View larger
PT PE/S+1X2-24-ST 2819008 PHOENIX CONTACT Surge protection plug
PT PE/S+1X2-24-ST
2819008
PHOENIX CONTACT
1 Pcs.
Automation > Combined arrester for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact offers the PT PE/S+1X2-24-ST 2819008 PHOENIX CONTACT Surge protection plug for maintaining electrical safety in industrial automation systems. Protective plugs are routinely utilized in modular terminal configurations to guard sensitive measurement and control devices against harmful voltage transients. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2819008
- Packing unit: 10 pc
- Catalog page: Page 99 (C-4-2017)
- GTIN: 4017918819323
- Weight per Piece (excluding packing): 25.830 g
- Custom tariff number: 85363010
- Country of origin: DE (Germany)
- Height: 44.8 mm
- Width: 17.5 mm
- Depth: 51.7 mm
- Horizontal pitch: 1 Div.
- Complete module height: 90 mm
- Complete module width: 17.7 mm
- Complete module depth: 65.5 mm
- Ambient temperature (operation): -40 °C ... 85 °C
- Ambient temperature (storage/transport): -40 °C ... 85 °C
More info
▲Key Commercial Data
| Orderkey | 2819008 |
|---|---|
| Packing unit | 10 pc |
| Catalog page | Page 99 (C-4-2017) |
| GTIN | 4017918819323 |
| Weight per Piece (excluding packing) | 25.830 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Dimensions
| Height | 44.8 mm |
|---|---|
| Width | 17.5 mm |
| Depth | 51.7 mm |
| Horizontal pitch | 1 Div. |
| Complete module height | 90 mm |
| Complete module width | 17.7 mm |
| Complete module depth | 65.5 mm |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 85 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
General
| Housing material | PA 6.6 |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | jet black RAL 9005 |
| Mounting type | on base element |
| Type | Male |
| Current supply arrester can be tested with CHECKMASTER starting with software version: | From SW rev. 1.00 |
| Direction of action | L-N-PE & Signal Line-Signal Line-Earth Ground |
Protective circuit, power supply
| EN type | T3 |
|---|---|
| Arrester rated voltage UC | 34 V AC |
| 44 V DC | |
| Nominal frequency fN | 50 Hz (60 Hz) |
| Rated load current IL | 6 A (30 °C) |
| Operating effective current ICat UC | ≤ 1.5 mA |
| Residual current IPE | ≤ 5 µA |
| Nominal discharge current In(8/20) µs | 700 A |
| Max. discharge current Imax(8/20) µs | 2 kA |
| Combination wave UOC | 2 kV |
| Voltage protection level Up(L-N) | ≤ 0.18 kV |
| Voltage protection level Up(L-PE) | ≤ 0.55 kV |
| Response time (L-N) | ≤ 25 ns |
| Response time (L-PE) | ≤ 100 ns |
| Surge protection fault message | optical |
Connection (protective circuit, power supply)
| Connection method | Screw connection (in connection with the base element) |
|---|---|
| Connection method IN | PLUGTRAB plug-in system |
| Connection method OUT | PLUGTRAB plug-in system |
| Screw thread | M3 |
| Stripping length | 8 mm |
Protective circuit, information technology
| Nominal voltage UN | 24 V AC |
|---|---|
| Arrester rated voltage UC | 40 V DC |
| 28 V AC | |
| Rated current | 450 mA (45°C) |
| Operating effective current ICat UC | ≤ 5 µA |
| Residual current IPE | ≤ 2 µA |
| Nominal discharge current In(8/20) µs (line-line) | 10 kA |
| Nominal discharge current In(8/20) µs (line-earth) | 10 kA |
| Max. discharge current Imax(8/20) µs maximum (line-line) | 10 kA |
| Max. discharge current Imax(8/20) µs maximum (line-earth) | 20 kA (in total) |
| Voltage protection level Up(line-line) | ≤ 80 V (C2 - 10 kV / 5 kA) |
| Voltage protection level Up(line-earth) | ≤ 450 V (C2 - 10 kV / 5 kA) |
| Response time tA(line-line) | ≤ 1 ns |
| Response time tA(line-earth) | ≤ 100 ns |
| Input attenuation aE, sym. | typ. 0.5 dB (≤ 1.5 MHz / 50 Ω) |
| typ. 0.2 dB (≤ 500 kHz / 150 Ω) | |
| typ. 0.1 dB (≤ 100 kHz / 600 Ω) | |
| Cut-off frequency fg (3 dB), sym. in 50 Ohm system | typ. 8 MHz |
| Cut-off frequency fg (3 dB), sym. in 150 Ohm system | typ. 3 MHz |
| Cut-off frequency fg (3 dB), sym. in 600 Ohm system | typ. 800 kHz |
| Capacity (line-line) | typ. 1.1 nF |
| Capacity (line-earth) | typ. 4 pF |
| Resistance in series | 2.2 Ω ±10 % |
| Surge protection fault message | Optical, remote indicator contact |
| Output voltage limitation at 1 kV/µs (wire-wire) | ≤ 55 V |
| Output voltage limitation at 1 kV/µs (wire-earth) | ≤ 25 V |
| Residual voltage at In(line-line) | ≤ 55 V |
| Residual voltage with Ian (10/1000) µs (line-line) | ≤ 65 V |
| Impulse durability (line-line) | C2 - 10 kV/5 kA |
| C3 - 23 A | |
| Impulse durability (line-earth) | C2 - 10 kV/5 kA |
| D1 - 2.5 kA |
Power supply, general
| Connection method | Screw connection (in connection with the base element) |
|---|---|
| Connection method IN | PLUGTRAB plug-in system |
| Connection method OUT | PLUGTRAB plug-in system |
| Screw thread | M3 |
| Stripping length | 8 mm |