Filter terminal block Terminal block for test pulse filtering of safe semiconductor outputs with adjustable filter values (20 μF/86 μF) as well as EMC filtering of 24 V signals up to a current intensity of 2 A.

Automation > Accessories/spare parts for controls
Safety

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

A Phoenix Contact filter terminal block (PSR-FTB/20/86) manages signal conditioning and electrical noise suppression inside control cabinets. Such terminal blocks help maintain signal integrity by filtering out unwanted electromagnetic interference across sensitive automation networks.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Accessory (EF013236): Yes
  • Spare part (EF013237): No

More info

▲

Key Commercial Data

Orderkey2904477
Packing unit1 pc
Catalog pagePage 295 (C-6-2017)
GTIN4046356831512
Weight per Piece (excluding packing)43.600 g
Custom tariff number85369010
Country of originDE (Germany)

Note

Utilization restrictionEMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width6.2 mm
Height94 mm
Depth80 mm

Ambient conditions

Ambient temperature (operation)-25 °C ... 55 °C
Ambient temperature (storage/transport)-25 °C ... 70 °C
Degree of protectionIP20

Input data

Nominal input voltage UN24 V DC ±20 % (Control voltage USTright/left)
Typical input current at UNmax. 20 mA
Protective circuitSurge protection

Output data

Nominal output voltage24 V DC ±20 % (Control voltage USTright/left)
Nominal output voltage range19.2 V DC ... 28.8 V DC (Control voltage USTright/left)
Limiting continuous currentmax. 2 A (in total for OUT1 + OUT2)

Connection data, control circuit

Connection nameControl circuits
Connection methodPush-in connection
Stripping length8 mm
Conductor cross section solid0.14 mm² ... 2.5 mm²
Conductor cross section flexible0.14 mm² ... 2.5 mm²
Conductor cross section AWG26 ... 14

Connection data load circuit

Connection nameLoad circuit
Connection methodPush-in connection
Stripping length8 mm
Conductor cross section solid0.14 mm² ... 2.5 mm²
Conductor cross section flexible0.14 mm² ... 2.5 mm²
Conductor cross section AWG26 ... 14

General

Mounting positionVertical (horizontal DIN rail)
Assembly instructionsIn rows with zero spacing
Operating mode100% operating factor

Standards and Regulations

DesignationAir clearances and creepage distances between the power circuits
Standards/regulationsEN 61131
Rated insulation voltage50 V
Rated surge voltage1.5 kV
InsulationBasic insulation
Degree of pollution2
Overvoltage categoryII

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications