View larger
PT 4-12DC-ST 2839237 PHOENIX CONTACT Surge protection plug
PT 4-12DC-ST
2839237
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Providing dependable transient voltage limitation, the Phoenix Contact PT 4-12DC-ST surge protection plug safeguards low-voltage control lines within industrial automation systems. These pluggable modules allow fast replacement inside crowded control panels, maintaining continuous protection for sensitive electronics. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Nominal voltage DC (EF008799): 12 V
More info
▲Key Commercial Data
| Orderkey | 2839237 |
|---|---|
| Packing unit | 10 pc |
| Catalog page | Page 116 (C-4-2017) |
| GTIN | 4017918182779 |
| Weight per Piece (excluding packing) | 21.140 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Dimensions
| Height | 45 mm |
|---|---|
| Width | 17.7 mm |
| Depth | 52 mm |
| Horizontal pitch | 1 Div. |
| Complete module height | 90 mm |
| Complete module width | 17.7 mm |
| Complete module depth | 65.5 mm |
General
| Housing material | PA 6.6 |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | black |
| Standards for cearances and creepage distances | VDE 0110-1 |
| IEC 60664-1 | |
| Mounting type | on base element |
| Type | Male |
| Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
| Arrester can be tested with CHECKMASTER from software version: | From SW rev. 1.00 |
Protective circuit
| IEC test classification | C1 |
|---|---|
| C2 | |
| C3 | |
| D1 | |
| VDE requirement class | C1 |
| C2 | |
| C3 | |
| D1 | |
| Nominal voltage UN | 12 V DC |
| Maximum continuous voltage UC | 12.8 V DC |
| 9 V AC | |
| Rated current | 2 A (80 °C) |
| Operating effective current ICat UC | ≤ 1 mA |
| Residual current IPE | ≤ 4 µA (Directly grounded) |
| ≤ 1 µA (with PT 4+F-BE) | |
| Nominal discharge current In(8/20) µs (line-line) | 690 A |
| Nominal discharge current In(8/20) µs (line-earth) | 10 kA |
| Pulse discharge current Iimp(10/350) µs | 2.5 kA (per path) |
| Total discharge current Itotal(8/20) µs | 20 kA |
| Max. discharge current Imax(8/20) µs maximum (line-line) | 690 A |
| Max. discharge current Imax(8/20) µs maximum (line-earth) | 10 kA |
| Nominal pulse current Ian (10/1000) µs (line-line) | 128 A |
| Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 20 V |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 450 V |
| ≤ 1 kV (with PT 4+F-BE) | |
| Output voltage limitation at 1 kV/µs (line-line) static | ≤ 18 V |
| Residual voltage at In(line-line) | ≤ 50 V |
| Residual voltage with Ian (10/1000) µs (line-line) | ≤ 25 V |
| Voltage protection level Up(line-line) | ≤ 40 V (C1 - 1 kV/500 A) |
| Voltage protection level Up(line-earth) | ≤ 450 V |
| ≤ 1 kV (with PT 4+F-BE) | |
| Response time tA(line-line) | ≤ 1 ns |
| Response time tA (line-signalground) | ≤ 1 ns |
| Response time tA(line-earth) | ≤ 100 ns |
| Input attenuation aE, sym. | 0.1 dB (≤ 600 kHz) |
| Cut-off frequency fg (3 dB), sym. in 50 Ohm system | typ. 3 MHz |
| Surge protection fault message | none |
| Max. required back-up fuse | 2 A (T) |
| Impulse durability (line-line) | C1 - 1 kV/500 A |
| C3 - 100 A | |
| Impulse durability (line-earth) | C2 - 10 kV/5 kA |
| D1 - 2.5 kA |
Connection data
| Connection method | Screw connection (in connection with the base element) |
|---|---|
| Screw thread | M3 |
| Tightening torque | 0.5 Nm |
| Stripping length | 8 mm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
Standards and Regulations
| Standards/regulations | IEC 61643-21 |
|---|---|
| DIN EN 61643-21 | |
| UL 497B | |
| Standards/specifications | IEC 61643-21 2000 |