PHOENIX CONTACT PTTBS 2,5-PE/L PTTBS 2,5-PE/L 3209621 PHOENIX CONTACT Protective conductor double-level terminal block View larger
Images are for illustrative purposes only. Please refer to data sheet for details

PTTBS 2,5-PE/L 3209621 PHOENIX CONTACT Protective conductor double-level terminal block

PTTBS 2,5-PE/L

3209621

PHOENIX CONTACT

50 Pcs.

Protective conductor double-level terminal block Double-deck terminal block with protective conductor, nominal voltage: 500 V, nominal current: 24 A, connection type: Push-in connection, 1st and 2nd floor, Sizing cross-section: 2.5 mm², cross-section: 0.14 mm² - 4 mm², mounting class: NS 35/7.5, NS 35/15, color: gray Multi-level terminal block, nom. voltage: 500 V, nominal current: 24 A, connection method: Push-in connection, 1st and 2nd level, Rated cross section: 2.5 mm2, cross section: 0.14 mm2 - 4 mm2, mounting type: NS 35/7,5, NS 35/15, color: gray

Automation > Ground terminal block
Modular TBs

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

This Phoenix Contact PTTBS 2,5-PE/L 3209621 PHOENIX CONTACT Protective conductor double-level terminal block operates as a ground terminal block configured to save panel space by integrating multiple connection tiers within a compact footprint. Multi-level terminal blocks manage high-density signal and power routing in modern industrial control cabinets.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Product type: Ground terminal block
  • Pitch: 5.2 mm
  • Number of connections: 4
  • Number of rows: 2
  • Data management status Article revision: 10
  • Insulation characteristics Overvoltage category: III
  • Degree of pollution: 3
  • Rated surge voltage: 6 kV
  • Maximum power dissipation for nominal condition: 0.77 W
  • Grounding foot: Yes
  • Number of connections per level: 2
  • Nominal cross section: 2.5 mm²
  • 1st and 2nd level Note: Please observe the current carrying capacity of the DIN rails.
  • Stripping length: 10 mm
  • Internal cylindrical gage: A3
  • Connection in acc. with standard: IEC 60947-7-1/IEC 60947-7-2

More info

▲
Technical data

Product properties
Product typeGround terminal block
Pitch5.2 mm
Number of connections4
Number of rows2
Data management status
Article revision10
Insulation characteristics
Overvoltage categoryIII
Degree of pollution3

Electrical properties
Rated surge voltage6 kV
Maximum power dissipation for nominal condition0.77 W

Connection data
Grounding footYes
Number of connections per level2
Nominal cross section2.5 mm²
1st and 2nd level
NotePlease observe the current carrying capacity of the DIN rails.
Stripping length10 mm
Internal cylindrical gageA3
Connection in acc. with standardIEC 60947-7-1/IEC 60947-7-2
Conductor cross section rigid0.14 mm² ... 4 mm²
Cross section AWG26 ... 12 (converted acc. to IEC)
Conductor cross section flexible0.14 mm² ... 4 mm²
Conductor cross section, flexible [AWG]26 ... 12 (converted acc. to IEC)
Conductor cross-section flexible (ferrule without plastic sleeve)0.14 mm² ... 2.5 mm²
Flexible conductor cross section (ferrule with plastic sleeve)0.14 mm² ... 2.5 mm²
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve0.5 mm²
Nominal current24 A
Maximum load current30 A (with 4 mm² conductor cross section, rigid)
Nominal voltage500 V
Nominal cross section2.5 mm²
1st and 2nd level Connection cross sections directly pluggable
Conductor cross section rigid0.34 mm² ... 4 mm²
Conductor cross-section flexible (ferrule without plastic sleeve)0.34 mm² ... 2.5 mm²
Flexible conductor cross section (ferrule with plastic sleeve)0.34 mm² ... 2.5 mm²

Dimensions
Width5.2 mm
End cover width2.2 mm
Height78 mm
Depth on NS 35/7,554.5 mm
Depth on NS 35/1562 mm
Pitch5.2 mm

Material specifications
Colorgray (RAL 7042)
Flammability rating according to UL 94V0
Insulating material groupI
Insulating materialPA
Static insulating material application in cold-60 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))125 °C
Relative insulation material temperature index (Elec., UL 746 B)130 °C
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26HL 1 - HL 3
Calorimetric heat release NFPA 130 (ASTM E 1354)27,5 MJ/kg
Surface flammability NFPA 130 (ASTM E 162)passed
Specific optical density of smoke NFPA 130 (ASTM E 662)passed
Smoke gas toxicity NFPA 130 (SMP 800C)passed

Electrical tests
Surge voltage test
Test voltage setpoint7.3 kV
ResultTest passed
Temperature-rise test
Requirement temperature-rise testIncrease in temperature ≤ 45 K
ResultTest passed
Short-time withstand current 2.5 mm²0.3 kA
Short-time withstand current 4 mm²0.48 kA
ResultTest passed
Power-frequency withstand voltage
Test voltage setpoint1.89 kV
ResultTest passed

Mechanical properties
Mechanical data
Open side panelYes

Mechanical tests
Mechanical strength
ResultTest passed
Test for conductor damage and slackening
Rotation speed10 rpm
Revolutions135
Conductor cross section/weight0.14 mm² / 0.2 kg
2.5 mm² / 0.7 kg
4 mm² / 0.9 kg
ResultTest passed

Environmental and real-life conditions
Aging
Temperature cycles192
ResultTest passed
Needle-flame test
Time of exposure30 s
ResultTest passed
Oscillation/broadband noise
SpecificationDIN EN 50155 (VDE 0115-200):2008-03
SpectrumService life test category 2, bogie-mounted
Frequencyf1= 5 Hz to f2= 250 Hz
ASD level6.12 (m/s²)²/Hz
Acceleration3.12g
Test duration per axis5 h
Test directionsX-, Y- and Z-axis
ResultTest passed
Shocks
SpecificationDIN EN 50155 (VDE 0115-200):2008-03
Pulse shapeHalf-sine
Acceleration30g
Shock duration18 ms
Number of shocks per direction3
Test directionsX-, Y- and Z-axis (pos. and neg.)
ResultTest passed
Ambient conditions
Ambient temperature (operation)-60 °C ... 110 °C (Operating temperature range incl. self-heating; for max. short-term operating temperature, see RTI Elec.)
Ambient temperature (storage/transport)-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Ambient temperature (assembly)-5 °C ... 70 °C
Ambient temperature (actuation)-5 °C ... 70 °C
Permissible humidity (operation)20 % ... 90 %
Permissible humidity (storage/transport)30 % ... 70 %

Standards and regulations
Connection in acc. with standardIEC 60947-7-1/IEC 60947-7-2

Mounting
Mounting typeNS 35/7,5
NS 35/15

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.