A repeater like the Phoenix Contact PSM-ME-REP LON485-P extends the physical range and segment capacity of industrial network architectures by regenerating degraded communication signals. These units prevent packet loss over long cable runs, maintain signal integrity, and isolate node faults in expansive automation layouts. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Number of HW-interfaces industrial Ethernet (EF003020): 0
- Number of interfaces PROFINET (EF006932): 0
- Number of HW-interfaces RS-232 (EF003021): 0
- Number of HW-interfaces RS-422 (EF003022): 0
- Number of HW-interfaces RS-485 (EF003023): 0
- Number of HW-interfaces serial TTY (EF003024): 0
- Number of HW-interfaces USB (EF003025): 0
- Number of HW-interfaces parallel (EF003026): 0
- Number of HW-interfaces wireless (EF006933): 0
- Number of HW-interfaces other (EF003027): 0
- With optical interface (EF003028): No
- Radio standard Bluetooth (EF007178): No
- Radio standard WLAN 802.11 (EF007179): No
- Radio standard GPRS (EF008523): No
- Radio standard GSM (EF008524): No
- Radio standard UMTS (EF008525): No
More info
▲Key Commercial Data
| Orderkey | 2708041 |
|---|---|
| Packing unit | 1 pc |
| GTIN | 4017918907570 |
| Weight per Piece (excluding packing) | 188.800 g |
| Custom tariff number | 85176200 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 70 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
| Altitude | 5000 m (For restrictions see manufacturer's declaration) |
| Degree of protection | IP20 |
| Noise immunity | EN 61000-6-2:2005 |
General
| Transmission channels | 2 (1/1), RxD, TxD, full duplex |
|---|---|
| Bit distortion | < 1.5 % (applies to device: Distortions caused by system-specific cables are not accounted for) |
| Electrical isolation | VCC // RS-485 (A) // RS-485 (B) |
| Test voltage data interfaces | 2 kV AC |
| Test voltage data interface/power supply | 2 kV AC |
| 2 kV | |
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
| Noise emission | EN 50 081-1 |
| Net weight | 188.8 g |
| Housing material | PA |
| Color | green |
| MTTF | 1808 Years (SN 29500 standard, temperature 25 °C, operating cycle 21 % (5 days a week, 8 hours a day)) |
| 796 Years (SN 29500 standard, temperature 40 °C, operating cycle 34.25 % (5 days a week, 12 hours a day)) | |
| 334 Years (SN 29500 standard, temperature 40 °C, operating cycle 100 % (7 days a week, 24 hours a day)) | |
| Degree of pollution | 2 |
| Conformance | CE-compliant |
| ATEX | II 3 G Ex nA IIC T4 Gc (Please follow the special installation instructions in the documentation!) |
| IECEx | Ex nA IIC T4 Gc |
| UL, USA/Canada | 508 recognized |
| Class I, Div. 2, Groups A, B, C, D | |
| Class I, Zone 2, AEx nA IIC T4 | |
| Class I, Zone 2, Ex nA IIC T4 Gc X |
Power supply
| Nominal supply voltage | 24 V AC/DC ±20 % |
|---|---|
| Max. current consumption | 100 mA |
| Typical current consumption | 90 mA (24 V DC) |
Serial interface
| Interface 1 | RS-485 interface in acc. with EIA/TIA-485, DIN 66259-4 |
|---|---|
| Operating mode | Semi-duplex |
| Connection method | Pluggable screw connection |
| File format/coding | Manchester, slip-tolerant |
| Data direction switching | Automatic control |
| Transmission medium | 2-wire twisted pair, shielded |
| Transmission length | ≤ 1200 m (depends on transmission speed, bus system and cable type) |
| Termination resistor | 120 Ω |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 14 |
| Serial transmission speed | 39.1/ 78.1/ 500/ 625/ 1000/ 1250/ 2000 kbps |
| Interface 2 | RS-485 interface in acc. with EIA/TIA-485, DIN 66259-4 |
| Operating mode | Semi-duplex |
| Connection method | Pluggable screw connection |
| File format/coding | Manchester, slip-tolerant |
| Data direction switching | Automatic control |
| Transmission medium | 2-wire twisted pair, shielded |
| Transmission length | ≤ 1200 m (depends on transmission speed, bus system and cable type) |
| Termination resistor | 120 Ω |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 14 |
| Serial transmission speed | 39.1/ 78.1/ 500/ 625/ 1000/ 1250/ 2000 kbps |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Noise emission | EN 50 081-1 |
| Noise immunity | EN 61000-6-2:2005 |
| Connection in acc. with standard | CUL |
| Standards/regulations | EN 61000-4-2 |
| Contact discharge | ± 6 kV (Test Level 3) |
| Standards/regulations | EN 61000-4-3 |
| Frequency range | 80 MHz ... 3 GHz (Test Level 3) |
| Standards/regulations | EN 61000-4-4 |
| Comments | Criterion B |
| Standards/regulations | EN 61000-4-5 |
| Signal | ± 2 kV |
| Standards/regulations | EN 55011 |
| EN 61000-4-6 | |
| Frequency range | 0.15 MHz ... 80 MHz |
| Conformance | CE-compliant |
| ATEX | II 3 G Ex nA IIC T4 Gc |
| IECEx | Ex nA IIC T4 Gc |
| UL, USA/Canada | 508 recognized |
| Class I, Div. 2, Groups A, B, C, D | |
| Class I, Zone 2, AEx nA IIC T4 | |
| Class I, Zone 2, Ex nA IIC T4 Gc X | |
| Noxious gas test | ISA-S71.04-1985 G3 Harsh Group A |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |