View larger
PT 2X2-HF-24 DC-ST 2839729 PHOENIX CONTACT Surge protection plug
PT 2X2-HF-24 DC-ST
2839729
PHOENIX CONTACT
10 Pcs.
Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
This PT 2X2-HF-24 DC-ST 2839729 PHOENIX CONTACT surge protection plug provides robust transient suppression for high-frequency signal circuits in automated plants. Engineers implement these pluggable modules in control enclosures to protect communication lines and sensitive instrumentation from the hazards of electrical surges.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Nominal voltage AC (EF008798): 24 V
More info
▲Key Commercial Data
| Orderkey | 2839729 |
|---|---|
| Packing unit | 10 pc |
| Catalog page | Page 161 (C-4-2017) |
| GTIN | 4017918607210 |
| Weight per Piece (excluding packing) | 22.320 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
General
| Housing material | PA |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | black |
| Standards for cearances and creepage distances | DIN VDE 0110-1 |
| IEC 60664-1 | |
| Mounting type | on base element |
| Type | Male |
| Number of positions | 5 |
| Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
| Arrester can be tested with CHECKMASTER from software version: | From SW rev. 1.00 |
Protective circuit
| IEC test classification | C1 |
|---|---|
| C2 | |
| C3 | |
| D1 | |
| VDE requirement class | C1 |
| C2 | |
| C3 | |
| D1 | |
| Nominal voltage UN | 24 V DC |
| Maximum continuous voltage UC | 28 V DC |
| 19.8 V AC | |
| Rated current | 450 mA (45°C) |
| Operating effective current ICat UC | ≤ 5 µA |
| Residual current IPE | ≤ 4 µA (with PT 2X2-BE) |
| ≤ 1 µA (with PT 2X2+F-BE) | |
| Nominal discharge current In(8/20) µs (line-line) | 10 kA |
| Nominal discharge current In(8/20) µs (line-earth) | 10 kA |
| Pulse discharge current Iimp(10/350) µs | 2.5 kA |
| Total discharge current Itotal(8/20) µs | 20 kA |
| Max. discharge current Imax(8/20) µs maximum (line-line) | 10 kA |
| Max. discharge current Imax(8/20) µs maximum (line-earth) | 10 kA |
| Nominal pulse current Ian (10/1000) µs (line-line) | 30 A |
| Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 120 V |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 450 V |
| ≤ 1 kV (with PT 2X2+F-BE) | |
| Output voltage limitation at 1 kV/µs (line-line) static | ≤ 45 V |
| Output voltage limitation at 1 kV/µs (line-signalground) static | ≤ 450 V |
| Residual voltage at In(line-line) | ≤ 40 V |
| Residual voltage with Ian (10/1000) µs (line-line) | ≤ 50 V |
| Voltage protection level Up(line-line) | ≤ 120 V (C2 - 10 kV / 5 kA) |
| Voltage protection level Up(line-earth) | ≤ 450 V (C2 - 10 kV / 5 kA) |
| Response time tA(line-line) | ≤ 500 ns |
| Response time tA(line-earth) | ≤ 500 ns |
| Input attenuation aE, sym. | 0.2 dB (≤ 5 MHz) |
| Input attenuation aE, asym. | |
| Cut-off frequency fg (3 dB), sym. in 100 Ohm system | typ. 70 MHz |
| Capacity (line-line) | typ. 30 pF |
| Resistance in series | 2.2 Ω |
| Surge protection fault message | none |
| Max. required back-up fuse | 500 mA (T) |
| Impulse durability (line-line) | C2 - 10 kV/5 kA |
| Impulse durability (line-earth) | C2 - 10 kV/5 kA |
| D1 - 2.5 kA |
Connection data
| Connection method | Screw connection (in connection with the base element) |
|---|---|
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |