View larger
OTTA 2,5-PE 0790556 PHOENIX CONTACT Ground modular terminal block
OTTA 2,5-PE
0790556
PHOENIX CONTACT
50 Pcs.
Automation > Ground terminal block
Enclosures connectivity
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The OTTA 2,5-PE ground modular terminal block manufactured by Phoenix Contact provides robust protective conductor termination for high-requirement electrical distribution boards. Grounding blocks ensure system safety by cleanly diverting unexpected electrical faults away from sensitive control hardware.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 0790556
- Packing unit: 50 pc
- Catalog page: Page 533 (C-1-2017)
- GTIN: 4017918005665
- Weight per Piece (excluding packing): 26.000 g
- Custom tariff number: 85369010
- Country of origin: IN (India)
- Number of levels: 1
- Number of connections: 2
- Nominal cross section: 2.5 mm²
- Color: green-yellow
- Insulating material: PA
- Flammability rating according to UL 94: V2
- Rated surge voltage: 8 kV
- Degree of pollution: 3
- Overvoltage category: III
More info
▲Key Commercial Data
| Orderkey | 0790556 |
|---|---|
| Packing unit | 50 pc |
| Catalog page | Page 533 (C-1-2017) |
| GTIN | 4017918005665 |
| Weight per Piece (excluding packing) | 26.000 g |
| Custom tariff number | 85369010 |
| Country of origin | IN (India) |
General
| Number of levels | 1 |
|---|---|
| Number of connections | 2 |
| Nominal cross section | 2.5 mm² |
| Color | green-yellow |
| Insulating material | PA |
| Flammability rating according to UL 94 | V2 |
| Rated surge voltage | 8 kV |
| Degree of pollution | 3 |
| Overvoltage category | III |
| Insulating material group | I |
| Connection in acc. with standard | IEC 60947-7-2 |
| Nominal current IN | 17.5 A |
| Nominal voltage UN | 500 V |
| Open side panel | No |
| Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
| Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 130 °C |
| Static insulating material application in cold | -60 °C |
| Behavior in fire for rail vehicles (DIN 5510-2) | Test passed |
| Flame test method (DIN EN 60695-11-10) | V0 |
| Oxygen index (DIN EN ISO 4589-2) | >32 % |
| NF F16-101, NF F10-102 Class I | 2 |
| NF F16-101, NF F10-102 Class F | 2 |
| Surface flammability NFPA 130 (ASTM E 162) | passed |
| Specific optical density of smoke NFPA 130 (ASTM E 662) | passed |
| Smoke gas toxicity NFPA 130 (SMP 800C) | passed |
| Calorimetric heat release NFPA 130 (ASTM E 1354) | 28 MJ/kg |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
Dimensions
| Length | 43.5 mm |
|---|---|
| Width | 10 mm |
| Height NS 35/7,5 | 45.5 mm |
| Height NS 35/15 | 53 mm |
| Height NS 32 | 50.5 mm |
Connection data
| Connection method | Bolt connection |
|---|---|
| Conductor cross section solid min. | 0.1 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.1 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 26 |
| Conductor cross section AWG max. | 14 |
| Conductor cross section flexible, with ferrule with plastic sleeve min. | 0.2 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve max. | 2.5 mm² |
| Cable lug connection according to standard | DIN 46234 |
| Min. cross section for cable lug connection | 0.1 mm² |
| Max. cross section for cable lug connection | 2.5 mm² |
| Hole diameter, min. | 3.2 mm |
| Cable lug width, max. | 7.6 mm |
| Bolt diameter | 3 mm |
| Cable lug connection according to standard | DIN 46237 |
| Min. cross section for cable lug connection | 0.5 mm² |
| Max. cross section for cable lug connection | 2.5 mm² |
| Hole diameter, min. | 3.2 mm |
| Cable lug width, max. | 7.6 mm |
| Bolt diameter | 3 mm |
| Screw thread | M3 |
| Tightening torque, min | 0.6 Nm |
| Tightening torque max | 0.8 Nm |
Standards and Regulations
| Connection in acc. with standard | CSA |
|---|---|
| IEC 60947-7-2 | |
| Flammability rating according to UL 94 | V2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
Environmental Product Compliance
| REACh SVHC | 4-Nonylphenol, ethoxylated |
|---|---|
| Lead 7439-92-1 | |
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |