View larger
PSR-M-EF7-XC-SAI4-PI 1337851 PHOENIX CONTACT Secure expansion module with 4 secure analog inputs, 0 V ... 10..
PSR-M-EF7-XC-SAI4-PI
1337851
PHOENIX CONTACT
1 Pcs.
Automation > Device for monitoring of safety-related circuits
Safety
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A Phoenix Contact secure expansion module processes analog input signals within safety-rated automation loops, monitoring variables like pressure or temperature in hazardous zones. It integrates directly with master control architectures to maintain functional safety compliance.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product type: Safety device
- Application: Analog IN
- Insulation characteristics Protection class: III
- Times Response time: see user manual
- Restart time: min. 5 s (Boot time)
- Maximum power dissipation for nominal condition: 2.76 W (with max. permissible load)
- Nominal operating mode: 100% operating factor
- Interfaces: DIN rail TBUS for connection to the master module, supplied as standard
- Rated surge voltage/insulation: Basic insulation 4 kV between all current paths and housing
- Supply Designation: A1/A2
- Rated control circuit supply voltage U S: 19.2 V DC ... 28.8 V DC
- Rated control circuit supply voltage U S: 24 V DC -20 % / +20 % (external fuse, typically 6 A)
- Rated control supply current I S: typ. 82 mA (without sensor supply)
- Power consumption at U S: typ. 1.96 W (without sensor supply)
- Inrush current: max. 14 A (Δt = 1 ms at U s )
- Filter time: typ. 5 ms (in the event of voltage dips at U s )
More info
▲| Product type | Safety device |
| Application | Analog IN |
| Insulation characteristics | |
| Protection class | III |
| Times | |
| Response time | see user manual |
| Restart time | min. 5 s (Boot time) |
| max. 10 s (Boot time) | |
| Maximum power dissipation for nominal condition | 2.76 W (with max. permissible load) |
| Nominal operating mode | 100% operating factor |
| Interfaces | DIN rail TBUS for connection to the master module, supplied as standard |
| Air clearances and creepage distances | |
| Rated insulation voltage | 250 V AC |
| Rated surge voltage/insulation | Basic insulation 4 kV between all current paths and housing |
| Electrical isolation, 0.5 kV functional insulation between logic and analog inputs and between the analog inputs | |
| Supply | |
| Designation | A1/A2 |
| Rated control circuit supply voltage US | 19.2 V DC ... 28.8 V DC |
| Rated control circuit supply voltage US | 24 V DC -20 % / +20 % (external fuse, typically 6 A) |
| Rated control supply current IS | typ. 82 mA (without sensor supply) |
| typ. 212 mA (with sensor supply) | |
| Power consumption at US | typ. 1.96 W (without sensor supply) |
| typ. 5.08 W (with sensor supply) | |
| Inrush current | max. 14 A (Δt = 1 ms at Us) |
| Filter time | typ. 5 ms (in the event of voltage dips at Us) |
| Protective circuit | Serial protection against polarity reversal |
| General | |
| Protective circuit | Overload protection of the current inputs; Suppressor diode |
| Analog | |
| Input name | IN S1, IN S2, IN S3, IN S4 |
| Description of the input | Safety-oriented analog inputs, configurable as current or voltage inputs, galvanically isolated |
| Number of inputs | 4 |
| Connection technology | 2-conductor, 3-conductor or 4-conductor (2-conductor sensor signal + 2-conductor sensor supply) |
| Note regarding the connection technology | shielded |
| Scanning rate | 2.5/5/10/16.6/20/50/60/100/200/400/800/1000/2000/4000 Hz |
| Current input signal | 0 mA ... 25 mA (Measuring range) |
| 0 mA ... 20 mA (Configurable measuring range with diagnostics range 20.1 mA ... 23 mA) | |
| 4 mA ... 20 mA (Configurable measuring range with diagnostics range 20.1 mA ... 23 mA (upper limit), 2.5 mA ... 3.8 mA (lower limit)) | |
| Voltage input signal | 0 V ... 12 V (Measuring range) |
| 0 V ... 10 V (Configurable measuring range with diagnostics range 10.05 V ... 11.5 V (upper limit), 0.1 V (lower limit)) | |
| Max. permissible current | max. 35 mA (as current input) |
| Permissible voltage | max. 24 V (as current input) |
| max. 14 V (as voltage input) | |
| Input resistance current input | 290 Ω ±25 % (incl. internal protective circuit) |
| Input resistance of voltage input | 185 kΩ ±25 % |
| A/D converter resolution | 16 bit |
| Resolution (current) | 381 nA |
| Resolution (voltage) | 152 µV |
| Precision | typ. ± 2 % (as current input, relative to the measuring range final value) |
| max. ± 2.5 % (as current input) | |
| typ. ± 1 % (as voltage input, relative to the measuring range final value) | |
| max. ± 1.5 % (as voltage input) | |
| Temperature coefficients | typ. ± 0.07 %/K |
| max. ± 0.07 %/K | |
| Limit frequency (3 dB) | 160 Hz (RC low pass, 1st order, as current input) |
| 4 Hz (RC low pass, as voltage input) | |
| Frequency | 20 Hz (max. recommended sensor signal frequency, as current input) |
| 2 Hz (max. recommended sensor signal frequency, as voltage input) | |
| Permissible cable length | max. 100 m (per input) |
| Protective circuit | Overload protection of the current inputs |
| Overload protection of the voltage inputs | |
| Sensor supply: OUT S1/0V ...OUT S4/0V | |
| Description | Sensor supply voltage per analog input |
| Supply voltage | 24 V DC ±3 % |
| Current | max. 30 mA (Sensor current recording per channel) |
| Short-circuit-proof | yes |
| Protective circuit | Overload protection Overload detection at 38 mA |
| Connection technology | |
| pluggable | yes |
| Conductor connection | |
| Connection method | Push-in connection |
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross-section AWG | 24 ... 16 |
| Stripping length | 10 mm |
| Status display | 4x LED (yellow, red) |
| Operating voltage display | 1 x green LED |
| Width | 22.61 mm |
| Height | 107.74 mm |
| Depth | 113.6 mm |
| Housing material | Polyamide PA non-reinforced |
| Safety data | |
| Stop category | 0 |
| Safety data: EN ISO 13849 | |
| Performance level (PL) | e (2-channel wiring) |
| d (1-channel wiring) | |
| Safety data: IEC 61508 - High-demand for 2-channel wiring | |
| Safety Integrity Level (SIL) | 3 |
| Safety data: IEC 61508 - High-demand for 1-channel wiring | |
| Safety Integrity Level (SIL) | 2 |
| Safety data | |
| Safety Integrity Level (SIL) | 2 |
| Safety data: EN IEC 62061 | |
| Safety Integrity Level (SIL) | 3 (2-channel wiring) |
| 2 (1-channel wiring) | |
| Ambient conditions | |
| Degree of protection | IP20 |
| Min. degree of protection of inst. location | IP54 |
| Ambient temperature (operation) | -10 °C ... 70 °C (observe derating) |
| Ambient temperature (storage/transport) | -20 °C ... 85 °C |
| Maximum altitude | ≤ 2000 m (Above sea level) |
| Max. permissible humidity (storage/transport) | 95 % (non-condensing) |
| Max. permissible relative humidity (operation) | 95 % (non-condensing) |
| Shock | 10g for Δt = 16 ms (continuous shock, 1000 shocks in each space direction) |
| Vibration (operation) | 10 Hz ... 150 Hz, 2g |
| CE | |
| Identification | CE-compliant |
| Environmental simulation test | |
| Identification | ISA-S71.04 |
| Note | G3 |
| Mounting type | DIN rail mounting |
| Assembly instructions | Observe derating |
| Mounting position | vertical or horizontal |
| Connection method | Push-in connection |