View larger
PSR-M-B2-XC-SDI8-SDO4-DO4-PI 1337849 PHOENIX CONTACT Configurable safety module (basic module), 8 safe input..
PSR-M-B2-XC-SDI8-SDO4-DO4-PI
1337849
PHOENIX CONTACT
1 Pcs.
Automation > Device for monitoring of safety-related circuits
Safety
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A Phoenix Contact PSR-M-B2-XC-SDI8-SDO4-DO4-PI configurable safety module (basic module), 8 safe input.. provides programmable logic control for sophisticated machine safety architectures. Engineers use this modular controller to process multiple safety channels and customize protective responses for demanding industrial environments.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product type: Safety device
- Application: Emergency stop
- Times Response time: see user manual
- Restart time: min. 5 s (Boot time)
- Maximum power dissipation for nominal condition: 7.48 W (with max. permissible load)
- Nominal operating mode: 100% operating factor
- Interfaces: DIN rail TBUS for connection to the master module, not supplied as standard
- Rated surge voltage/insulation: See section “Insulation coordination”
- Supply Designation: A1/A2
- Rated control circuit supply voltage U S: 19.2 V DC ... 28.8 V DC
- Rated control circuit supply voltage U S: 24 V DC -20 % / +20 % (external fuse, typically 4 A)
- Rated control supply current I S: typ. 55 mA (Outputs inactive)
- Power consumption at U S: typ. 1.32 W (Outputs inactive)
- Inrush current: 9.16 A (Δt = 0.5 ms at U s )
- Filter time: typ. 5 ms (in the event of voltage dips at U s )
- Protective circuit: Serial protection against polarity reversal
More info
▲| Product type | Safety device |
| Application | Emergency stop |
| Light grid | |
| Safety door | |
| Safe shutdown | |
| Times | |
| Response time | see user manual |
| Restart time | min. 5 s (Boot time) |
| max. 10 s (Boot time) | |
| Maximum power dissipation for nominal condition | 7.48 W (with max. permissible load) |
| Nominal operating mode | 100% operating factor |
| Interfaces | DIN rail TBUS for connection to the master module, not supplied as standard |
| Air clearances and creepage distances between the power circuits | |
| Rated insulation voltage | 250 V AC |
| Rated surge voltage/insulation | See section “Insulation coordination” |
| Supply | |
| Designation | A1/A2 |
| Rated control circuit supply voltage US | 19.2 V DC ... 28.8 V DC |
| Rated control circuit supply voltage US | 24 V DC -20 % / +20 % (external fuse, typically 4 A) |
| Rated control supply current IS | typ. 55 mA (Outputs inactive) |
| Power consumption at US | typ. 1.32 W (Outputs inactive) |
| Inrush current | 9.16 A (Δt = 0.5 ms at Us) |
| Filter time | typ. 5 ms (in the event of voltage dips at Us) |
| Protective circuit | Serial protection against polarity reversal |
| Digital: IN1, IN2, IN3, IN4, IN5, IN6, IN7, IN8 | |
| Description of the input | Safety-related digital inputs |
| NPN | |
| Number of inputs | 8 |
| Input voltage range "0" signal | 0 V DC ... 5 V DC (for safe Off) |
| Input voltage range "1" signal | 11 V DC ... 28.8 V DC |
| Input current range "0" signal | < 0.2 mA |
| Inrush current | max. 524 mA (Δt = 6 µs at Us) |
| Filter time | min. 3 ms (adjustable) |
| max. 250 ms (adjustable) | |
| Test pulse rate ≥ 2x set filter time, min. Test pulse rate = 10 ms | |
| max. 3 ms (Test pulse rate ≥ 10x configured filter time for low test pulse) | |
| max. 250 ms (Test pulse rate ≥ 10x configured filter time for high test pulse) | |
| Cable length | max. 100 m |
| Max. permissible overall conductor resistance | max. 1.2 kΩ (Input and reset circuit at US) |
| Current consumption | typ. 3.7 mA (typically with US) |
| max. 4.6 mA (at a control voltage of 28.8 V DC) | |
| Digital: Reset inputs (FBK) | |
| Description of the input | configurable (as signal output or reset input) |
| NPN, digital | |
| Number of inputs | 4 (Non-safe inputs) |
| Input voltage range "0" signal | 0 V DC ... 5 V DC (for safe Off) |
| Input voltage range "1" signal | 11 V DC ... 28.8 V DC |
| Input current range "0" signal | < 0.2 mA |
| Inrush current | max. 906.53 mA (Δt = 10 µs at Us) |
| Filter time | 250 ms (constant) |
| < 250 ms (Test pulse duration) | |
| > 1 s (Test pulse rate) | |
| Cable length | max. 100 m |
| Max. permissible overall conductor resistance | 1.2 kΩ (Input and reset circuit at US) |
| Current consumption | typ. 5.7 mA (typically with US) |
| max. 7 mA (at a control voltage of 28.8 V DC) | |
| Digital: O1, O2, O3, O4 | |
| Output description | Safety-related digital outputs |
| PNP, OSSD, digital | |
| IEC 61131-2 type 0.25 (observe limiting continuous current) | |
| Number of outputs | 4 |
| Short-circuit protection | no |
| Output voltage | < 0.3 V (Low state) |
| Leakage current | < 500 µA (Low state) |
| Cable length | max. 100 m |
| Max. capacitive load | max. 820 nF |
| Max. inductive load | See "Protective circuit" |
| Limiting continuous current | 400 mA (per channel) |
| 1.6 A (Total current of all safe digital outputs) | |
| Inrush current | max. 600 mA (Δt = 25 ms at Us) |
| Nominal output voltage | 24 V DC (Supply via A1) |
| Nominal output voltage range | 18.6 V DC ... 28.2 V DC (US- 0,7 V) |
| Switching frequency | max. 1/4 x tCycle[Hz] |
| Test pulses | < 235 µs (Test pulse width of low test pulses) |
| ≥ 650 ms (Test pulse rate for low test pulse) | |
| < 150 µs (Test pulse width, high test pulse) | |
| ≥ 1.5 s (Test pulse rate, high test pulse) | |
| Discharging circuit | Yes, internal |
| Signal: MO1, MO2, MO3, MO4 | |
| Output description | PNP, digital, IEC 61131-2 type 0.1 |
| non-safety-related, configurable (as signal output or reset input) | |
| Number of outputs | 4 |
| Output voltage when switched off | max. 0.1 V |
| Voltage | 24 V DC (via A1) |
| Maximum inrush current | 1.1 A (Δt = 3 s at Us) |
| Limiting continuous current | 100 mA (per channel) |
| 400 mA (Total current of all digital signal outputs) | |
| Leakage current | max. 4.5 mA (Low state) |
| Switching frequency | max. 1/4 x tCycle[Hz] |
| Short-circuit protection | Yes (self-limitation at 1.1 A) |
| Cable length | max. 100 m |
| Clock: T1, T2, T3, T4 | |
| Output description | PNP, digital, IEC 61131-2 type 0.1 |
| Number of outputs | 4 |
| Voltage | 24 V DC (via A1) |
| Maximum inrush current | 1.1 A (Δt = 3 s at Us) |
| Limiting continuous current | 100 mA (per channel) |
| 400 mA (Total current of all outputs) | |
| Test pulses | ≤ 200 µs (Test pulse duration) |
| Test pulse rate = 8 x tCycle[ms] | |
| Short-circuit protection | Yes (self-limitation at 1.1 A) |
| Cable length | max. 100 m |
| Max. capacitive load | max. 470 nF |
| Max. inductive load | max. 2.4 mH |
| Discharging circuit | Yes, internal |
| Connection technology | |
| pluggable | yes |
| Conductor connection | |
| Connection method | Push-in connection |
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross-section AWG | 24 ... 16 |
| Stripping length | 10 mm |
| Data: Service interface | |
| Connection method | USB 2.0 Hi-Speed |
| Number of connections | 1 |
| Data: Local bus | |
| Note | via the PSR-TBUS DIN rail connector |
| Status display | 1 x LED (green), 1 x LED (orange), 1 x LED (blue) |
| 4 x LED (green, yellow, red) | |
| 12 x LED (yellow) | |
| Operating voltage display | 1 x green LED |
| Error indication | 2 x LED (red) |
| Width | 22.61 mm |
| Height | 107.74 mm |
| Depth | 113.6 mm |
| Housing material | Polyamide PA non-reinforced |
| Safety data: EN ISO 13849 | |
| Performance level (PL) | e (2-channel wiring) |
| d (1-channel wiring) | |
| Safety data: IEC 61508 - High-demand for 2-channel wiring | |
| Safety Integrity Level (SIL) | 3 |
| Safety data: IEC 61508 - High-demand for 1-channel wiring | |
| Safety Integrity Level (SIL) | 2 |
| Safety data | |
| Safety Integrity Level (SIL) | 2 |
| Safety data: EN IEC 62061 | |
| Safety Integrity Level (SIL) | 3 (2-channel wiring) |
| 2 (1-channel wiring) | |
| Ambient conditions | |
| Degree of protection | IP20 |
| Min. degree of protection of inst. location | IP54 |
| Ambient temperature (operation) | -10 °C ... 70 °C (observe derating) |
| Ambient temperature (storage/transport) | -20 °C ... 85 °C |
| Maximum altitude | ≤ 2000 m (Above sea level) |
| Max. permissible humidity (storage/transport) | 95 % (non-condensing) |
| Max. permissible relative humidity (operation) | 95 % (non-condensing) |
| Shock | 10g for Δt = 16 ms (continuous shock, 1000 shocks in each space direction) |
| Vibration (operation) | 10 Hz ... 150 Hz, 2g |
| CE | |
| Identification | CE-compliant |
| Environmental simulation test | |
| Identification | ISA-S71.04 |
| Note | G3 |
| DNV | |
| Identification | C, EMC2 |
| Certificate | XXX |
| Mounting type | DIN rail mounting |
| Assembly instructions | Observe derating |
| Mounting position | vertical or horizontal |
| Connection method | Push-in connection |