The Phoenix Contact PT 5-HF-12 DC-ST is a specialized surge protection plug designed to defend high-frequency signal interfaces against transient overvoltages. High-frequency protective plugs are commonly deployed in telecommunications and data processing lines to prevent signal distortion or hardware failure. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Nominal voltage AC (EF008798): 12 V
More info
▲Key Commercial Data
| Orderkey | 2838775 |
|---|---|
| Packing unit | 10 pc |
| Catalog page | Page 147 (C-4-2017) |
| GTIN | 4017918480646 |
| Weight per Piece (excluding packing) | 25.600 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Dimensions
| Height | 45 mm |
|---|---|
| Width | 17.7 mm |
| Depth | 52 mm |
| Horizontal pitch | 1 Div. |
| Complete module height | 90 mm |
| Complete module width | 17.7 mm |
| Complete module depth | 65.5 mm |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 85 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Degree of protection | IP20 |
General
| Housing material | PA 6.6 |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | jet black RAL 9005 |
| Overvoltage category | III |
| Degree of pollution | 2 |
| Mounting type | on base element |
| Type | Male |
| Number of positions | 5 |
| Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
| Arrester can be tested with CHECKMASTER from software version: | From SW rev. 1.10 |
Protective circuit
| IEC test classification | C1 |
|---|---|
| C2 | |
| C3 | |
| D1 | |
| Nominal voltage UN | 12 V DC |
| Maximum continuous voltage UC | 14 V DC |
| 9.8 V AC | |
| Rated current | 450 mA (45°C) |
| Operating effective current ICat UC | ≤ 5 µA |
| Residual current IPE | ≤ 5 µA (with PT 2X2-BE) |
| ≤ 1 µA (with PT 2X2+F-BE) | |
| Nominal discharge current In(8/20) µs (line-line) | 10 kA |
| Nominal discharge current In(8/20) µs (line-earth) | 20 kA (in total) |
| Pulse discharge current Iimp(10/350) µs | 2.5 kA |
| Total discharge current Itotal(8/20) µs | 20 kA |
| Max. discharge current Imax(8/20) µs maximum (line-line) | 10 kA |
| Max. discharge current Imax(8/20) µs maximum (line-earth) | 20 kA (in total) |
| Nominal pulse current Ian (10/1000) µs (line-line) | 67 A |
| Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 55 V |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 55 V (with PT 2X2-BE) |
| ≤ 700 V (with PT 2X2+F-BE) | |
| Output voltage limitation at 1 kV/µs (line-line) static | ≤ 25 V |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 25 V (with PT 2X2-BE) |
| ≤ 40 V (with PT 2X2+F-BE) | |
| Residual voltage at In(line-line) | ≤ 25 V |
| Residual voltage at In(line-earth) | ≤ 40 V (with PT 2X2-BE) |
| Residual voltage at In(line-signalground) | ≤ 25 V (with PT 2X2-BE) |
| Residual voltage with Ian (10/1000) µs (line-line) | ≤ 25 V |
| Residual voltage with Ian (10/1000) µs (line-signalground) | ≤ 25 V |
| Voltage protection level Up(line-line) | ≤ 80 V (C1 - 1 kV/500 A) |
| ≤ 100 V (C2 - 10 kV / 5 kA) | |
| ≤ 50 V (C3 - 25 A) | |
| ≤ 80 V (6 kV / 3 kA) | |
| Voltage protection level Up(line-earth) | ≤ 85 V (C1 - 1 kV / 500 A with PT 2X2-BE) |
| ≤ 140 V (C2 - 10 kV / 5 kA with PT 2X2-BE) | |
| ≤ 100 V (6 kV / 3 kA with PT 2X2-BE) | |
| ≤ 50 V (C3 - 25 A with PT 2X2-BE) | |
| Voltage protection level Up(line-signalground) | ≤ 50 V (C3 - 25 A with PT 2X2-BE) |
| ≤ 140 V (C2 - 10 kV / 5 kA with PT 2X2-BE) | |
| Voltage protection level Upstatic (line-line) | ≤ 25 V (C2 - 10 kV / 5 kA) |
| ≤ 27 V (C3 - 25 A) | |
| Voltage protection level Upstatic (line-earth) | ≤ 45 V (C2 - 10 kV / 5 kA with PT 2X2-BE) |
| ≤ 27 V (C3 - 25 A with PT 2X2-BE) | |
| Voltage protection level Upstatic (line-signalground) | ≤ 25 V (C2 - 10 kV / 5 kA with PT 2X2-BE) |
| ≤ 27 V (C3 - 25 A) | |
| Response time tA | ≤ 500 ns |
| Input attenuation aE, sym. | typ. 0.3 dB (≤ 5 MHz / 100 Ω) |
| Cut-off frequency fg (3 dB), sym. in 100 Ohm system | typ. 60 MHz |
| Capacity (line-line) | typ. 30 pF |
| Resistance in series | 2.2 Ω ±10 % |
| Surge protection fault message | none |
| Max. required back-up fuse | 500 mA (T) |
| Impulse durability (line-line) | C2 - 10 kV/5 kA |
| C3 - 67 A | |
| Impulse durability (line-earth) | C2 - 10 kV/5 kA |
| C3 - 67 A | |
| D1 - 2.5 kA |
Connection data
| Connection method | Screw connection (in connection with the base element) |
|---|---|
| Screw thread | M3 |
| Tightening torque | 0.8 Nm |
| Stripping length | 8 mm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |