View larger
PT 4X1-48AC-ST 2804856 PHOENIX CONTACT Surge protection plug
PT 4X1-48AC-ST
2804856
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Phoenix Contact PT 4X1-48AC-ST surge protection plug provides modular overvoltage defense for multi-channel signal applications. Units of this designation are frequently applied in control cabinets to secure industrial machinery against electrical disturbances. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Nominal voltage DC (EF008799): 48 V
More info
▲Key Commercial Data
| Orderkey | 2804856 |
|---|---|
| Packing unit | 10 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 113 (C-4-2017) |
| GTIN | 4046356339865 |
| Weight per Piece (excluding packing) | 25.950 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Dimensions
| Height | 45 mm |
|---|---|
| Width | 17.7 mm |
| Depth | 52 mm |
| Horizontal pitch | 1 Div. |
| Complete module height | 90 mm |
| Complete module width | 17.7 mm |
| Complete module depth | 65.5 mm |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 85 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Degree of protection | IP20 |
General
| Housing material | PA 6.6 |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | jet black RAL 9005 |
| Mounting type | on base element |
| Type | Male |
| Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
| Arrester can be tested with CHECKMASTER from software version: | From SW rev. 3.17 |
Protective circuit
| IEC test classification | C1 |
|---|---|
| C2 | |
| C3 | |
| D1 | |
| Nominal voltage UN | 48 V AC |
| Maximum continuous voltage UC | 77 V DC |
| 55 V AC | |
| Rated current | 300 mA (45°C) |
| Operating effective current ICat UC | ≤ 5 µA |
| Residual current IPE | ≤ 1 µA (with PT 4X1+F-BE) |
| ≤ 20 µA (Directly grounded) | |
| Nominal discharge current In(8/20) µs (line-earth) | 10 kA |
| Pulse discharge current Iimp(10/350) µs | 2.5 kA (per path) |
| Total discharge current Itotal(8/20) µs | 20 kA |
| Max. discharge current Imax(8/20) µs maximum (line-earth) | 10 kA (per path) |
| 20 kA (in total) | |
| Nominal pulse current Ian (10/1000) µs (line-earth) | 12 A |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 110 V (with PT 4X1-BE) |
| ≤ 600 V (with PT 4X1+F-BE) | |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 50 V (with PT 4X1+F-BE) |
| Residual voltage at In(line-earth) | ≤ 160 V (spike) |
| ≤ 110 V (static) | |
| Residual voltage with Ian (10/1000) µs (line-signalground) | ≤ 125 V |
| Voltage protection level Up(line-earth) | ≤ 150 V (C2 - 10 kV / 5 kA with PT 4X1-BE) |
| Voltage protection level Upstatic (line-earth) | ≤ 40 V (C2 - 10 kV / 5 kA with PT 4X1-BE) |
| Response time tA (line-signalground) | ≤ 1 ns (with PT 4X1+F-BE) |
| Response time tA(line-earth) | ≤ 1 ns (with PT 4X1-BE) |
| ≤ 100 ns (with PT 4X1+F-BE) | |
| Input attenuation aE, asym. | 0.5 dB (≤ 2.5 MHz / 50 Ω) |
| 0.2 dB (≤ 0.5 MHz / 150 Ω) | |
| 0.1 dB (≤ 0.1 MHz / 600 Ω) | |
| Cut-off frequency fg (3 dB), asym. (PE) in 50 Ohm system | typ. 10 MHz |
| Cut-off frequency fg (3 dB), asym. (PE) in 150 Ohm system | typ. 3.5 MHz |
| Cut-off frequency fg (3 dB), asym. (PE) in 600 Ohm system | typ. 900 kHz |
| Capacity (line-earth) | typ. 400 pF (with PT 4X1-BE) |
| typ. 2 pF (with PT 4X1+F-BE) | |
| Resistance in series | 4.7 Ω ±10 % |
| Surge protection fault message | none |
| Max. required back-up fuse | 315 mA (T) |
| Impulse durability (line-earth) | C2 - 10 kV/5 kA |
| D1 - 2.5 kA |
Connection data
| Connection method | Screw connection (in connection with the base element) |
|---|---|
| Screw thread | M3 |
| Tightening torque | 0.5 Nm |
| Stripping length | 8 mm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |