Control room architectures utilize the Phoenix Contact CT 10-2/2-GS/3E-110AC magazine to organize and house multi-line surge protection modules securely. Signal magazines provide structured terminal management while maintaining effective circuit defense across complex networks. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Nominal voltage AC (EF008798): 110 V
More info
▲Key Commercial Data
| Orderkey | 2920829 |
|---|---|
| Packing unit | 10 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 168 (C-4-2017) |
| GTIN | 4046356181822 |
| Weight per Piece (excluding packing) | 75.000 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -25 °C ... 75 °C |
|---|---|
| Altitude | ≤ 2000 mm (amsl (above mean sea level)) |
| Degree of protection | IP20 |
General
| Housing material | PBT |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | gray |
| Standards for cearances and creepage distances | VDE 0110-1 |
| IEC 60664-1 | |
| Mounting type | On CT-TERMIBLOCK and LSA-PLUS disconnect strip |
| Type | LSA-PLUS module |
| Number of positions | 20 |
| Direction of action | Line-Line & Line-Earth Ground |
Protective circuit
| IEC test classification | C2 |
|---|---|
| C3 | |
| D1 | |
| Nominal voltage UN | 110 V AC |
| Maximum continuous voltage UC | 60 V DC |
| 130 V AC | |
| Rated current | 1.5 A AC (per path) |
| 150 mA DC (per path) | |
| Operating effective current ICat UC | ≤ 1 µA (per path) |
| Residual current IPE | ≤ 20 µA |
| Nominal discharge current In(8/20) µs (line-earth) | 5 kA |
| Pulse discharge current Iimp(10/350) µs (line-earth) | 2.5 kA |
| Nominal pulse current Ian (10/1000) µs (line-earth) | 100 A |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 500 V |
| Response time tA(line-earth) | ≤ 100 ns |
| Capacity (line-earth) | typ. 5 pF |
| Resistance in series | ≤ 10 mΩ |
| Surge protection fault message | none |
| Impulse durability (line-earth) | C2 - 10 kV/5 kA |
| C3 - 100 A | |
| D1 - 2.5 kA | |
| Alternating current carrying capacity (line-earth) | 10 A - 1 s |
Connection data
| Connection method | can be plugged into COMTRAB-TERMIBLOCK and LSA-PLUS disconnect and switching strips |
|---|---|
| Connection method IN | COMTRAB plug-in system |
| Connection method OUT | COMTRAB plug-in system |
| Connection technology | LSA-PLUS |
Standards and Regulations
| Standards/specifications | IEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012 |
|---|---|
| EN 61643-21 2001 + A1:2009 + A2:2013 |