Relay: Enabling current path | |
| Output description | safety-related N/O contacts |
| Number of outputs | 2 (undelayed) |
| Contact switching type | 2 enabling current paths |
| Contact material | AgSnO2 |
| Switching voltage | min. 12 V AC/DC |
| max. 250 V AC/DC (13/14, observe the load curve) | |
| max. 60 V AC/DC (93/94, observe the load curve) | |
| Switching capacity | min. 60 mW |
| Inrush current | min. 3 mA |
| max. 6 A | |
| Switching capacity (360/h cycles) | 4 A (24 V (DC13)) |
| 5 A (230 V (AC 15)) | |
| Limiting continuous current | 6 A (observe derating) |
| Sq. Total current | 72 A2(observe derating) |
| Switching frequency | max. 1 Hz |
| Mechanical service life | 10x 106cycles |
| Output fuse | 6 A gL/gG |
| 4 A gL/gG (for low-demand applications) | |
| Relay: Confirmation current path | |
| Output description | Safety-related N/C contacts |
| Number of outputs | 1 (undelayed) |
| Contact switching type | 1 confirmation current path |
| Contact material | AgCuNi, + Au |
| Switching voltage | min. 3.3 V AC/DC |
| max. 26.4 V DC | |
| Switching capacity | min. 3.3 mW |
| Inrush current | min. 1 mA |
| max. 100 mA | |
| Limiting continuous current | 100 mA |
| Output fuse | 150 mA fast blow |
| Connection technology | |
| pluggable | yes |
| Conductor connection | |
| Connection method | Push-in connection |
| Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
| Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6) |
| Conductor cross section flexible, with ferrule without plastic sleeve | 0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6) |
| Conductor cross-section AWG | 24 ... 16 |
| Stripping length | 8 mm |
| Status display | 1 x LED (green), 1 x LED (yellow) |
| Operating voltage display | 1 x yellow LED |
| Width | 17.5 mm |
| Height | 117.4 mm |
| Depth | 114.5 mm |
| Color (Housing) | yellow (RAL 1018) |
| Housing material | Polyamide |
| Safety data | |
| Stop category | 0 |
| Safety data: EN 50156-2 | |
| Safety Integrity Level (SIL) | 3 (Reference IEC 61508) |
| Safety data: IEC 61508 - High demand | |
| Safety Integrity Level (SIL) | 3 ( |
| Safety data: IEC 61508 - Low demand | |
| Safety Integrity Level (SIL) | 3 ( |
| Ambient conditions | |
| Degree of protection | IP20 |
| Min. degree of protection of inst. location | IP54 |
| Ambient temperature (operation) | -40 °C ... 70 °C (observe derating) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Maximum altitude | ≤ 2000 m (Above sea level) |
| Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
| Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
| Shock | 15g |
| Vibration (operation) | 10 Hz ... 150 Hz, 2g |
| ATEX | |
| Identification | II 3G Ex ec nC IIC T4 Gc |
| Certificate | UL 22 ATEX 2912X |
| IECEx | |
| Identification | Ex ec nC IIC T4 Gc |
| Certificate | IECEx UL 22.0037X |
| UL, USA/Canada | |
| Identification | cULus |
| Certificate | E140324 |
| UL Ex, USA / Canada | |
| Identification | Class I, Zone 2, AEx nA nC IIC T4 / Ex nA nC IIC Gc T4 X |
| Class I, Div. 2, Groups A, B, C, D, T4 | |
| Certificate | E360692 |
| CE | |
| Identification | CE-compliant |
| Environmental simulation test | |
| Identification | G3 |
| Certificate | ISA-S71.04 |
| CCC / China-Ex | |
| Identification | Ex ec nC IIC T4 Gc |
| Certificate | 2022122304115695 |
| Air clearances and creepage distances between the power circuits | |
| Standards/regulations | EN 60664-1, EN 60079-7, EN 60079-15 |
| Mounting type | DIN rail mounting |
| Assembly note | See derating curve |
| Mounting position | vertical or horizontal |