View larger
PSR-FTB/1.5/11.5 2904476 PHOENIX CONTACT Filter terminal block
PSR-FTB/1.5/11.5
2904476
PHOENIX CONTACT
1 Pcs.
Automation > Accessories/spare parts for controls
Safety
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A filter terminal block is a specialized electrical connection component designed to manage signal noise and provide organized wire distribution in control panels. These terminal assemblies are commonly integrated into industrial power and signal circuits to maintain signal integrity and safe grounding. Exact pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Accessory (EF013236): Yes
- Spare part (EF013237): No
More info
▲Key Commercial Data
| Orderkey | 2904476 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 295 (C-6-2017) |
| GTIN | 4046356831505 |
| Weight per Piece (excluding packing) | 28.600 g |
| Custom tariff number | 85369010 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -25 °C ... 55 °C |
|---|---|
| Ambient temperature (storage/transport) | -25 °C ... 70 °C |
| Degree of protection | IP20 |
Input data
| Nominal input voltage UN | 24 V DC ±20 % (Control voltage USTright/left) |
|---|---|
| Typical input current at UN | max. 15 mA |
| Protective circuit | Surge protection |
Output data
| Nominal output voltage | 24 V DC ±20 % (Control voltage USTright/left) |
|---|---|
| Nominal output voltage range | 19.2 V DC ... 28.8 V DC (Control voltage USTright/left) |
| Limiting continuous current | max. 2 A (in total for OUT1 + OUT2) |
Connection data, control circuit
| Connection name | Control circuits |
|---|---|
| Connection method | Push-in connection |
| Stripping length | 8 mm |
| Conductor cross section solid | 0.14 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
| Conductor cross section AWG | 26 ... 14 |
Connection data load circuit
| Connection name | Load circuit |
|---|---|
| Connection method | Push-in connection |
| Stripping length | 8 mm |
| Conductor cross section solid | 0.14 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
| Conductor cross section AWG | 26 ... 14 |
General
| Mounting position | Vertical (horizontal DIN rail) |
|---|---|
| Assembly instructions | In rows with zero spacing |
| Operating mode | 100% operating factor |
Standards and Regulations
| Designation | Air clearances and creepage distances between the power circuits |
|---|---|
| Standards/regulations | EN 61131 |
| Rated insulation voltage | 50 V |
| Rated surge voltage | 1.5 kV |
| Insulation | Basic insulation |
| Degree of pollution | 2 |
| Overvoltage category | II |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |