Designed for installation in potentially explosive locations, the Phoenix Contact MACX MCR-EX-T-UIREL-UP-SP is a specialized temperature measuring transducer that provides reliable signal conditioning and relay switching capabilities. These devices are deployed in process control systems to monitor critical thermal thresholds and safely isolate field instrumentation from control electronics.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Measuring range (EF001836): -250 °C
- Analogue output 0 mA ... 20 mA (EF006808): No
- Analogue output 4 mA ... 20 mA (EF006810): Yes
- Analogue output 0 V ... 2 V (EF009886): No
- Analogue output 0 V ... 5 V (EF009887): No
- Analogue output 0 V ... 10 V (EF006807): No
- Analogue output 2 V ... 10 V (EF009888): No
- With switching output (EF005225): Yes
- EMC-version (EF001062): Yes
- Ambient temperature (EF002386): 65 °C
- Weight (EF000167): 0.2 kg
More info
▲Key Commercial Data
| Orderkey | 2924799 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 150 (C-5-2017) |
| GTIN | 4046356629096 |
| Weight per Piece (excluding packing) | 200.000 g |
| Custom tariff number | 85437090 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -20 °C ... 65 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Maximum altitude | ≤ 2000 m |
| Permissible humidity (operation) | typ. 5 % ... 95 % (non-condensing) |
| Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
| Shock | 15g, according to IEC 60068-2-27 |
| Vibration (operation) | 5g, accordance to IEC 60068-2-6 |
Input data
| Sensor types (RTD) that can be used | Pt, Ni, Cu sensors: 2, 3, 4-wire |
|---|---|
| Sensor types that can be used (TC) | B, E, J, K, N, R, S, T, L, U, CA, DA, A1G, A2G, A3G, MG, LG |
| Temperature measuring range | -250 °C ... 2500 °C (Range depending on the sensor type) |
| Input signal range | 0 Ω ... 50 kΩ |
| Potentiometer resistance range | 0 Ω ... 50 kΩ |
| Input signal range | -1000 mV ... 1000 mV |
Output data
| Configurable/programmable | Yes |
|---|---|
| Max. voltage output signal | ± 11 V |
| Current output signal | 4 mA ... 20 mA (in the case of SIL; further free configuration without SIL) |
| Max. current output signal | 22 mA |
| Load/output load voltage output | ≥ 10 kΩ |
| Load/output load current output | ≤ 600 Ω (at 20 mA) |
| Behavior in the event of a sensor error | according to NE 43 or freely configurable |
| Output name | Relay output |
| Configurable/programmable | no |
| Contact type | 3 PDTs |
| Contact material | AgSnO2, hard gold-plated |
| Maximum switching voltage | 250 V AC (250 V DC) |
| Maximum inrush current | 2 A (250 V AC) |
| 2 A (28 V DC) | |
| Mechanical service life | 1x 105cycles |
Power supply
| Supply voltage range | 24 V ... 230 V AC/DC (-20 %/+10 %, 50/60 Hz) |
|---|---|
| Typical current consumption | < 100 mA (24 V DC) |
| Power consumption | < 2.4 W |
Connection data
| Conductor cross section solid min. | 0.2 mm² |
|---|---|
| Conductor cross section solid max. | 1.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 1.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 16 |
| Stripping length | 8 mm |
| Connection method | Push-in connection |
General
| Maximum transmission error | 0.1 % (e.g. for Pt 100, 300 K span, 4 ... 20 mA) |
|---|---|
| Maximum temperature coefficient | 0.01 %/K |
| Step response (0–99%) | typ. 1000 ms (With SIL) |
| typ. 700 ms (Without SIL) | |
| Status display | Green LED (supply voltage, PWR) |
| Red LED, flashing (line, sensor error, ERR) | |
| Red LED (module error, ERR) | |
| Yellow LED (switching output) | |
| Flammability rating according to UL 94 | V0 |
| Degree of pollution | 2 |
| Overvoltage category | II |
| Electromagnetic compatibility | Conformance with EMC directive |
| Housing material | PA 6.6-FR |
| Color | gray |
| Designation | Input/output/power supply |
| Electrical isolation | 2.5 kV (50 Hz, 1 min., test voltage) |
| Designation | Input/output |
| Electrical isolation | 375 V (Peak value in accordance with EN 60079-11) |
| Designation | Input/power supply |
| Electrical isolation | 375 V (Peak value in accordance with EN 60079-11) |
| Designation | Input/switching output |
| Electrical isolation | 375 V (Peak value in accordance with EN 60079-11) |
| Designation | Output/supply |
| Electrical isolation | 300 Vrms(Rated insulation voltage (overvoltage category II; degree of pollution 2, safe isolation as per EN 61010-1)) |
| Conformance | CE-compliant |
| ATEX | II (1) G [Ex ia Ga] IIC |
| II (1) D [Ex ia Da] IIIC | |
| II 3 G Ex nA nC ic IIC T4 Gc X | |
| IECEx | [Ex ia Ga] IIC |
| [Ex ia Da] IIIC | |
| Ex nA nC ic IIC T4 Gc X | |
| UL, USA/Canada | UL 508 Listed |
| SIL | 2 |
Safety data
| Max. internal inductance Li | negligible |
|---|---|
| Max. internal capacitance Ci | 44 nF |
| Max. output voltage Uo | 6 V |
| Max. output current Io | 7.4 mA |
| Max. output power Po | 11 mW |
| Group | IIC |
| Max. external inductivity Lo | 100 mH |
| Max. external capacity Co | 1.3 µF |
| Group | IIC |
| Max. external inductivity Lo | 10 mH |
| Max. external capacity Co | 1.7 µF |
| Group | IIC |
| Max. external inductivity Lo | 1 mH |
| Max. external capacity Co | 2.6 µF |
| Group | IIB |
| Max. external inductivity Lo | 100 mH |
| Max. external capacity Co | 6.8 µF |
| Group | IIB |
| Max. external inductivity Lo | 10 mH |
| Max. external capacity Co | 9.2 µF |
| Group | IIB |
| Max. external inductivity Lo | 1 mH |
| Max. external capacity Co | 15 µF |
| Safety-related maximum voltage Um | 253 V AC/DC |
EMC data
| Designation | Electromagnetic RF field |
|---|---|
| Standards/regulations | EN 61000-4-3 |
| Typical deviation from the measuring range final value | 2 % |
| Designation | Fast transients (burst) |
| Standards/regulations | EN 61000-4-4 |
| Typical deviation from the measuring range final value | 2 % |
| Designation | Conducted interferences |
| Standards/regulations | EN 61000-4-6 |
| Typical deviation from the measuring range final value | 2 % |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC directive |
|---|---|
| Designation | Electromagnetic RF field |
| Standards/regulations | EN 61000-4-3 |
| EN 61000-4-4 | |
| Designation | Conducted interferences |
| Standards/regulations | EN 61000-4-6 |
| Electrical isolation | 4-way, between input/output/power supply/switching output |
| Flammability rating according to UL 94 | V0 |
| Shock | 15g, according to IEC 60068-2-27 |
| Vibration (operation) | 5g, accordance to IEC 60068-2-6 |
| Conformance | CE-compliant |
| ATEX | II (1) G [Ex ia Ga] IIC |
| II (1) D [Ex ia Da] IIIC | |
| II 3 G Ex nA nC ic IIC T4 Gc X | |
| IECEx | [Ex ia Ga] IIC |
| [Ex ia Da] IIIC | |
| Ex nA nC ic IIC T4 Gc X | |
| UL, USA/Canada | UL 508 Listed |
| DNV GL-Temperature | B |
| DNV GL-Humidity | B |
| DNV GL-Vibration | A |
| DNV GL-EMC | A |
| DNV GL-Enclosure | Required protection according to the Rules shall be provided upon installation on board |
| Group | IIC |
| IIC | |
| IIC | |
| IIB | |
| IIB | |
| IIB |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |