View larger
PT 4X1-24AC-ST 2838351 PHOENIX CONTACT Surge protection plug
PT 4X1-24AC-ST
2838351
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Protecting delicate control loops from unexpected voltage surges, the Phoenix Contact PT 4X1-24AC-ST 2838351 PHOENIX CONTACT Surge protection plug is an essential component for industrial automation hardware. These specialized modules are commonly deployed in control cabinets to absorb electrical transients and safeguard signal integrity across complex automation infrastructure.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Nominal voltage DC (EF008799): 24 V
More info
▲Key Commercial Data
| Orderkey | 2838351 |
|---|---|
| Packing unit | 10 pc |
| Catalog page | Page 113 (C-4-2017) |
| GTIN | 4017918182731 |
| Weight per Piece (excluding packing) | 22.140 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Dimensions
| Height | 45 mm |
|---|---|
| Width | 17.7 mm |
| Depth | 52 mm |
| Horizontal pitch | 1 Div. |
| Complete module height | 90 mm |
| Complete module width | 17.7 mm |
| Complete module depth | 65.5 mm |
General
| Housing material | PA 6.6 |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | jet black RAL 9005 |
| Standards for cearances and creepage distances | VDE 0110-1 |
| IEC 60664-1 | |
| Mounting type | on base element |
| Type | Male |
| Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
| Arrester can be tested with CHECKMASTER from software version: | From SW rev. 1.00 |
Protective circuit
| IEC test classification | C1 |
|---|---|
| C2 | |
| C3 | |
| D1 | |
| VDE requirement class | C1 |
| C2 | |
| C3 | |
| D1 | |
| Nominal voltage UN | 24 V AC |
| Maximum continuous voltage UC | 40 V DC |
| 28 V AC | |
| Rated current | 300 mA (45°C) |
| Operating effective current ICat UC | ≤ 5 µA |
| Residual current IPE | ≤ 1 µA (with PT 4X1+F-BE) |
| ≤ 20 µA (Directly grounded) | |
| Nominal discharge current In(8/20) µs (line-earth) | 10 kA |
| Pulse discharge current Iimp(10/350) µs | 2.5 kA (per path) |
| Total discharge current Itotal(8/20) µs | 20 kA |
| Max. discharge current Imax(8/20) µs maximum (line-earth) | 10 kA |
| Nominal pulse current Ian (10/1000) µs (line-earth) | 23 A |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 60 V |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 55 V |
| Residual voltage at In(line-earth) | ≤ 55 V |
| Voltage protection level Up(line-earth) | ≤ 100 V (C2 - 10 kV / 5 kA) |
| Response time tA(line-earth) | ≤ 1 ns |
| Input attenuation aE, asym. | 0.5 dB (≤ 1.5 MHz) |
| Cut-off frequency fg (3 dB), asym. (PE) in 50 Ohm system | typ. 8 MHz |
| Cut-off frequency fg (3 dB), asym. (PE) in 150 Ohm system | typ. 3 MHz |
| Cut-off frequency fg (3 dB), asym. (PE) in 600 Ohm system | typ. 800 kHz |
| Capacity (line-earth) | 1.1 nF |
| Resistance in series | 4.7 Ω 10 % |
| Surge protection fault message | none |
| Max. required back-up fuse | 315 mA (T) |
| Impulse durability (line-earth) | C2 - 10 kV/5 kA |
| D1 - 2.5 kA |
Standards and Regulations
| Standards/regulations | IEC 61643-21 |
|---|---|
| DIN EN 61643-21 | |
| UL 497B | |
| Standards/specifications | IEC 61643-21 2000 |