View larger
PT 1X2-48DC-ST 2803658 PHOENIX CONTACT Surge protection plug
PT 1X2-48DC-ST
2803658
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Acting as a surge protection plug, the Phoenix Contact PT 1X2-48DC-ST 2803658 shields vital measurement equipment and instrumentation lines from hazardous voltage surges. Pluggable design features allow for straightforward maintenance and rapid replacement within industrial control panel assemblies. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Nominal voltage DC (EF008799): 48 V
More info
▲Key Commercial Data
| Orderkey | 2803658 |
|---|---|
| Packing unit | 10 pc |
| Catalog page | Page 98 (C-4-2017) |
| GTIN | 4046356299268 |
| Weight per Piece (excluding packing) | 19.750 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Dimensions
| Height | 45 mm |
|---|---|
| Width | 17.7 mm |
| Depth | 52 mm |
| Horizontal pitch | 1 Div. |
| Complete module height | 90 mm |
| Complete module width | 17.7 mm |
| Complete module depth | 65.5 mm |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 85 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Degree of protection | IP20 |
General
| Housing material | PA 6.6 |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | jet black RAL 9005 |
| Mounting type | on base element |
| Type | Male |
| Number of positions | 2 |
| Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
| Arrester can be tested with CHECKMASTER from software version: | From SW rev. 3.15 |
Additional descriptions
| Note | Technical data is valid in association with the following specified base elements: |
|---|---|
| PT 1X2+F-BE 2856126 | |
| PT 1X2-BE 2856113 |
Protective circuit
| IEC test classification | C1 |
|---|---|
| C2 | |
| C3 | |
| D1 | |
| Nominal voltage UN | 48 V DC |
| Maximum continuous voltage UC | 53 V DC |
| 37 V AC | |
| Rated current | 450 mA (45°C) |
| Operating effective current ICat UC | ≤ 5 µA |
| Residual current IPE | ≤ 2 µA (with PT 1X2-BE) |
| ≤ 1 µA (with PT 1X2+F-BE) | |
| Nominal discharge current In(8/20) µs (line-line) | 10 kA |
| Nominal discharge current In(8/20) µs (line-earth) | 10 kA |
| Pulse discharge current Iimp(10/350) µs | 2.5 kA |
| Total discharge current Itotal(8/20) µs | 20 kA |
| Max. discharge current Imax(8/20) µs maximum (line-line) | 10 kA |
| Max. discharge current Imax(8/20) µs maximum (line-earth) | 20 kA (in total) |
| Nominal pulse current Ian (10/1000) µs (line-line) | 18 A |
| Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 70 V |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 450 V (with PT 1X2-BE) |
| ≤ 1 kV (with PT 1X2+F-BE) | |
| Output voltage limitation at 1 kV/µs (line-line) static | ≤ 70 V |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 25 V (with PT 1X2-BE) |
| ≤ 50 V (with PT 1X2+F-BE) | |
| Voltage protection level Up(line-line) | ≤ 80 V (C1 - 1 kV/500 A) |
| ≤ 85 V (C2 - 2 kV/1 kA) | |
| ≤ 120 V (C2 - 10 kV / 5 kA) | |
| Voltage protection level Up(line-earth) | ≤ 450 V (C1 - 1 kV / 500 A with PT 1X2-BE) |
| ≤ 550 V (C2 - 2 kV / 1 kA with PT 1X2-BE) | |
| ≤ 600 V (C2 - 10 kV / 5 kA with PT 1X2-BE) | |
| ≤ 800 V (C1 - 1 kV / 500 A with PT 1x2+F-BE) | |
| ≤ 900 V (C2 - 2 kV / 1 kA with PT 1x2+F-BE) | |
| ≤ 1000 V (C2 - 10 kV / 5 kA with PT 1X2+F-BE) | |
| Response time tA(line-line) | ≤ 1 ns |
| Response time tA(line-earth) | ≤ 100 ns |
| Input attenuation aE, sym. | typ. 0.5 dB (≤ 2 MHz / 50 Ω) |
| typ. 0.2 dB (≤ 600 kHz / 150 Ω) | |
| Cut-off frequency fg (3 dB), sym. in 50 Ohm system | typ. 10 MHz |
| Cut-off frequency fg (3 dB), sym. in 150 Ohm system | typ. 3.5 MHz |
| Capacity (line-line) | typ. 1 nF |
| Capacity (line-earth) | typ. 4 pF (with PT 1X2-BE) |
| typ. 2 pF (with PT 1X2+F-BE) | |
| Resistance in series | 2.2 Ω ±10 % |
| Surge protection fault message | none |
| Max. required back-up fuse | 500 mA (T) |
| Impulse durability (line-line) | C1 - 1 kV/500 A |
| C2 - 2 kV/1 kA | |
| C2 - 10 kV/5 kA | |
| Impulse durability (line-earth) | C1 - 1 kV/500 A |
| C2 - 2 kV/1 kA | |
| C2 - 10 kV/5 kA | |
| D1 - 2.5 kA |
Connection data
| Connection method | Screw connection (in connection with the base element) |
|---|---|
| Screw thread | M3 |
| Tightening torque | 0.5 Nm |
| Stripping length | 8 mm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
Standards and Regulations
| Standards/specifications | IEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012 |
|---|---|
| EN 61643-21 2001 + A1:2009 + A2:2013 |